Page 161

GX Labels

Source Points (Outputs)

TSnEXS

A 1 when a time schedule module has its extension enabled by a BAS or a DX front panel command.

TSnOUT

A 1 when the real time is currently between the start and stop times of an event of the time schedule module and the current day is specified for that event.

Destination Points

Optimal Start/Stop Configuration

TSnOF@

A connection to externally force the output of a time schedule to Off.

TSnON@

A connection to externally force the output of a time schedule to On.

TSnEX@

A connection to the external extension of a time schedule.

Two optimal start/stop modules each calculate the minimum time needed to bring a controlled zone temperature to a desired condition at occupancy time under heating and/or cooling conditions. The modules also calculate the optimal stop time to maintain the desired conditions up to the end of the occupancy time. When an optimal start/stop module is configured for heating and cooling, the module assumes a:

Function

•

Heating mode for startup if the zone temperature is below setpoint

•

Cooling mode for startup if the zone temperature is above setpoint

•

Heating mode for shutdown if the outdoor temperature is below the zone on setpoint

•

Cooling mode if the outdoor temperature is above the zone on setpoint

Via the GX Tool

Click on PM in the toolbar, select Optimum Start/Stop, and position the module (box) on the screen. Select the module and then Data to call up the Data Window. At the Module Type field, enter the value corresponding to the desired configuration: 1

= Heating

2

= Cooling

3

= Heating and Cooling

Configuration Guides - DX-9100 Configuration Guide

161

Page 162

Via the SX Tool

The OSnOPT (RI.00) defines the operating mode of the optimal start/stop module by setting bit X1 and X2 as follows: X2X1 = 00

Not used

X2X1 = 01

Heating mode (heating plant only)

X2X1 = 10

Cooling mode (cooling plant only)

X2X1 = 11

Heating and Cooling mode (plant heats and cools)

The status of the mode can be seen at Item OSnSTA, bit X3, (OSn HEAT) where 0 = Cooling and 1 = Heating. Optimal Start Adaptive Process

The adaptive process monitors how quickly the temperature reaches the halfway point between the setpoint and actual temperature: •

If it takes less than the calculated warmup time based on the building factor, then the building factor will be decreased so that the next calculation will result in a shorter warmup time, all other factors being equal.

•

If it takes more than the calculated warmup time based on the building factor, then the building factor will be increased so that the next calculation will result in a longer warmup time, all other factors being equal.

The adaptive process calculation only takes place when the Optimal Start module actually starts the plant. Temperature

Control Range (Comfort Zone)

Module Updates Building Factor

Zone Air Setpoint (SP)

Delta Time

Optimal Start Curve

Delta Temp

Zone Air Temperature (ZT) Purge Time

Purge Time

Maximum Startup Time Start Plan (OSnOUT=1) (OSnPRE=1) (TSnOUT=0)

Occupancy (TSnOUT=1) (OSnPRE=0) (OSnOUT=1)

Figure 29: Optimal Start Module in Heating Mode

162

Configuration Guides - DX-9100 Configuration Guide

Time dxcon031

Page 163

The required startup time is calculated as follows: WarmupTime = Building Factor ( Heating ) x( SP − ZT + TC )2 + PT TC =

( HTD − OT ) when HTD > OT , else TC = 0 4

Cooldown Time = Building Factor ( Cooling ) x ( ZT − SP + TC ) 2 + PT TC =

OT − CTD when OT > CTD, else TC = 0 4

When the Zone Air Temperature has risen (when in heating mode) or fallen (when in cooling mode) halfway towards the Zone Setpoint, the module updates the corresponding Building Factor value using the following calculation: NBF =

(100 − FW ) x OBF + FW x deltaTime /(deltaTemp ) 2 100

If the Zone Air Temperature does not reach the halfway point, the corresponding Building Factor is automatically increased by a fixed amount equal to 10% of the existing value. The Building Factor is not updated if the initial Zone Air Temperature is within the Control Range. NBF =

New Building Factor

FW

Filter Weight

=

OBF =

Old Building Factor

SP

=

Zone Air Setpoint Temperature

ZT

=

Zone Air Temperature

PT

=

Min. Heat/Cool Time (Purge Time)

HTD =

Outdoor Design Temperature Heating

CTD =

Outdoor Design Temperature Cooling

TC

=

Temperature Compensation

OT

=

Outdoor Temperature

The Building Factor (Heating) is updated in the Heating mode and the Building Factor (Cooling) is updated in the Cooling mode.

Configuration Guides - DX-9100 Configuration Guide

163

Page 164

If the difference between the outdoor air and the zone temperature is small, the heating equipment can be stopped at an earlier time than if the difference is large.

Optimal Stop Operation

Zone Temperature Control Range (Comfort Zone) Cooling Mode

On Setpoint

Heating Mode

Off Bias in Degrees Off Bias in Degrees

Maximum Optimal Stop Time Time Optimal Stop Time (OSnOUT=1) (OSnSTO=0) (TSnOUT=1)

Stop Plant (OSnOUT=0) (OSnSTO=1) (TSnOUT=1)

Vacancy (unoccupied) (OSnOUT=0) (OSnSTO=0) (TSnOUT=0)

dxhcmtb

Figure 30: Optimal Stop Module in Heating/Cooling Mode Opt. Stop Time =

Zone Temp. Off Bias * Shutdown Building Htg/Clg Factor Zone Temp. - Outdoor Temp.

or = Maximum Optimal Stop Time (whichever is least). If the Zone Temperature (ZT) is not within the Control Range (CRNG), or Outdoor Temperature (OT) is not connected, the Optimal Stop algorithm is not executed and the output OSnOUT is reset at the normal vacancy time (i.e., the Optimal Stop Time set at 0). Zone Temperature

The Zone Temperature is an analog input to the module, which gives the actual temperature of the conditioned zone. Via the GX Tool

Make a connection between the Zone Temperature source point and the OSZT@ input point of the OSn module.

164

Configuration Guides - DX-9100 Configuration Guide

Page 165

Via the SX Tool

Configure this function by entering the source address at Item OSnZT@ (RI.01). Outdoor Temperature

The Outdoor Temperature is an analog input to the module, which gives the actual outdoor temperature. If the input is not connected, the module does not compensate for outdoor temperature and the optimal stop function is disabled. Via the GX Tool

Make a connection between the Outdoor Temperature source point and the OSOT@ input point of the OSn module. Via the SX Tool

Configure this function by entering the source address at Item OSnOT@ (RI.02). Zone Temperature on Setpoint

This is the desired zone temperature at the scheduled occupancy time. If the connection is made, it will be the active setpoint. If there is no connection, the value entered as the Zone Temperature setpoint will be used. Via the GX Tool

Make a connection between the Zone Temperature On setpoint source point and the OSSP@ input point of the OSn module. If connected, the value will replace the value entered at Zone Temp. SP. Or, for a fixed setpoint, select the OSn module and then Data to call up the Data Window. At the Zone Temp. SP field, enter the desired zone temperature at occupancy. Via the SX Tool

Configure the active setpoint by entering the source address at Item Location OSnSP@ (RI.03). If no connection is made, the value entered at Item OSnSP (RI.21) will be used.

Configuration Guides - DX-9100 Configuration Guide

165

Page 166

Zone Temperature Off Bias

This is an analog input or value that determines the maximum change in zone temperature during the optimal stop period. If the input is not connected, the module will use the value entered as the Zone Temp. Off Bias. For a heating plant only, the value must be negative; for a cooling plant only, the value must be positive. For the Heating and Cooling mode, an absolute value is used, and the Heating or Cooling mode is automatically determined by the module from the outdoor temperature. (Refer to Figure 30.) Via the GX Tool

Make a connection between the Off Bias source point and the OSOB@ input point of the OSn module. If there is no connection, the module will use the fixed value entered at the Zn Tmp Off SP Bias field. Or for a fixed bias, select the OSn module and then Data to call up the Data Window. Select the Zn Tmp Off SP Bias field, and enter the maximum change in zone temperature during the optimal stop period. Via the SX Tool

The software connection is configured by entering the source address at the OSnOB@ Item location (RI.04). If no connection is made, the value entered at Item OSnOB (RI.22) will be used. Disable Module

This connection is a logic input, which disables the operation of the module. If the input is not connected, the module will use the default value 0 and the module will be enabled. When disabled, the Optimal Start module will simply output the start and stop commands of the Time Schedule module to which it is connected. Via the GX Tool

Make a connection between the disable module source point and the OSD1@ input point of the OSn module. Via the SX Tool

Enter the logic source address at Item OSnDI@ (RI.05). Disable Adaptive Action

166

This connection is a logic input, which disables the adaptive operation of the module. If the input is not connected, the module will use the default value 0, and the module will be adaptive. The adaptation should only be disabled after the module has obtained some history and the configuration has been uploaded for safe keeping.

Configuration Guides - DX-9100 Configuration Guide

Page 167

Via the GX Tool

Make a connection between the Disable Adaptive Action source point and the OSDA@ input point of the OSn module. Via the SX Tool

Enter the logic source address under OPT. ST. at Item OSnDA@ (RI.06). Time Schedule Command Source

The connection at OSnTS@ is a logic input that indicates the occupancy period of the zone controlled by the module. The source is a TSnOUT variable from a time schedule module. The optimal start module uses the time information from the time schedule module to determine the normal occupancy time and to calculate earlier start and stop times. Via the GX Tool

Only TSnOUT logic variables may be selected. Note: The Next Output and Time to Next Output mentioned below will automatically be connected by the GX Tool. Make a connection between the TSnOUT source point and the OSTS@ input point of the OSn module. Via the SX Tool

Enter the logic source address under OPT. ST. at Item OSnTS@ (RI.07). Next Output (SX only)

The connection at OSnNX@ (RI.08) is a logic input that indicates the status of the next Start/Stop Command. The software connection is configured by entering the source address at the OSnNX@ Item location. The source is normally the TSnNXO variable from the time schedule module connected to the OSnTS@ (RI.07) Item. Time to Next Output (SX only)

The connection at OSnTIM@ (RI.09) is a numerical input that indicates the time in minutes to the next output. The source is normally the TSnTIM variable from the time schedule module connected to the OSnTS@ Item (RI.07). The software connection is configured by entering the source address at the OSnTIM@ Item (RI.09) location. Minimum Heat/Cool Time

This parameter is a number, which defines the minimum time the AHU or other equipment should begin operating before occupancy (minutes) to condition the space to comfort setpoint.

Configuration Guides - DX-9100 Configuration Guide

167

Page 168

Via the GX Tool

Select the OSn module and then Data to call up the Data Window. Select the Min Startup Time field, and enter a value in minutes. Via the SX Tool

Enter a value under OPT. ST. at Item OSnPURGE (RI.10) in minutes. Maximum Startup Time

This parameter is a number, which defines the time period (minutes) given for the module to calculate when to start the heating or air conditioning equipment before occupancy. The module begins its calculation when the maximum startup time is equal to the occupancy time minus the current time. This parameter is used to limit the startup time, and consequently the energy used; if its value is too small the space may not reach comfort setpoint by occupancy time under extreme weather conditions. Via the GX Tool

Select the OSn module and then Data to call up the Data Window. Select the Max Startup Time field, and enter a value in minutes. Via the SX Tool

Enter a value under OPT. ST. at Item OSnMAXST (RI.11) in minutes. Maximum Shutdown Time

This is a number, which defines the time period (minutes) given for the module to calculate when to stop heating or air conditioning equipment before the end of occupancy. The module begins its calculation when the maximum shutdown time is equal to the normal vacancy time minus the current time. Via the GX Tool

Select the OSn module and then Data to call up the Data Window. Select the Max Shutdown Time field, and enter a value in minutes. Via the SX Tool

Enter a value under OPT. ST. at Item OSnMAXSO (RI.12) in minutes. Start Mode Building Factor (Heating)

168

This factor is a number, expressed in min./degrees2, which defines the initial building factor for the first Optimal Start heating calculation. It will be automatically updated by the module when adapting is enabled. (For an understanding of the effect of different values, refer to the calculations under Optimal Start/Stop Configuration.)

Configuration Guides - DX-9100 Configuration Guide

Page 169

Via the GX Tool

Select the OSn module and then Data to call up the Data Window. Select the Start Heat. Factor field, and enter an appropriate value or accept the default. After a few weeks of operation, upload the configuration with the new value for record purposes and stop the adaptive process. (During seasonal transitions, the adaptive process may take longer to stabilize.) Note: A new download to the controller will override any adaptively changed values with the values stored in the download file. Via the SX Tool

Enter a value under OPT. ST. at Item OSnBHK (RI.13). Start Mode Building Factor (Cooling)

This factor is a number, expressed in min/degrees2, which defines the initial building factor for the first Optimal Start cooling calculation. It will be automatically updated by the module when adapting is enabled. (For an understanding of the effect of different values, refer to the calculations under Optimal Start/Stop Configuration.) Via the GX Tool

Select the OSn module and then Data to call up the Data Window. Select the Start Cool. Factor field, and enter an appropriate value or accept the default. After a few weeks of operation, note the new value for record purposes and stop the adaptive process. (Seasonal transitions may take longer to stabilize.) Note: A new download to the controller will override any adaptive values with the values stored in the download file. Via the SX Tool

Enter a value under OPT. ST. at Item OSnBCK (RI.14). Stop Mode Building Factor (Heating)

This factor is a number, expressed in min/degrees, which defines the building factor for the Optimal Stop heating calculation. Via the GX Tool

Select the OSn module and then Data to call up the Data Window. Select the Stop Heat Factor field, and enter an appropriate value or accept the default. Via the SX Tool

Enter a value under OPT. ST. at Item OSnSBHK (RI.15). Configuration Guides - DX-9100 Configuration Guide

169

Page 170

Stop Mode Building Factor (Cooling)

This factor is a number, expressed in min/degrees, which defines the building factor for the Optimal Stop cooling calculation. Via the GX Tool

Select the OSn module and then Data to call up the Data Window. Select the Stop Cool Factor field, and enter an appropriate value or accept the default. Via the SX Tool

Enter a value under OPT. ST. at Item OSnSBCK (RI.16). Adaptive Control (Filter Weight)

This is a number, expressed in percent, which defines the proportion of the latest calculated factor used to update the stored building factor. One percent is a slow update (100 days); 10% is a relatively fast update (10 days); 0% stops the update of building factors and has the same effect as disabling the adaptive process. (For information on the effect of different values, refer to the calculations under Optimal Start/Stop Configuration.) Via the GX Tool

Select the OSn module and then Data to call up the Data Window. Select the Filter Weight field, and enter a value from 0 to 100%. Via the SX Tool

Enter a value under OPT. ST. at Item OSnFW (RI.17) from 0 to 100%. Outdoor Air Design Temperature (Heating)

This is a number, expressed in degrees, defining the coldest outdoor temperature that the heating equipment is designed to handle. When the outdoor air is below this value, the module will not update the building factors. Note: For North American applications, these values change based on geographical location, and can be obtained from the ASHRAE Handbook of Fundamentals, Chapter 24, Table 1, Climatic Conditions for the United States.

170