DX-9100 Extended Digital Plant Controller Introduction
This document covers all three versions of the DX-9100 Extended Digital Controller, including the DX-912x LONWORKS® version. They include: Version 1 – provides up to eight output modules, which are configured to give two analog outputs and six digital outputs (triacs). Version 2 – provides six additional analog output modules, giving a total of eight analog outputs. Version 3 – the DX-912x LONWORKS version brings peer-to-peer communication to the feature set of the Version 2 controller, and enhanced alarm reporting capability when used as an integral part of an Building Automation System (BAS). In this document, BAS is a generic term, which refers to the Metasys® Network, Companion™, and Facilitator™ supervisory systems. The specific system names are used when referring to system-specific applications. The DX-9100 is the ideal digital control solution for multiple chiller or boiler plant control applications, for the Heating, Ventilating, and Air Conditioning (HVAC) process of air handling units or for distributed lighting and related electrical equipment control applications. It provides precise Direct Digital Control (DDC) as well as programmed logic control. In a standalone configuration, the DX-9100 Controller has both the hardware and software flexibility to adapt to the variety of control processes found in its targeted applications. Along with its outstanding control flexibility, the controller can expand its input and output point capability by communicating with I/O Extension Modules on an expansion bus, and provides monitoring and control for all connected points via its built-in Light-Emitting Display (LED). Versions 1 and 2 can communicate on the N2 Bus as well as on the System 91 Bus*, providing point control to the full BAS Network or to the N30 system or Companion/Facilitator System. The Version 3 controller uses the LONWORKS (Echelon®) N2 Bus of the Metasys Control Module (NCM311 or NCM361 in Europe, NCM300 or NCM350 elsewhere) in place of the N2 Bus. *The terms System 91 Bus and Metasys Control Station are not used in North America.
Configuration Guides - DX-9100 Configuration Guide
5
Page 6
The DX-9100 has two packaging styles. In Version 1, all terminals for field wiring are located within the controller enclosure. Versions 2 and 3 require a separate field wiring mounting base or cabinet door mounting frame, which enables all field wiring to be completed before the controller is installed.
Figure 1: Version 1 (DX-9100-8154)
Figure 2: DX-9100-8454 (Version 2)/DX-912x-8454 (Version 3) with Mounting Base Note: The mounting base differs for DX-9120 and DX-9121.
6
Configuration Guides - DX-9100 Configuration Guide
Page 7
The DX-9100 processes the analog and digital input signals it receives, using twelve multi-purpose programmable function modules, a software implemented Programmable Logic Controller (PLC), time schedule modules, and optimal start/stop modules; producing the required outputs (depending on the module configuration), operating parameters, and programmed logic. Configuration of all versions of the DX-9100 Controller are achieved by using a Personal Computer (PC) with GX-9100 Graphic Configuration Software (Version 5 or later) supplied by Johnson Controls. Changes to the configuration can be made by using an SX-9120 Service Module (Version 3.1 or later). Versions 1 and 2 (N2 Bus)
The DX-9100 unit (Versions 1 and 2) has two communication links. One is called the N2 Bus or Bus 91 (the term Bus 91 is not used in North America) and is used to interface to a supervisory unit. The other link is called the XT Bus and is used to expand the DX-9100 input/output capability by interfacing up to eight XT-9100 or XTM-905 extension modules. The DX-9100 input/output can be extended by up to 64 remote input/outputs, analog or digital, depending on the type of the connected extension modules and XP expansion modules. Point connections are made on XP modules, which are monitored and controlled by the XT-9100 or XTM-905 modules. For more details, refer to the XT-9100 Technical Bulletin in the System 9100 Manual (FAN 636.4 or 1628.4). One XP module can provide either eight analog points or eight digital points. Two XP modules connected to one extension module provides eight analog and eight digital points, or sixteen digital points. Version 1 or 2 of the DX-9100 can be used as a standalone controller or it can be connected to a BAS through the RS-485 serial communications bus (N2 Bus or Bus 91).
Version 3 (LONWORKS N2 Bus)
Version 3 of the controller (DX-912x-8454) brings peer-to-peer communication to the feature set of the Version 2 controller, and enhanced alarm reporting capability when used as an integral part of a Metasys BAS Network. The new communications features are provided by the LONWORKS Network, which enables Version 3 controllers to pass data from one to another and to send event-initiated data to the NCM350 (NCM361 in Europe) Network Control Module, in the BAS. The LONWORKS (Echelon) N2 Bus is used in place of the N2 Bus, and the NCM300 or NCM350 (NCM311 or NCM361 in Europe) must be fitted with a LONWORKS (Echelon) driver card. The Version 3 controller retains all the input/output point and control capabilities of the Version 2 controller, including the point expansion feature using extension modules and expansion modules. Configuration Guides - DX-9100 Configuration Guide
7
Page 8
In addition to the Version 2 features, the Version 3 controller has network input and output points, which can be configured to transmit and receive data over the LONWORKS Bus. Each controller may have up to 16 network analog input modules, 16 network analog output modules, 8 network digital input modules, and 8 network digital output modules. While network analog input and output modules each contain a single analog value, the network digital input and output modules each contain 16 digital states, which are transmitted as a block between controllers. The transmission of point data is managed by the LONWORKS Network and is independent of the supervisory functions of the BAS Network Control Module (NCM). A network of Version 3 controllers can be installed to share analog and digital data between controllers on a peer-to-peer basis; a Network Control Module is not required unless the network is to be supervised by a BAS. Complex control strategies may now be performed in multiple DX-912x controllers without the need for network data exchange routines in a supervisory controller. Applications include the control of multiple, interdependent air handling units, and large hot water or chilled water generating plants with components distributed in various locations within the building. LONMARK Compatibility
The Version 3 controller has been approved as a LONMARK device and conforms to the LONMARK specification for network data transmission.
R
Figure 3: LONMARK Trademark Further information about compatibility and interoperability with other LONMARK devices may be requested from your local Johnson Controls office.
8
Configuration Guides - DX-9100 Configuration Guide
Page 9
Related Information
Refer to Table 1 for additional information on System 9100 controllers: Table 1: Related Information Document Title
Code Number
FAN
DX-9100 Extended Digital Controller Technical Bulletin
LIT-6364020
636.4, 1628.4
DX-9100 Configuration Guide
LIT-6364030
636.4, 1628.4
GX-9100 Software Configuration Tool User’s Guide
LIT-6364060
636.4, 1628.4
LONWORKS N2 Bus Technical Bulletin
LIT-6364100
636.4
XT-9100 Technical Bulletin
LIT-6364040 LIT-1628440
636.4 1628.4
XT-9100 Configuration Guide
LIT-6364050 LIT-1628450
636.4 1628.4
NDM Configurator Application Note
LIT-6364090 LIT-1628490
636.4 1628.4
Scheduling Technical Bulletin
LIT-636116
636
Point History Technical Bulletin
LIT-636112
636
SX-9100 Service Module User’s Guide
LIT-6364070 LIT-1628470
636.4 1628.4
Configuration Guides - DX-9100 Configuration Guide
9
Page 10
Hardware Configuration
For full details of the hardware configuration, refer to the DX-9100 Extended Digital Controller Technical Bulletin(LIT-6364020) and the XT-9100 Technical Bulletin (LIT-6364040). In summary, the DX-9100 has the following interfaces, inputs, and outputs:
Versions 1 and 2
•
One N2 Bus (Bus 91) RS-485 port for BAS communication
Version 3
•
One LONWORKS N2 Bus for BAS communication and peer-to-peer communication with other controllers on the same bus (maximum of 30 controllers on one LONWORKS Bus)
All Versions
•
One XT Bus (RS-485 port) for up to 8 extension modules and a maximum of 64 inputs/outputs
•
One port for service module (SX-9120) communication
•
Eight digital input ports for connection to voltage-free contacts
•
Eight analog input ports; the DX-9100 accepts 0-10 VDC or 0-20 mA signals from active sensors, or can be connected to Nickel 1000 (Johnson Controls or DIN standard), Pt1000, or A99 passive RTD sensors, as selected via jumpers on the circuit board
•
Six isolated triac digital outputs to switch external 24 VAC circuits with devices such as actuators or relays
Version 1
•
Two analog output ports, 0-10 VDC or 0-20 mA, as selected via jumpers on the circuit board; also, 4-20 mA may be selected by configuration
Versions 2 and 3
•
Four analog outputs, 0-10 VDC or 0-20 mA, as selected via jumpers on the circuit board; also, 4-20 mA may be selected by configuration
•
Four additional analog outputs, 0-10 VDC only
•
One RS-232-C port for local downloading and uploading software configurations (N2 Bus protocol)
The software configuration determines how these inputs and outputs are used, and their range and application. The DX-9100 must be supplied with a 24 VAC power source. All models are suitable for 50 Hz or 60 Hz through software configuration.
10