DX-9100 Configuration Guide: Software Configuration, pages 151 to 160

Pages 151 to 160 of 288, from DX-9100 Configuration Guide

The original document is the PDF (1.3 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Johnson Controls DX-9100

Page 151

INC in % 100 90

OLF8 = 10%

LDF=2%

OLF2=2% OLF1=10% OLF5=10% OLF4=10% OLF3=10% OLF8=10%

80 70 60 50 40 30

OLF7 = 20% OLF6 = 20% OLF5 = 10% OLF4 = 10% OLF3 = 10% OLF2 = 10% OLF1 = 10%

OLF7=20%

20 10 0 Input FSD=0 Stages

NST1 = 2 NST2 = 0

OLF6=20% Time Input FSD=1

T5

T1

1

Set 1

T4

T2

2 T5

T3

3 T4

T2

NST3 = 3 NST4 = 0 NST5 = 0

Set 2

4 T4

T2

5

T5

T3

6 NST6 = 3 NST7 = 0 NST8 = 0

T4

T2

T4

Set 3

7 T2

T4

T4

8 Delay Period After Switching dxcon029

Figure 27: Sequencer Module Example 2, Sequential Mode

Configuration Guides - DX-9100 Configuration Guide

151

Page 152

Algorithm 23 – Four Channel Line Segment (Version 1.1 or Later)

Each channel of a four channel line segment has an output, which is a nonlinear function of its input variable defined on an X,Y plane using four break points. The function is linear between break points. The input break values must go in increasing order, although the output break values can increase or decrease. This is typically used for a simple reset schedule. Output n

Y2,Y3

Y0,Y1 X

X

X0

X1

X

X

X2

X3

Input n n = 1-4 dxcon030

Figure 28: Example of a Line Segment Function Function

Via the GX Tool

Click on PM in the toolbar, select Numeric, then Four-Segment, and position the module (box) on the screen. Make connections between the numeric source points and In@ inputs, as applicable. Select the module and then Data to call up the Data Window. Under CH #n, in the X column, enter input (X) break values at the 0, 1, 2, and 3 fields. In the Y column, in each field, enter the output (Y) break value, which corresponds to the input entry. Define the values of X for the complete range of the input.

152

Configuration Guides - DX-9100 Configuration Guide

Page 153

Via the SX Tool

This algorithm is assigned to a programmable function module when the value 23 is configured in PM Item PMnTYP (RI.00). For Channel n (n = 1-4): In@ = Input Variable Connection (RI.10 to RI.13) Break Point 0 defined by coordinates X0-n,Y0-n (X0-n; RI.26, .34, .42, .50; Y0-n; RI.27, .35, .43, .51) Break Point 1 defined by coordinates X1-n,Y1-n (X1-n; RI.28, .36, .44, .52; Y1-n; RI.29, .37, .45, .53) Break Point 2 defined by coordinates X2-n,Y2-n (X2-n; RI.30, .38, .46, .54; Y2-n; RI.31, .39, .47, .55) Break Point 3 defined by coordinates X3-n,Y3-n (X3-n; RI.32, .40, .48, .56; Y3-n; RI.33, .41, .49, .57) Notes

1.

The output of each channel can be seen on the SX Tool at Alg. Item NCMn (RI.60 to RI.63).

2.

X values must be entered in ascending order and the same number may not be entered twice. Unlike Algorithm 16, the outputs for inputs outside of the defined range are as follows: for X < X0, Y=Y0 for X > X3, Y=Y3

GX Labels

3.

Each channel of the module can be put in Hold mode by entering the value 1 in Alg. Item PMnHDC (RI.70 bits X1 to X4) on the SX Tool or by the PLC. The channel output may be modified by a BAS when in Hold mode.

4.

As the numeric output cannot be read at the DX front panel, it is recommended that this algorithm is used in the higher PM numbers, reserving the lower PM numbers for algorithms that can be displayed.

Source Points (Outputs)

PMnHLDm A 1 when the channel of the program module has been overridden (in hold) from an SX service module or a BAS. PMnNCMm The calculation result of a channel of a numeric module. Destination Points (Inputs)

In@

Analog input connections to a programmable module.

Configuration Guides - DX-9100 Configuration Guide

153

Page 154

Algorithm 24 – Eight Channel Calculator (Version 1.1 or Later)

Each channel of an eight channel calculator has an output that is the result of an algebraic expression of two input variables. When an input is not connected, a value of 1 is assumed and the corresponding constant (Kn) must be set to the required value. If the denominator is 0, the equation outputs the last reliable calculation. The following show how the calculations are actually performed: (K1-n * I1-n) + (K2-n * I2-n) (K1-n * I1-n) - (K2-n * I2-n) (K1-n * I1-n) * (K2-n * I2-n) (K1-n * I1-n) / (K2-n * I2-n) MIN (K1-n * I1-n, K2-n * I2-n) MAX (K1-n * I1-n, K2-n * I2-n)

Function

Via the GX Tool

Click on PM in the toolbar, select Numeric, then Eight-Calculator, and position the module (box) on the screen. Select the module and then Data to call up the Data Window. At the Ch #n Equation Type field, enter the value to describe the equation type: 0

= Disabled

1

= Addition

2

= Subtraction

3

= Multiplication

4

= Division

5

= Minimum Select

6

= Maximum Select

Then enter the constant values for the different channels by selecting the Constant K1, Constant K2, etc., fields and entering values for the desired calculation. Make connections between numeric source points and module inputs I1-n@ and I2-n@.

154

Configuration Guides - DX-9100 Configuration Guide

Page 155

Via the SX Tool

This algorithm is assigned to a programmable function module when the value 24 is configured in PM Item PMnTYP (RI.00). The bit structure of the Alg. Item FUNn (RI.02 to RI.09) defines the function of the algorithm channel where n = 1-8. X3X2X1 = 000

Disabled

X3X2X1 = 001

Addition

X3X2X1 = 010

Subtraction

X3X2X1 = 011

Multiplication

X3X2X1 = 100

Division

X3X2X1 = 101

Minimum

X3X2X1 = 110

Maximum

I1-n@ = Input Variable 1 Channel n. (even numbers RI.10 to RI.24) I2-n@ = Input Variable 2 Channel n. (odd numbers RI.11 to RI.25) K1-n = Constant 1 Channel n (even numbers RI.26 to RI.40) K2-n = Constant 2 Channel n. (odd numbers RI.27to RI.41) Notes

GX Labels

1.

The output of each channel can be seen on the SX Tool at Alg. Item NCMn (RI.60 to RI.67).

2.

Each channel of the module can be put in Hold mode by entering the value 1 in Alg. Item PMnHDC (RI.70, bits X1 to X8) on the SX Tool or by the PLC. The channel output may be modified in the Hold mode by a BAS.

3.

As the numeric output cannot be read at the DX front panel, it is recommended that this algorithm is used in the higher PM numbers, reserving the lower PM numbers for algorithms, which can be displayed.

4.

To build up more complex equations the output of one channel may be connected to the input of another channel to form a chain. Note that outputs only get transferred to inputs when the module begins execution so that there is always a delay of one second between individual channel calculations in one module when they are chained.

Source Points (Outputs)

PMnHLDm A 1 when the channel of the program module has been overridden (in hold) from an SX service module or a BAS. PMnNCMm The calculation result of a channel of a numeric module. Destination Points (Inputs)

In-m@

Analog input connections to an eight channel calculator module. Configuration Guides - DX-9100 Configuration Guide

155

Page 156

Time Program Functions Real Time Clock

The following variables are available and may be displayed on the front panel of the controller: Year:

Years

1990-2020 (up to 2035 in Versions 1.4, 2.3, and 3.3, or later)

Month:

Month of the year

1-12

Day:

Day of the month

1-31

Hour:

Hours since midnight

0-23

Minute:

Minutes after the hour 0-59

Day Of Week:

1=MONDAY 2=TUESDAY 3=WEDNESDAY 4=THURSDAY 5=FRIDAY 6=SATURDAY 7=SUNDAY

Exception Day:

8=HOLIDAY

The actual day of the week is automatically calculated as a function of the programmed calendar day at the power up initialization and at every date change. Daylight Saving

This function automatically advances the current time by one hour at the beginning of the daylight saving period and sets the current time back by one hour at the end of the period. The daylight saving period begins at time 00:00 of the START DATE and ends at 01:00 of the END DATE. Via the GX Tool

To set daylight saving dates, select Edit-Global Data. At the DL Savings Start Date (MM/DD) field, enter the date of the Sunday when the next daylight saving period begins. At the DL Savings End Date (MM/DD) field, enter the date of the Sunday when the current or next daylight saving period ends. (This function cannot be accessed by the SX Tool, but can be executed from the front panel of the DX controller.) 156

Configuration Guides - DX-9100 Configuration Guide

Page 157

Exception Days

An exception day table, composed of up to 30 entries, determines exceptions for the day of the week status. On exception days, holiday status will be set and the day number will be set to 8. Each entry in the table is described by a START DATE and an END DATE in the format [Month] [Day]. When the DX is at Day 8, the only schedules that will operate are ones that have been programmed with an 8 in the Days for Event. Examples: For a holiday of December 24 and 25, enter 12:24 as Start and 12:25 as End. For a holiday of January 1, enter 01:01 as Start and 01:01 as End. Via the GX Tool

Click on PM in the toolbar, select Exception Days, and position the module (box) on the screen. Select the module and then Data to call up the Data Window. At the #n Start: field, enter the date to start the holiday. At the #n End: field, enter the date to stop the holiday. For a single day holiday, enter the same date for start and end. (This function cannot be accessed by the SX Tool, but can be executed from the front panel of the DX-9100 Controller.) Time Schedule Configuration

The eight time schedule modules each provide the control of a logic output as a function of a programmable event schedule, the day of the week, exception days condition, and of the realtime clock. One time schedule can contain up to eight entries, each containing the following information: •

START TIME:

[Hour][Minute]

•

STOP TIME:

[Hour][Minute]

•

DAYS FOR EVENT:

To select on which days of the week (Mon, Tue, Wed, Thu, Fri, Sat, Sun, and Holiday) the START/STOP command will be issued; the command may be enabled for more than one day.

The event on time can be extended to cover a period greater than one day by programming the STOP TIME of one event as 24:00 and the START TIME of the next event as 00:00. If, for one event, the STOP TIME is earlier than the START TIME, the DX (when downloaded) will automatically change the STOP TIME to one minute after the START TIME.

Configuration Guides - DX-9100 Configuration Guide

157

Page 158

The time schedule module is executed each minute. If external forcing conditions are not present, the event schedule is examined to verify whether a start/stop command is programmed for the actual time and day of the week. GX Tool

Via the GX Tool

Click on PM in the toolbar, select Time Schedule, and position the module (box) on the screen. Select the module and then Data to call up the Data Window. Set the start and stop times in the respective fields: Start Time Event #n Stop Time Event #n Then, at the Days for Event #n field, enter a value corresponding to the desired schedule: 1=MONDAY 2=TUESDAY 3=WEDNESDAY 4=THURSDAY 5=FRIDAY 6=SATURDAY 7=SUNDAY 8=HOLIDAY

(Exception Day)

0=ALL DAYS

(Monday to Sunday - Not Holiday)

9=WEEKDAYS

(Monday to Friday)

Example: For days Monday, Tuesday, and Wednesday, enter 123. Output Type

Via the SX Tool

Bit X1 of Item TSnOPT (RI.00) defines the output type. It should be set to 0 for logic output type, which is the only available output type in the current versions of firmware. (This setting is available only through the SX Tool.) Overriding the Time Schedule

Three logic inputs can override the normal function of the time schedule module: •

158

The External Extension Connection defines a logic variable which, if On at a programmed stop time of the module, extends the On period for a programmed extension time. (The extension can also be set from the DX front panel or by a BAS when the module output is On. See the following Notes section.)

Configuration Guides - DX-9100 Configuration Guide

Page 159

•

The On Forcing Connection forces the output to On, if the connection equals 1.

•

The Off Forcing Connection forces the output to Off if the connection equals 1.

•

The logic forcing inputs are executed according to following priority: forcing to Off, forcing to On, and extension.

Via the GX Tool

Select the time schedule module and then Data to call up the Data Window. Make connections between External Forcing On source points and TSnON@ inputs. Similar connections for Off Forcing TSnOF@ and for Extension External TSnEX@ can be made as required. At the Extension Time field, enter a value for the desired extension time in minutes (0 - 255). Via the SX Tool

Set the connections via the following Items: •

The External Extension Connection Item = TSnEX@ (RI.01).

•

The On Forcing Connection Item = TSnON@ (RI.02).

•

The Off Forcing Connection Item = TSnOF@ (RI.03).

The value in Item TSnXTM, (RI.04) defines the extension time (0-255minutes). Notes

1.

The time, date, year, extension time, daylight saving dates, time schedule output, and start/stop event days and times can be read and modified using the DX front panel. See Display Panel and Keypads in the DX-9100 Extended Digital Controller Technical Bulletin (LIT-6364020) in FAN 636.4 or 1628.4.

2.

The extension can be set from the DX front panel. See Display Panel and Keypads in the DX-9100 Extended Digital Controller Technical Bulletin in FAN 636.4 or 1628.4.

3.

On the SX Tool, the value in Item TSnTIM (RI.05) indicates the time in minutes to the next change of the logic output TSnOUT. This output will be active when a change of output within the current or next day is scheduled.

Configuration Guides - DX-9100 Configuration Guide

159

Page 160

4.

The bit values in Item TSnSTA (RI.06) indicate on the SX Tool the time schedule status as follows: X1=1 TSnHLD

Time schedule module is in Hold mode. The output of the module (TSnOUT) can be modified in the Hold mode. X2 TSnOUT Output status and control is the output of the time schedule module, and can be used as logic input to any of the programmable or output modules. X3=1 TSn EXT Extension command is set by an extension ?? override command from the DX front panel or BAS. This command toggles the extension status (TSnEXS) on and off. X4 TSnNXO Indicates the next scheduled output of the time schedule module (0 or 1). X5= 1TSnEXS Indicates an active extension from the DX front panel or BAS. X6=1 TSnXDI Indicates an active extension from a logical (digital) input (via the External Extension Connection). X7=1 TSnON Indicates a forced On status. X8=1 TSnOFF Indicates a forced Off status. Status Items can be used as logic (digital) connections using the GX Tool or SX Tool.

160

5.

When an extension is set from the DX front panel or by a BAS, the extension status (TSnEXS) of the module is true (bit X5 = 1). An extension via the DX front panel or BAS is automatically reset when the extension period ends.

6.

When an extension is set by the External Extension Connection, the extension status TSnXDI of the module is true (Bit X6 = 1) when the output status (TSnOUT) is true, and remains true until the end of the extension period.

7.

When making a connection from a time schedule module to an optimal start/stop module, the Items TSnOUT, TSnNXO, and TSnTIM must be connected via the SX Tool. If using the GX Tool, when TSnOUT is connected, the TSnNXO and TSnTIM are connected internally.

8.

When a start or stop time of an event in a time schedule module is changed, the time schedule module will take up to one minute to update its output.

9.

Time schedules may be uploaded, modified, and downloaded at the Operator Workstation (OWS). Refer to the Scheduling Technical Bulletin (LIT-636116) in FAN 636.

Configuration Guides - DX-9100 Configuration Guide