Page 171

Via the GX Tool

Select the OSn module and then Data to call up the Data Window. Select the OA Design Temp Htg field, and enter the design temperature. Via the SX Tool

Enter a value under OPT. ST. at Item OSnHTD (RI.18). Outdoor Air Design Temperature (Cooling)

This is a number, expressed in degrees, defining the warmest outdoor temperature that the cooling equipment is designed to handle. When the outdoor air is above this value, the module will not update the building factors. Note: For North American applications, these values change based on geographical location, and can be obtained from the ASHRAE Handbook of Fundamentals, Chapter 24, Table 1, Climatic Conditions for the United States. Via the GX Tool

Select the OSn module and then Data to call up the Data Window. Select the OA Design Temp Clg field, and enter the design temperature. Via the SX Tool

Enter a value under OPT. ST. at Item OSnCTD (RI.19). Control Range (+/-)

This is a number, expressed in degrees, that defines the temperature band above and below the zone air temperature setpoint within which the heating/cooling equipment is regulated. The Building Factor is not updated if the initial Zone Air Temperature is within the Control Range. See Figure 30. Via the GX Tool

Select the OSn module and then Data to call up the Data Window. Select the Control Range field, and enter the temperature band. Via the SX Tool

Enter a value under OPT. ST. at Item OSnCRNG (RI.20).

Configuration Guides - DX-9100 Configuration Guide

171

Page 172

Notes

1.

The value in OSnTIM (RI.23) indicates the calculated startup time (in minutes) for the currently active optimal start period (during unoccupied period) or for the last optimal start period to have been active (during occupied period) (Version 1.1 or later).

2.

The bit values in Item OSnSTA (RI.24) indicate the Operating Status as follows: X1 = 1

OSnHLD puts the optimal start/stop module in Hold mode. The output of the module (OSnOUT) can be modified in the Hold mode.

X2

OSnOUT output status and control is the Output of the optimal start/stop module, can be used as logic input to any of the programmable or output modules, and will typically be used to start the main heating, cooling, or AHU equipment.

X3 = 1

OSnHEAT indicates when the module is in Heating mode and can be used as logic input to any of the programmable or output modules.

X4 = 1

OSnPRE indicates when the module is in precooling or preheating and can be used as logic input to any of the programmable or output modules.

X5 = 1

OSnSTO indicates that the output has been reset (OSnOUT = 0) during the optimal stop period, and can be used as a logic input to any of the programmable or output modules.

X6

OSnIN status of the command input (usually time schedule TSnOUT).

X7 = 1

OSnADP adapting algorithm disabled.

X8 = 1

OSnDAS module disabled.

Status Items can be used as logic (digital) connections using the GX Tool or SX Tool. 3.

172

Optimal Start/Stop values cannot be viewed directly from the DX front panel.

Configuration Guides - DX-9100 Configuration Guide

Page 173

GX Labels

Source Points (Outputs)

OSnHEAT

A 1 when Optimal Start module is in the Heating mode.

OSnOUT

A 1 when the Optimal Start module requires equipment to be On. It is the controlling output of an Optimal Start module to START/STOP heating or cooling equipment.

OSnPRE

A 1 while the Optimal Start module is in the Preconditioning mode (will turn Off at occupancy).

OSnSTO

A 1 when the Optimal Start module is in the Optimal Stop mode (will turn Off at vacancy - unoccupied).

Destination Points (Inputs)

OSnDA@

The connection to disable the adaptive action of an Optimal Start/Stop module.

OSnDI@

The connection to disable the Optimal Start/Stop module.

OSnOB@

The connection to the Off Setpoint Bias, which replaces the entered value when connected in an Optimal Start/Stop module.

OSnOT@

The connection for the Outdoor Air Temperature sensor of an Optimal Start/Stop module.

OSnSP@

The connection for the Optimal Start Zone Temperature setpoint. If connected, it replaces the entered setpoint.

OSnTS@

The connection in an Optimal Start/Stop module for the time schedule that determines when the building is occupied.

OSnZT@

The connection for the Zone Temperature sensor in an Optimal Start/Stop module.

Configuration Guides - DX-9100 Configuration Guide

173

Page 174

Programmable Logic Control Configuration Introduction

The DX-9100 operating system provides a software-implemented Programmable Logic Controller (PLC). Every second the PLC module executes a user-defined program, which operates on a 2,048-bit memory area containing an image of the hardware digital input/outputs, logic variables from function modules, and digital constants. In the memory area each input, output, and logic variable has its own, pre-allocated address. Variables in the memory area are frozen before the execution of the program in the PLC module, and the resulting changes in the logic variables are transferred out of the memory area to the appropriate hardware or function modules at the end of the module execution. Hardware Inputs

Hardware Outputs

PLC Memory Area

Logic Variables

User-defined Program

PLC Module dxcon033

Figure 31: Programmable Logic Control PLC UserDefined Program

A user-defined program is a sequence of instruction blocks, which contains logic instructions, each leading to a PLC result status. An instruction block always begins with a LOAD or LOAD NOT (like an IF or IF NOT) logic instruction, which initializes the PLC result status, and normally terminates with an instruction performing an output to the memory area using the final result status (THEN). LOAD and LOAD NOT instructions may also be used within an instruction block to create a logic sub block. In the GX-9100 Graphic Programming Software, the instructions are laid out in eight pages of ladder diagrams, each containing eight lines of up to eight instructions, graphically depicted as shown below. The following instructions are available: (1 = On, 0 = Off).

174

Configuration Guides - DX-9100 Configuration Guide

Page 175

Instruction LOAD

This instruction begins the operation of an instruction block; the value of the addressed variable (0 or 1) is placed in the result status. This instruction also begins the operation of an ANDB or ORB sub block and saves the current value of the result status; the value of the addressed variable is placed in the sub block result status. (Think of LOAD as an IF statement.) In the figure below, the logic variable DI1 (Digital Input 1) is shown. DI1

L dxcon034

Figure 32: Load Instruction Table 8: LOAD LOAD Status Of Addressed Variable

Result Status

1

1

0

0

IF

THEN

Instruction LOAD NOT

This instruction begins the operation of an instruction block; the inverted value of the addressed variable (0 or 1) is placed in the result status. This instruction also begins the operation of an ANDB or ORB sub block and saves the current value of the result status; the value of the addressed variable is placed in the sub block result status. In the figure below, the logic variable AIH8 (high alarm status of Analog Input 8) is shown. AIH8 L dxcon035

Figure 33: Load Not Instruction Table 9: LOAD NOT LOAD NOT Status Of Addressed Variable

Result Status

0

1

1

0

IF NOT

THEN

Configuration Guides - DX-9100 Configuration Guide

175

Page 176

Instruction AND

This instruction calculates the logical AND between the value of the addressed variable and the result status; the result is placed in the result status. This instruction may also be used within sub blocks. In Figure 34, the logic variable DI2 (Digital Input 2) is shown. DI1

DI2

L dxcon036

Figure 34: AND Instruction Table 10: AND Previous Result Status

AND Status of Addressed Variable

Result Status

1

1

1

0

1

0

1

0

0

0

0

0

IF

AND

THEN

Instruction AND NOT

This instruction calculates the logical AND between the inverted value of the addressed variable and the result status; the result is placed in the result status. This instruction may also be used within sub blocks. In Figure 35, the logic variable DI3 (Digital Input 3) is shown. DI1

DI3

L dxcon037

Figure 35: AND NOT Instruction Table 11: AND NOT

176

Previous Result Status

AND NOT Status of Addressed Variable

Result Status

1

0

1

0

0

0

1

1

0

0

1

0

IF

AND NOT

THEN

Configuration Guides - DX-9100 Configuration Guide

Page 177

Instruction OR

This instruction calculates the logical OR between the value of the addressed variable and the result status; the result is placed in the result status. This instruction may also be used within sub blocks. In Figure 36, the logic variable DI4 (Digital Input 4) is shown. Note: Only one addressed variable can be OR’d, whereas an ORB allows a block of variables linked by AND and OR instructions to be OR’d. DI1 L DI4 dxcon038

Figure 36: OR Instruction Table 12: OR Previous Result Status

OR Status of Addressed Variable

Result Status

1

1

1

0

1

1

1

0

1

0

0

0

IF

OR

THEN

Instruction OR NOT

This instruction calculates the logical OR between the inverted value of the addressed variable and the result status; the result is placed in the result status. This instruction may also be used within sub blocks. In Figure 37, the logic variable DI5 (Digital Input 5) is shown. DI1 L DI5 dxcon039

Figure 37: OR NOT Instruction

Configuration Guides - DX-9100 Configuration Guide

177

Page 178

Table 13: OR NOT Previous Result Status

OR NOT

Result Status

1

0

1

0

0

1

1

1

1

0

1

0

IF

OR NOT

THEN

Instruction ANDB (AND Block)

This instruction terminates a logic sub block and indicates that a logical AND operation must be performed between the sub block result status and the result status saved before the execution of the sub block. No logic variable is referenced. Note: In the GX Tool an AND Block is started with a LOAD or LOADNOT instruction and closed by an ANDB instruction. AND Block DI1

XT1DI1

L

L

XT1DI2 B

XT1DI3 dxcon040

Figure 38: AND Block Instruction Table 14: AND Block

178

Previous Result Status

Sub Block Result Status

Final Result Status

1

1

1

0

1

0

1

0

0

0

0

0

IF

AND

THEN

Configuration Guides - DX-9100 Configuration Guide

Page 179

Instruction ORB

This instruction terminates a logic sub block and indicates that a logical OR operation must be performed between the sub block result status and the result status saved before the execution of the sub block. An ORB allows a block of variables linked by AND and OR instructions to be OR’d, whereas a single OR allows only one addressed variable to be OR’d. DI1

XT1DI1

L

L

XT1DI3

XT1DI4

XT1DI2

L dxcon041

Figure 39: OR Block Instruction Table 15: ORB Previous Result Status

Sub Block Result Status

Final Result Status

1

1

1

0

1

1

1

0

1

0

0

0

IF

OR

THEN

An OR Block may be nested within an AND Block. In this case, the ORB must come before an ANDB. Note: In the GX Tool an ORB must be declared before defining the block to be OR’d for graphic formatting purposes. AND Block DI1

XT1DI1

L

L DI4

XT1DI2

B

DI5

L DO3

OR Block dxcon42

Figure 40: OR Block Nested Within AND Block

Configuration Guides - DX-9100 Configuration Guide

179

Page 180

Instruction OUT

This instruction causes the value of the result status, obtained from the preceding logic instructions in the instruction block, to be transferred to the addressed memory location. (Think of OUT as a THEN statement.) In Figure 41, the result is transferred to the Logic Result Status Variable LRS1. DI1

DI2

LRS1

L DI3 dxcon043

Figure 41: OUT Instruction Table 16: OUT Previous Result Status

OUT to Addressed Variable

0

0

1

1

IF

THEN

Instruction OUT NOT

This instruction causes the inverted value of the result status, obtained from the preceding logic instructions in the instruction block, to be transferred to the addressed memory location. In Figure 42, the result is transferred to the Logic Result status Variable LRS2. DI1

DI2

LRS2

L DI3 dxcon044

Figure 42: OUT NOT Instruction Table 17: OUT NOT

180

Previous Result Status

OUT NOT to Addressed Variable

0

1

1

0

IF

THEN

Configuration Guides - DX-9100 Configuration Guide