Page 11

Software Configuration DX-9100 Software Elements

Version 3 Only

Configuration Tools

The DX-9100 is a microprocessor-based programmable controller. It has the following software elements: • eight analog input modules

• eight digital input modules

• two analog output modules in Version 1; eight analog output modules in Versions 2 and 3

• six digital output modules

• up to 64 additional inputs/outputs from up to 8 extension modules

• twelve programmable function modules with algorithms for control and calculation

• eight analog constants and 32 digital constants

• one programmable logic control module with 64 logic result statuses

• eight time schedule modules

• two optimal start/stop modules

• sixteen network analog input modules

• eight network digital input modules

• sixteen network analog output modules

• eight network digital output modules

A user configures the controller using the GX-9100 Graphic Software Configuration Tool. The SX-9120 Service Module is used to troubleshoot and adjust individual parameters. Techniques for both tools are described in the following sections. For complete documentation on both tools, see the GX-9100 Software Configuration Tool User’s Guide and the SX-9120 Service Module User’s Guide in FAN 636.4 or 1628.4. Following is a brief description of the main features of the GX-9100 Software Configuration Tool. Note that the term, click on, means to position the cursor on the module or menu and then press the appropriate mouse button to select it. Note: When using the GX Tool, after entering a parameter, always click on OK to confirm. Configuration Guides - DX-9100 Configuration Guide

11

Page 12

Entering Data into Modules

To enter data into a module displayed on the screen of the GX Tool, place the cursor on the module, click once on the right mouse button and the module menu will appear: Data... Delete Connect...

F5

Disconnect...

F4

Show Selected Show User Names dxcon004

Figure 4: Module Menu Place the cursor on Data and press either mouse button. A Data Window appears containing all module data. Use the <Tab> key or mouse to move the cursor from field to field. To make an entry, move the cursor to the entry field and type in the information. To go to the second page in the Data Window (if there is one), click on the Data-2 field. To return to the first page, click on OK or Cancel. To exit a window, click on OK to confirm entries, or Cancel to discard them, while in the first page. Entering Values

The following table shows the accuracy that may be lost due to rounding errors. Numbers with a modulus of greater that 2047 may be rounded up or down by 0.1% as follows: Table 2: Rounding Errors Range

Rounding (+/-)

2048-4095

2

4096-8191

4

8192-16383

8

16384-32767

16

The rounding is due to the external communications bus protocol and does not compromise the precision of the internal control processes.

12

Configuration Guides - DX-9100 Configuration Guide

Page 13

Entering User Names

The Data Window contains User Name and Description entry fields. Up to 8 characters may be entered in the User Name field, and the Description field can have up to 24 characters. The Data Window also contains an Output Tag field for module outputs (i.e., source points), which can be connected to another module as inputs (destinations) and an Input Tag field for module inputs. To enter User Names for outputs, position the cursor over the Output Tag field and press the left mouse button once. To enter User Names for inputs, select the Input Tag field.

Making Connections

To expand a module displayed on the screen of the GX Tool, in order to view input/output connections, place the cursor over the module and double-click on the left mouse button. Input connections appear in the left column with @ attached to the Tag Name, and output connections are shown in the right column, except for output modules where all connections appear in one column. To close a module, place the cursor over the expanded module and double-click on the left mouse button. Connections are made using one of the four methods outlined below. Note that only the first method is referred to later in this guide. An existing connection must be disconnected before making a new connection. •

The first method is to expand the source and destination modules by moving the cursor to each module in turn and double-clicking the left mouse button. Move the cursor over the desired output of the source module and the cursor appears as an output arrow. Hold down the left mouse button and drag the arrow to the desired destination input. When the left mouse button is released, a connection line will be drawn between the two modules.

•

The second method is to select the source module by positioning the cursor over the module and pressing the left mouse button and then the <F5> key. A list of the possible source output connections for that module will be shown. Move the cursor to the desired output to select it (it will appear highlighted) and click on OK (alternatively, double-click on the desired output). To complete the connection, select the destination module by pressing the left mouse button and then the <F5> key. A list of the possible destination inputs for that module will be shown. Select the desired destination from the dialog box and click on OK (alternatively, double-click on the desired destination). A connection line will be drawn between the two modules.

Configuration Guides - DX-9100 Configuration Guide

13

Page 14

Configuring the Controller

•

The third method is to select the source module by positioning the cursor over it and pressing the right mouse button. The module menu will appear. Select Connect and a list of possible source outputs for that module will appear in a dialog box. Move the cursor to the desired output to select it (it will appear highlighted) and click on OK (alternatively, double-click on the desired output). Then select the destination module by positioning the cursor on it and pressing the right mouse button. The module menu will appear. Select Connect and a list of possible destination inputs for that module will be shown. Move the cursor to the desired input to select it and click on OK (alternatively, double-click on the desired input). A connection line will be drawn between the two modules.

•

The fourth method is to go to the destination module data window, move the cursor to a connection field, press the <*> key on the keyboard, and the available source output tags will be displayed for selection.

Configuring the controller involves: • defining characteristics and parameters of the input and output modules, the programmable function modules for control and calculation, the extension modules, and the programmable logic control module

• defining connections between the modules in order to achieve the desired sequence of control

• setting the time scheduling, optimal start/stop, and realtime clock parameters

Proceed in the following order: 1.

Select the controller type (Versions 1, 2, or 3).

2.

Define DX-9100 Global Data under the Edit menu.

3.

Define Job Information under the Edit menu.

4.

Define analog and digital input characteristics.

5.

Define analog and digital output characteristics.

6.

Define extension module structures and characteristics.

7.

When applicable, define network inputs and outputs for the Version 3 controller (LONWORKS Bus).

8.

Define programmable function module/algorithm characteristics.

9.

Define time schedule and exception day settings.

10. Define programmable logic control module.

14

Configuration Guides - DX-9100 Configuration Guide

Page 15

DX-9100 Controller Selection Via GX Tool

Via the SX Tool

Select the controller version under the Controller menu: •

DX Version 1.1, 1.2, 1.3, or

•

DX Version 1.4, or

•

DX Version 2.0, 2.1, 2.2, or

•

DX Version 2.3, 2.4 or

•

DX Version 3.0, 3.1, 3.2, or

•

DX Version 3.3 or 3.4

The SX Tool will display the controller type when first connected to the controller. No user selection is required.

DX-9100 Global Data Set Power Line Frequency (50 or 60 Hz)

Via the GX Tool

At the menu bar at the top of the screen, select Edit-Global Data and a window appears. Under Frequency, click on 50 or 60 Hz. Then click on OK to confirm the setting. (To discard an entry, click on Cancel.) Via the SX Tool

Under General Module, set bit X7 of Item DXS1 (RI.32):

Set Initialize on Power Up Flag

•

X7 = 0

50 Hz power line

•

X7 = 1

60 Hz power line

When this flag is set to cancel or 1, the override-type Items listed below are reset after each power up of the controller. When set to maintained or 0, these override-type Items are maintained through the power failure. •

Shutoff mode request

•

Startup mode request

•

Enable Digital Output (Triac) Supervisory Control

•

Set Digital Output (Triac) On

•

Output Hold mode (Analog and Digital)

•

Programmable Function Module Hold

•

Time Schedule Module Hold mode Configuration Guides - DX-9100 Configuration Guide

15

Page 16

Via the GX Tool

Select Edit-Global Data. Under Init. on Power Up, click on maintained or cancelled. Via the SX Tool

Under General Module, set bit X8 of Item DXS1 (RI.32): X8 = 0 No initialization on power up (commands from BAS maintained) X8 = 1 Initialization on power up (commands from BAS cancelled) Counter Type Flag

In the controller, four bytes are reserved for digital input counters and accumulators in programmable modules. When the DX-9100 is connected to a BAS, the counter type flag must be set to 0 because the system will only read 15 bits (maximum reading of 32,767). For BASs that can read four bytes, or for standalone applications, the flag may be set to 1. The counter will then read a maximum value of 9,999,999 and then reset to 0. See Supervisory Mode Control Settings (General Module) further in this document. Via the GX Tool

Select Edit-Global Data. Under Counter Type, click on one of the following: •

15-bit (BAS)

•

4-byte

Via the SX Tool

Under General Module, set in bit X4 of Item DXS1 (RS.32): X4 = 0 Selects 15-bit counters X4 = 1 Selects 4-bit counters Global Data Notes

For temperature unit selection, refer to the Analog Input Configuration section below. For daylight saving time, refer to the Time Program Functions section later in this document.

16

Configuration Guides - DX-9100 Configuration Guide

Page 17

Configuration Number (Version 1.1 or Later)

A configuration number may be entered for configuration identification purposes. The number will be displayed on the front panel of the controller during initialization. The configuration number is also read and used by the DX LCD Display to identify which of the display configurations in its database to use for this controller.

Via the GX Tool

Select Edit-Global Data. Enter the appropriate number in the User Config Code field.

Via the SX Tool

Under General Module, enter the appropriate number in Item ALG (RI.33).

Password Feature (Versions 1.4, 2.3, 3.3, or Later)

The password is used to protect a configuration when loaded into a controller. Once the password has been downloaded into the controller with the configuration, the controller will only allow a subsequent download or upload when the password is entered in the Download or Upload dialog box of the GX Software Configuration Tool. The password is encrypted by the GX Tool before download.

! WARNING:

If the password is lost and the user does not have access to the original configuration file that includes the password, then the controller must be returned to the supplier or the Johnson Controls factory to have the memory cleared.

IMPORTANT: A password of 0 disables the protection feature. The password feature is only available with firmware Versions 1.4, 2.3, 3.3, or later. In older versions, the password feature was not implemented. Note: The password feature is enabled by an entry in the GX9100.ini file of the GX Tool. The GX Tool software is delivered without this entry. Refer to the GX-9100 Software Configuration Tool User’s Guide (LIT-6364060) for details. Via the GX Tool

Select Edit-Global Data. Enter the password (one to four alphanumeric characters) in the Password field. Enter 0 if the password feature is not required. The default password is 0000.

Via the SX Tool

The password cannot be accessed via the SX Tool. A GX Tool must be used.

Configuration Guides - DX-9100 Configuration Guide

17

Page 18

Analog Input Configuration

The DX-9100 Controller can accept up to eight analog inputs, which are active (voltage or current) or passive (RTD). Each analog input is defined and configured by the following parameters: •

User Name and Description (GX only)

•

Input Signal/Range

•

Measurement Units

•

Enable Square Root

•

Alarm on Unfiltered Value

•

Alarm Limits

•

Filter Time Constant

AI: Input Signal and Ranging

Via the GX Tool

User Name and Description

Select AIn using the right mouse button. Then select Data in the module menu, and enter as appropriate:

To assign the input as active or passive, position the cursor on the appropriate box and double-click the left mouse button. Then position the cursor accordingly and click the left mouse button once to select either Active or Passive.

User Name (maximum 8 characters) Description (maximum 24 characters) For active inputs, at the Type of Active Input field, enter: 0 = 0-10 VDC 1 = 4-20 mA 2 = 0-20 mA

18

Configuration Guides - DX-9100 Configuration Guide

Page 19

Each analog input module performs the conversion of the input signal to a variable numeric value expressed in engineering units obtained using the high range and low range. High Range

(HR) = Enter the equivalent number for reading at high signal input (10 V, 20 mA)

Low Range

(LR) =

Enter the reading at low signal input

(0 V, 0 mA, 4 mA) AI =

(PR% / 100) * (HR - LR) + LR where: PR% = analog value in % of physical input signal

For passive inputs at the Type of Passive Input field, enter: 1 = Ni1000 (Johnson Controls characteristic) 2 = Ni1000 Extended Temperature Range (Johnson Controls characteristic) 3 = A99 (Johnson Controls characteristic)* 4 = Pt1000 (DIN characteristic) 5 = Ni1000 (L. & G. characteristic) (Firmware, Version 1.1 or later) 6 = Ni1000 (DIN characteristic) (Firmware, Version 1.1 or later) *Note: The North American Johnson Controls silicon sensors (TE-6000 series) have very similar characteristics to the A99 sensor. At 21°C (70°F) and 25°C (77°F) the reference values are identical. At -40°C (-40°F), the reading will be 0.8°C (1.5°F) high. At 38°C (100°F), the reading will be 0.3°C (0.5°F) high. For Resistance Temperature Device (RTD) inputs, the range of the displayed value is fixed according to the type of sensor. The high/low range entries will not have any effect on the actual sensor readout. The configured high and low ranges determine the control range of any control module to which it is connected. (The difference between the High Range value and the Low Range value is equivalent to a proportional band of 100%.) At the High/Low control range field, enter the required value: High Range (Control) = Low Range (Control) =

Configuration Guides - DX-9100 Configuration Guide

19

Page 20

Via the SX Tool

Under Analog Inputs configure Item AITn (RI.00): (Low Byte) X7 = 0

0-10 Volts

X7 = 1

0-20 mA, 0-2 V or RTD

X8 = 1

20% suppression (2-10 V or 4-20 mA)

(High Byte) X11 X10 X9

=

000

Active Sensor (Linear)

X11 X10 X9

=

001

Ni 1000 RTD Passive Sensor (Johnson Controls) (-45 to 121°C [-50 to 250°F])

X11 X10 X9

=

010

Ni 1000 RTD High Temperature Sensor (21 to 288°C [70 to 550°F])

X11 X10 X9

=

011

RTD Sensor A99 (Johnson Controls) (-50 to 100°C [-58 to 212°F])

X11 X10 X9

=

100

RTD Sensor Platinum 1000 (DIN) (-50 to 200°C [-58 to 392°F])

Version 1.1 or Later

X11 X10 X9

=

101

Ni 1000 RTD (L. & G.) (-50 to 150°C [-58 to 302°F])

X11 X10 X9

=

110

Ni 1000 RTD (DIN) (-50 to 150°C [-58 to 302°F])

For active inputs, the analog input module performs the conversion of the input signal to a variable numeric value expressed in engineering units obtained using the high range at Item HRn (RI.01) and low range at Item LRn (RI.02). For RTD passive inputs, the range of the displayed value is fixed according to the type of sensor. The configured range determines the control range of any control module to which it is connected. AI: Measurement Units

20

Via the GX Tool

To choose between Celsius and Fahrenheit for active and passive sensors, select Edit-Global Data. Under Temperature Units, select Celsius or Fahrenheit.

Configuration Guides - DX-9100 Configuration Guide