Page 141

Retroactive

The first stage is not switched On until the required load is equal to its load factor. Each subsequent stage is not switched until its load factor is required. This mode is normally required for equipment without modulating control, for the control of electric heaters, for example.

Switched Load 3 Each Load = 20% 2

1 0

20

40

60

Requested Load % dxcon027

Figure 25: Retroactive Sequencer Control Via the GX Tool

Select the sequencer module and then Data to call up the Data Window. Go to page 2. At the Retroactive (0=N) field, enter 0 for Proactive, or 1 for Retroactive. (A binary sequencer module is automatically set to Retroactive.) Via the SX Tool

Bit X9 of PM Item PMnOPT defines the Sequencer Control mode as follows: X9 = 0

Proactive Control

X9 = 1

Retroactive Control

Configuration Guides - DX-9100 Configuration Guide

141

Page 142

Configuring the Sets and Stages

This setting configures the number of stages in each set. For example, when the first set contains three stages, NST1 (Stg 1 first of ) is defined as 3, and NST2 (Stg 2 first of ) and NST3 (Stg 3 first of ) are defined as 0. A second set is then defined by NST4 (Stg 4 first of) with the required stages for that set, and the following Alg. Items NSTn in numerical sequence are defined as 0, and so on, until all required stages are defined. A binary code sequence will only operate on the first set as defined by NST1.In Version 1.1 or later; an option is available to reverse the action of all stages within sets, except the first stages. When this option is enabled, all stages within a set are switched on when the first stage of a set is switched on, and then the second and subsequent stages are switched off as the load increases. As the load decreases, stages are switched on again. A set cannot be switched off until all its stages are on. This option is applicable to chiller compressor control where the stages are connected to unloader solenoids. Via the GX Tool

Select the sequencer module and then Data to call up the Data Window. At the Stg #n first of field, enter a value to determine the number of stages in the set. If there are no sets, enter 1 at each Stg #n first of field for the number of individual stages needed. At the Invert Stgs in set field on page 2, enter 1 to reverse the action of stages in sets. For a binary sequencer module, select the binary sequencer module, and then Data to call up the Data Window. At the Number of Stages field, enter the number of outputs to be controlled as one binary coded set. Via the SX Tool

Enter the appropriate values at Alg. Item NSTn (n = 1-8) (RI.02 to RI.09). The reverse stages in sets option is defined in bit X6 of PM Item PMnOPT as follows:

142

X6

=0 Direct Stages in Sets

All stages are switched On for increasing load.

X6

=1 Invert Stages in Sets

Stages within a set are switched On when the set is On and switched Off for increasing load.

Configuration Guides - DX-9100 Configuration Guide

Page 143

Configuring the Disable Conditions

This setting configures the disable condition connections for the sequencer. When a stage is disabled by its connection being equal to 1, the sequencer will immediately switch off the stage and automatically select the next available stage according to the Sequencer mode defined. When any stage of a set is disabled, the complete set is considered as disabled and all stages are immediately switched off, and the sequencer will automatically select the next available set. Therefore, only the first stage needs to be disabled in order to disable all stages within a set. A disabled condition in a Binary Code sequencer will disable the sequencer operation. If a stage (or set) is disabled, the sequencer will use the load factors assigned to the enabled stages to run the sequencer. Via the GX Tool

Make connections between the logic source points and the DISn@ disable points in the sequencer module. In the binary sequencer module make a connection between the logic source point and the DIS@ disable point. Via the SX Tool

To disable an output stage, enter the address of a logic variable at Alg. Item DISn@ (n = 1-8) (RI.10 to RI.17). Configuring the Load Factors and Differential

The load factor of each stage is entered as a percentage of the maximum load required from all stages controlled by the sequencer module. The sum of the load factors of the stages may be greater than 100% if the controlled plant has standby capacity. For example, if a plant comprises five units where the maximum required load is provided by four units, and one unit acts as a standby, the load factor of each unit (stage) is set at 25%. If the units are not of equal capacity, the appropriate load factors (as a percentage of the maximum required load) may be entered and the algorithm will always switch the appropriate number of units available (i.e., those which are not disabled and have not exceeded their maximum switching cycles limit) to meet the required load. The load differential must normally be less than the minimum load factor entered for any stage. If the load differential is greater than the load factor of the first stage in a set, that set may not switch off at 0% load in Retroactive Control mode, and more than one stage may remain on at 0% load in Proactive Control mode. This can be avoided in Step mode by setting the load factor of the first stage at a higher value than the load differential, because in Step mode the first stage is always the last to be switched off in the sequence. (In other modes, any stage or set could be the last to be switched off because the algorithm changes the order of operation.)

Configuration Guides - DX-9100 Configuration Guide

143

Page 144

When the binary code option is selected, the algorithm will automatically assign load factors, which will summate to 100%, and the differential will be set to 20% of the minimum (first stage) load factor with a maximum of 3% of the total load. Via the GX Tool

Select the sequencer module and then Data to call up the Data Window. Go to page 2. At the Ld Fctr Stg #n (%) field, enter the percent for each stage that has been defined. At the Load Diffrntial (%) field, enter a value to determine the differential between successive on and off operations. Via the SX Tool

The output load factor is defined by Alg. Item OLFn (n = 1-8) (RI.26 to RI.33). The differential between successive on and off operations is set in Alg. Item LDF (RI.45). Configuring the Timers

A series of delay times have to be defined to control the sequencing steps. A set or stage cannot be switched until the delay time of the previous set or stage has expired. Note: The sequencer module will only switch one set or stage during each program cycle, which occurs every second. Therefore, the minimum effective time delay between sets or stages is one second. Time values of less than one second will result in a delay time of one second. Via the GX Tool

Select the sequencer module and then Data to call up the Data Window. Go to page 2. Set the following values (in seconds): First set on delay: Delay between the first and second stages of the first set, or delay between the first and second set if the first set has only one stage.

144

Stage on delay:

Delay between stages, and delay between the last stage of one set and the first stage of the next set.

Set on delay:

Delay between stage one and stage two of a set other than the first set, or delay between sets other than the first set if the sets have only one stage.

Stage off delay:

Off delay between stages.

Configuration Guides - DX-9100 Configuration Guide

Page 145

Set off delay:

Off delay between the last stage to be switched off one set and the first stage to be switched off the next set, or off delay between sets if the sets only have one stage.

At the Minimum On Time (sec) field, enter a value . It defines the time in seconds that a stage must be On before it may be switched Off. At the Minimum Off Time (sec) field, enter a value. It defines the time in seconds that a stage must be Off before it may be switched On. If the Minimum On Time and Minimum Off Time are only applied to the first stages in each set, then at the Min On/Off for set field, enter a 1. For a BIN SEQ, select DATA and set Interstage Delay (in seconds). Via the SX Tool

Define the sequencing timing control as follows: T1 First Set On Delay

[sec.]

(RI.34)

T2 Stage On Delay

[sec.]

(RI.35)

T3 Set On Delay

[sec.]

(RI.36)

T4 Stage Off Delay

[sec.]

(RI.37)

T5 Set Off Delay

[sec.]

(RI.38)

The Minimum On Time for a stage or set is defined by Alg. Item TON (RI.41). It defines the time in seconds that a stage must be On before it may be switched Off. The Minimum Off Time for a stage or set is defined by Alg. Item TOFF (RI.42). It defines the time in seconds that a stage must be Off before it may be switched On. If bit X7 of PM Type PMnOPT (RI.01) is set to 1, the Items TON and TOFF will only be applied to the first stage in a set and not to the other stages in the same set (if any). A Binary Code sequencer does not use the Minimum On and Off time parameter.

Configuration Guides - DX-9100 Configuration Guide

145

Page 146

Configuring Maximum Switching Cycles

The sequencer algorithm controls the starting of the first stage in each set such that the number of starts in one hour does not exceed the defined Maximum Switching Cycles value (MAXC). The algorithm does this by calculating the minimum time between start commands using the formula: 3600 sec./MAXC. The first stage in a set is effectively locked out and prevented from restarting within this period of time. This time is typically longer than the Minimum Off Time. When operating in Step or Sequential mode, the sequencer will wait for a set to become available again after a previous start command. In Equal Runtime mode, a set that is unavailable will be skipped and the set with the next lowest runtime will be selected. In a Binary Code sequencer, the MAXC parameter is not used. Via the GX Tool

Select the sequencer module and then Data to call up the Data Window. At the Max Switch Cycl/hr field, enter a value for cycles per hour. For example, if equal to 6, a stage will only be allowed one start every ten minutes. Via the SX Tool

The maximum number of switching cycles allowed for the first stage of each set in one hour is defined by Alg. Item MAXC (RI.43). Configuring Fast Step Down

A digital input connection will initiate a Fast Step Down cycle of the sequencer. The Fast Step Down cycle is controlled by a Fast Step Down Stage Delay and a Fast Step Down Set Delay. The Fast Step Down cycle does not respect the Minimum On Time parameter. Once the procedure is activated, it cannot be interrupted until the switching-off sequence is completed and all stages are off. The Fast Step Down connection is also used to switch off the final proactive load in the sequence when the plant is shut down. Via the GX Tool

Make a connection between the Fast Step Down logic source point and the FST@ input in the sequencer or binary sequencer module. Select the module and then Data to call up the Data Window. Enter values (in seconds) for the following fields: Fast Step Dwn (Stg): Off delay between stages. Fast Step Dwn (Set): Off delay between the last stage to be switched off of one set and the first stage to be switched off of the next set, or off delay between sets if the sets only have one stage. 146

Configuration Guides - DX-9100 Configuration Guide

Page 147

Via the SX Tool

A digital input connected to Alg. Item FSD@ (RI.20) initiates the Fast Step Down cycle of the sequencer. The Fast Step Down cycle is controlled by the Fast Step Down Stage Delay T4F (RI.39) and the Fast Step Down Set Delay T5F (RI.40). Notes

1.

You can view and override the sequencer output value and totalized runtime (in hours) of each stage using the DX front panel. See Display Panel and Keypads in the DX-9100 Extended Digital Controller Technical Bulletin (LIT-6364020) in FAN 636.4 or 1628.4.

2.

The output status of each stage can be seen on the SX Tool at PM Item PMnDO (RI.71) bits X1 to X8.

3.

The requested load can be seen on the SX Tool at Alg. Item OUT (RI.60).

4.

The output difference of the algorithm can be seen on the SX Tool at Alg. Item OUTD (RI. 61). It represents the required load minus the sum of the loads of all stages that are On. It can be used to control a modulating device between the switching of stages to provide continuous control over the complete range (sometimes referred to as Vernier control).

5.

The sum of the loads of all stages that are On can be seen on the SX Tool at Alg. Item OUTS (RI.62).

6.

The runtime (in hours) of each stage can be seen on the SX Tool at Alg. Item RTn (n = 1-8) (RI.73 to RI.80).

7.

The sequencer module can be put in Hold mode by entering the value 1 in Alg. Item PMnHDC (RI.70, bit X1). The requested output Alg. Item OUT can be modified in the Hold mode by a BAS.

8.

The output disabled status (1 for Disabled) of each stage can be seen on the SX Tool at Alg. Item PMnST (RI.72, bits X1 to X8).

9.

The status of the maximum switching cycles per hour timer for each stage can be seen at Alg. Item PMnST (RI.72, bits X9 to X16).

10. When a stage is switched on, the respective bit is set to 1 to indicate that it cannot be switched on again until its timer expires (if it is the first stage in a set).

Configuration Guides - DX-9100 Configuration Guide

147

Page 148

11. A sequencer module may be chained to the next programmable function module (in numerical sequence) by setting bit X16 in the PM Item PMnOPT (RI.01) to 1. (For GX: Select the sequencer module and then Data to call up the Data Window. In the Chain Next PM (0=N) field, enter 0 for No, 1 for Yes.) When a sequencer module is chained, the next programmable function module must be defined as a sequencer module where Stages 1-8 will act as Stages 9-16 and use the same data for Items INC@, DEC@ and FSD@, T1 - T5, T4F and T5F, TON, TOF, MAXC, FLR, and LDF in the first module. Only NSTn, OLFn, and DISn@ are required in the second module and its outputs OUT, OUTD, and OUTS have no meaning. (In the GX Tool only: Stage# first of, Output Load Fctr, and Disable are required.) GX Labels

Source Points (Outputs)

PMnHLD

A 1 when the program module is in the Hold mode, being overridden by the SX Tool or a BAS.

PMnMCSm A 1 as long as the maximum cycles status timer for an output stage is active. PMnOUT

The analog value of the requested output load % (percent) of a sequencer.

PMnOUTD

The output difference between the required load minus the sum of the loads of stages that are On in a Sequencer mode. This can be used for Vernier control.

PMnSTOm

A 1 when the staged output of a sequencer module is requested to be On.

Destination Points (Inputs)

148

DEC@

The connection to decrement an analog type output, PAT/DAT digital type output or a sequencer module. While connection is a logic 1, the output will decrease at a rate dependent on the type of module.

DISn@

A connection in a sequencer to disable the corresponding stage or set number.

FST@

The connection to set the sequencer module into Fast Step Down mode.

INC@

The connection to increment an analog type output, PAT/DAT digital type output or a sequencer module. While connection is a logic 1, the output will increase at a rate dependent on the type of module.

Configuration Guides - DX-9100 Configuration Guide

Page 149

Configuration Examples

The following examples show a sequencer with eight stages, subdivided into one set of two stages and two sets of three stages: Via the GX Tool

Stage 1 first of = 2

Stage 5 first of = 0

Stage 2 first of = 0

Stage 6 first of = 3

Stage 3 first of = 3

Stage 7 first of = 0

Stage 4 first of = 0

Stage 8 first of = 0

The sequencer is defined by connecting an analog source point to INC@. Proactive control is defined by entering 0 under the Retroactive (0=N) field on page 2. The output load factors are defined (in percentages) as follows: Ld Fctr Stg 1 (%) = 10

Ld Fctr Stg 5 (%) = 10

Ld Fctr Stg 2 (%) = 10

Ld Fctr Stg 6 (%) = 20

Ld Fctr Stg 3 (%) = 10

Ld Fctr Stg 7 (%) = 20

Ld Fctr Stg 4 (%) = 10

Ld Fctr Stg 8 (%) = 10

The Load Differential is set to 2% via Load Diffrntial (%) = 2 field. Via the SX Tool

Alg. Items NSTn (RI.02 to RI.09) must be defined as follows: NST1 = 2

NST5 = 0

NST2 = 0

NST6 = 3

NST3 = 3

NST7 = 0

NST4 = 0

NST8 = 0

The sequencer is defined with an analog input connected to INC@ (X8 = 0), and Stage 1 is On at 0% load (proactive control X9=0). The output load factors OFL 1 to 8 (RI.26 to RI.33) are defined as follows: OLF1 = 10

OLF5 = 10

OLF2 = 10

OLF6 = 20

OLF3 = 10

OLF7 = 20

OLF4 = 10

OLF8 = 10

The differential LDF (RI.45) is defined as 2%.

Configuration Guides - DX-9100 Configuration Guide

149

Page 150

INC in % 100 90

OLF8 = 10%

LDF = 2%

OLF7 = 20% 70 50 40 30 20 10 0 Input FSD=0 Stages NST1 = 2 NST2 = 0

OLF6 = 20% OLF5 = 10% OLF4 = 10% OLF3 = 10% OLF2 = 10% OLF1 = 10% Time Input FSD = 1 T1

T5

1 T2

Set 1

T4

2 T5

T3

3 NST3 = 3 NST4 = 0 NST5 = 0

T4

T2

Set 2

4 T4

T2

5 T3

T5

6 NST6 = 3 NST7 = 0 NST8 = 0

T4

T2

7 T2

Set 3

T4

8 Delay Period After Switching dxcon028

Figure 26: Sequencer Module Example 1, Step Mode

150

Configuration Guides - DX-9100 Configuration Guide