DX-9100 Configuration Guide: Software Configuration, pages 131 to 140

Pages 131 to 140 of 288, from DX-9100 Configuration Guide

The original document is the PDF (1.3 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Johnson Controls DX-9100

Page 131

Full Scale Limit

Via GX Tool

At the Full Scale Limit #n field, enter the required value. When the output reaches this value, the output will hold there until reset, or, if the Accumulated Total option is selected, the output will automatically be reset to 0 and the accumulated total for this channel will be incremented. Via SX Tool

The Full Scale Limits are entered at Alg. Items FSLn (RI.26 to RI.33), where n is equal to the channel number (1-8). Scale/Time Constant

Via GX Tool

At the Scale/Time Const #n field, enter the required value. For the Integrator, the value is in minutes. For Event, it is the number of On/Off transitions to count as one event. For Runtime, the value is in seconds; 60 would be runtime in minutes, 3600 would be runtime in hours. Note: Changing values after counts are already there will alter the totals accordingly. For example, if the Event scale was at 1 with 20 counts, and the Event scale was changed to 2, the counts would equal 10. Via SX Tool

The Scaling Factors/Time Constants are entered at Alg. Items FTCn (RI.34 to RI.41), where n is equal to the channel number (1-8). Increment Accumulated Total Function

Via GX Tool

At the Incrmnt ACC. #n (0=N) field, enter 1 or 0 (DX-9100 Version 1.1 or later.) This is the Increment Accumulated Total function. It is recommended that the Full Scale Limit should be set to 1,000, 100, or 10. Setting Increment ACC to 1 will enable the counter to count the number of times that the full scale limit is reached. The Accumulated Total is a 4-byte integer and can store up to 9,999,999 counts (32,767 when the Metasys option has been selected, under GLOBAL, Counter Type field). Via SX Tool

The Increment Accumulated Total function is defined by setting bit X8 in Alg. Item FUNn (n=1-8) (RI.02 to RI.09) as follows: X8 = 1

Increment ACTn and reset TOTn when FSSn = 1 (n=1-8) (Version 1.1 or later)

Configuration Guides - DX-9100 Configuration Guide

131

Page 132

When bit X8 is set to 0 (default) and the output reaches the Full Scale Limit FSLn, the algorithm function is frozen until reset. When bit X8 is set to 1 and the output reaches the Full Scale Limit FSLn, the totalized output is automatically reset to 0 and the Alg. Item ACTn (RI.73 to RI.80) is incremented by one count. Notes

GX Labels

1.

You can read and modify the totalized values from the DX front panel. See Display Panel and Keypads in the DX-9100 Extended Digital Controller Technical Bulletin (LIT-6364020) in FAN 636.4 or 1628.4.

2.

On the SX Tool, the output of each channel can be seen at Alg. Item TOTn (RI.60 to RI.67), and the Accumulated Total can be seen at Alg. Item ACTn (RI.73 to RI.80).

3.

On the SX Tool, each channel can be put in Hold mode by entering the value 1 at PM Item PMnHDC (n = 1-8) (RI.70); HLD1 is bit X1, HLD8 is bit X8. Its numeric (TOTn) output can be modified in the Hold mode by a BAS.

4.

The Full Scale Status of Channel #n can be seen at PM Item PMnST (n = 1-8) (RI.72); FSS1 is bit X1...FSS8 is bit X8. These logic variables can be used to signal an alarm or initiate a dial-up to notify an operator that a limit has been reached.

5.

A 1 on the Reset input forces the totalized output and the accumulated total to 0.

Source Points (Outputs)

PMnFSSm

A 1 when the output of a channel of a totalization module is at its full scale limit.

PMnHLDm A 1 when the channel of the program module has been overridden (in hold) from an SX service module or a BAS. PMnTOTm The totalized value of a totalization module channel; the number of events, runtime, or integration value. Destination Points (Inputs)

132

In@

Analog input connections to a programmable module.

RSn@

The connection to the reset function of a totalization module channel (to reset to 0 and re-start).

Configuration Guides - DX-9100 Configuration Guide

Page 133

Algorithm 21 Comparator

A Comparator Algorithm provides an eight-channel comparator algorithm. Each channel can be configured to perform the comparison of an analog input variable with a setpoint. A high limit, low limit, equality, or dynamic logic status is generated. Comparator functions: High Limit:

Logic Status

LSn = 1 when In >= SPn

LSn = 0 when In <= SPn - DFn

LS=1 Setpoint (SP) DF LS=0 dxcon023

Figure 21: Comparator High Limit Function Example Low Limit: Logic Status LSn = 1 when In <= SPn

LSn = 0 when In >= SPn + DFn

LS=0 Setpoint (SP)

LS=1

DF dxcon024

Figure 22: Comparator Low Limit Function Example

Configuration Guides - DX-9100 Configuration Guide

133

Page 134

Equality Status: Logic Status LSn = 1 when SPn - DFn < In < SPn + DFn

LSn = 0 when In < SPn - DFn or In > SPn + DFn

LS=0 Setpoint (SP)

LS=1

LS=1

DF DF

LS=0 dxcon025

Figure 23: Comparator Equality Status Function Example Dynamic Status: Logic Status

Function

LSn = 1 when In is changing more than the value of the differential (DFn) in one second.

LSn = 0 when In is changing less than the value of the differential (DFn) in one second.

Via the GX Tool

Click on PM in the toolbar, select Numeric, then Comparator and position the module (box) on the screen. Select the module and then Data to call up the Data Window. At the CHANNEL TYPE #n field, enter the value corresponding to the desired function: 0

= Channel Disabled

1

= High Limit

2

= Low Limit

3

= Equality Status

4

= Dynamic Status

Then enter the Setpoint and Differential values for each channel. At the Differential #n field, enter a fixed value. The Setpoint #n may be a fixed value or can be sourced from a numerical Item. Make connections between the source points and destination points In@ and SPn@, as applicable.

134

Configuration Guides - DX-9100 Configuration Guide

Page 135

Via the SX Tool

This algorithm is assigned to a programmable function module when the value 21 is configured in PM Item PMnTYP (RI.00). The bit structure of the Alg. Item FUNn (n = 1-8) (RI.02 to RI.09) defines the function of each channel of the algorithm: X3X2X1 = 000

Channel Disabled

X3X2X1 = 001

High Limit

X3X2X1 = 010

Low Limit

X3X2X1 = 011

Equality Status

X3X2X1 = 100

Dynamic Status

In@

Notes

= Analog Input Variable Connection for Channel #n (even numbers, RI.10 to RI.24)

n = 1-8

SPn@ = Setpoint value Variable Connection for Channel #n (odd numbers, RI.11 to RI.25)

n = 1-8

NCMn = Deviation (In - SPn) - Channel #n (RI.60 to RI.67)

n = 1-8

SPn

= Setpoint value (If SPn@ not connected) Channel #n (even numbers, RI.26 to RI.40)

n = 1-8

DFn

= Differential Channel #n (odd numbers, RI.27 to RI.41)

n = 1-8

1.

If there is no connection to Item SPn@, the module uses the setpoint value in Item SPn (even numbers, RI.26 to RI.40).

2.

On the SX Tool, each channel can be put in Hold mode by entering the value 1 at PM Item PMnHDC (RI.70); HLD1 = bit X1...HLD8 = bit X8. Its numeric output (NCMn) can be modified in the Hold mode by a BAS.

3.

The Logic Status of Channel #n can be seen at PM Item PMnST (RI.72); LS1 = bit X1...LS8 = bit X8.

4.

As the numeric output cannot be read at the DX front panel, it is recommended that this algorithm is used in the higher PM numbers, reserving the lower PM numbers for algorithms that can be displayed.

Configuration Guides - DX-9100 Configuration Guide

135

Page 136

GX Labels

Source Points (Outputs)

PMnHLDm A 1 when the channel of the program module has been overridden (in hold) from an SX service module or a BAS. PMnLSm

A 1 when the comparator module channel is at its comparison true logic state.

PMnNCMm The calculation result of a channel of a numeric module. Destination Points (Inputs)

Algorithm 22 Sequencer

In@

Analog input connections to a programmable module.

SPn@

A setpoint connection for a comparator channel if a remote setpoint is desired, otherwise the entered value for the setpoint will be used.

A Sequencer Algorithm provides the control of one to eight logic outputs as a function of the value of an analog source variable or two logic source variables (increase and decrease signals) and the state of eight logic (disable) inputs. A sequencer module may be chained to the next module in numerical sequence to provide control of 16 logic outputs in 1 sequencer algorithm. Each logic output represents one stage of the controlled load. The logic outputs or stages can be grouped into sets, each set having a definable number of stages. The sequencer module is used to control multi-stage equipment, maintaining minimum On/Off times, interstage delays, and sequencing loads. The sequencer can be interfaced to the PLC module and to other programmable function modules that provide control, interlocking, and alarm capability.

Function

Via the GX Tool

Click on PM in the toolbar and select Sequencer. For a Binary Code sequencer (see Configuring the Options), click on PM in the toolbar and select Binary Sequencer. Via the SX Tool

This algorithm is assigned to a programmable function module when value 22 is configured in PM Item PMnTYP (RI.00).

136

Configuration Guides - DX-9100 Configuration Guide

Page 137

Configuring the Options

Assumptions

The following configuration examples are based on these assumptions: •

Stg #1 first of = 3

•

LdFcfrStg#n = 33

•

Load Differential [%] = 33

•

Retroactive [0 = N] = 1]

Step Mode

The output stages are controlled in sequence according to the last on, first off principle. For example, a three stage sequencer controls the output stages in the following sequence: (0 = Off, 1 = On) Table 4: Step Mode Load Percent 0

33

66

100

66

33

0

Stage 1

0

1

1

1

1

1

0

Stage 2

0

0

1

1

1

0

0

Stage 3

0

0

0

1

0

0

0

Sequential Mode

The sets are controlled in sequence according to the first on, first off principle. Stages within a set are controlled to the last on, first off principle (like Step mode). For example, a three set sequencer controls the output sets in the following sequence: (0 = Off, 1 = On) Table 5: Sequential Mode Load Percent 0

33

66

100

66

33

0

Set 1

0

1

1

1

0

0

0

Set 2

0

0

1

1

1

0

0

Set 3

0

0

0

1

1

1

0

Equal Runtime

The On time of the first output stage of each set is totalized. In case of an increase of load requiring the activation of a new set, the set with the lowest On time will be switched on. In case of a decrease of load requiring the switching off of a stage in a set at full load, the set with the highest On time will be switched off first. Stages within a set are controlled to the last on, first off principle (Step mode). For example, a three set sequencer controls the output sets in the following sequence: (0 = Off, 1 = On). Configuration Guides - DX-9100 Configuration Guide

137

Page 138

Table 6: Runtime Increasing Load (Percent) Decreasing Load (Percent) Runtime 0 33 66 100 Runtime 100 66 33 0 Set 1

90 hours

0

0

0

1

95 hours

1

1

1

0

Set 2

40 hours

0

1

1

1

110 hours

1

0

0

0

Set 3

65 hours

0

0

1

1

99 hours

1

1

0

0

As the load increases, the set with a runtime of 40 hours starts first. As the load decreases, the set with a runtime of 110 hours stops first. Binary Code

The output stages must form one set and are controlled in sequence according to a binary code principle. For example, a three stage sequencer controls the output stages in the following sequence: Table 7: Binary Code Stage

0 kW

1 kW

2 kW

3 kW

4 kW

5 kW

6 kW

7 kW

1 (1 kW)

0

1

0

1

0

1

0

1

2 (2 kW)

0

0

1

1

0

0

1

1

3 (4 kW)

0

0

0

0

1

1

1

1

As load % increases ------------------------------> Notes: The Binary Code mode is intended for use only with electric heaters or other nonmechanical devices. The binary code sequencer will always select the appropriate stage combination for the requested output, with a stage delay between the changing of a stage combination. The sequencer will not step through successive combinations when a large change in requested output occurs. When the Binary Code mode is selected, the algorithm will automatically assign load factors that will summate to 100%, and the differential will be set to 20% of the minimum (first stage) load factor with a maximum of 3% of the total load.

138

Configuration Guides - DX-9100 Configuration Guide

Page 139

Via the GX Tool

Select the sequencer module and then Data to call up the Data Window. At the Sequen. Module mode field, enter the value that defines the desired mode: 0

= Disable

1

= Step mode

2

= Sequential

3

= Not Applicable (Use Binary Sequence for Binary Code)

4

= Equal Runtime

(For the binary sequence module, the Sequence Module mode is automatically set to binary code.) Via the SX Tool

The Algorithm mode is defined by bits X3 X2 X1 of PM Item PMnOPT (RI.01), as follows:

Analog Input Connection

X3 X2 X1 = 000

Disabled

X3 X2 X1 = 001

Step Mode

X3 X2 X1 = 010

Sequential

X3 X2 X1 = 011

Binary Code

X3 X2 X1 = 100

Equal Runtime

The analog control input determines the required output in percent of the total output, and would normally be the output of a PID module. The percent load factor for each output stage and the differential must be specified (see Configuring the Load Factors and Differential in this section), except for a Binary Code sequence, where the load factors are calculated automatically by the module. Via the GX Tool

Make a connection between the analog source point and the INC@ destination point, which also represents the analog input connection, in the sequencer module. Via the SX Tool

Set bit X8 of PM Item PMnOPT (RI.01) to 0 to define the input as analog. Connect the analog source point at Alg. Item INC@ (RI.18).

Configuration Guides - DX-9100 Configuration Guide

139

Page 140

Digital Input Connection

One digital control input increases the required output value and a second input decreases the output value. When digital inputs are connected, a Full Load Ramp Time (sec.) determines the time that the Increase Input must be On for the requested output to change from 0 to 100% or the Decrease Input must be On for the requested output to change from 100 to 0%. Via the GX Tool

Make a connection between the digital source point and the INC@ destination point. Also make a connection from the Decrease digital source point to the DEC@ destination point. Select the sequencer or binary sequencer module and then Data to call up the Data Window. Go to page 2. At the Full Load Rmp (sec) field, enter the value corresponding to the desired Full Load Ramp Time action. Via the SX Tool

Assign the input type by setting bit X8 of PM Item PMnOPT (RI.01) to 1 to define the input as digital. Enter the increase source point at Alg. Item INC@ (RI.18). Enter the decrease source point at Alg. Item DEC@ (RI.19). Set the Full Load Ramp Time at Alg. Item FLR (RI.44). Sequencer Control

The sequencer control is either proactive or retroactive. Proactive

The first stage selected by the sequencer is always On unless the Fast Step Down input is active. The second stage is switched On when the first stage is at its load factor, the third stage when the second stage is at its load factor, and so on. This mode is normally required for equipment with its own modulating control, for example, centrifugal refrigeration compressors.

Switched Load

3

Each Load = 20%

1 0

20

40

60

Requested Load % dxcon026

Figure 24: Proactive Sequencer 140

Configuration Guides - DX-9100 Configuration Guide