The text of a manual · part 21 of 31

DX-9100 Configuration Guide: Software Configuration, pages 191 to 200

Pages 191 to 200 of 288, from DX-9100 Configuration Guide

The original document is the PDF (1.3 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Johnson Controls DX-9100

Page 191

TIMER (TIMER 1) - Data ----------------------User Name :COS Description :TIMER USED AS COS BLOCK TIMER #1 TYPE Input Connection #1--> Reset Connection #1--> Time Period #1 Time Units #1 TIMER #2 TYPE Input Connection #2--> Reset Connection #2--> Time Period #2 Time Units #2 TIMER #3 TYPE Input Connection #3--> Reset Connection #3--> Time Period #3 Time Units #3 TIMER #4 TYPE Input Connection #4--> Reset Connection #4--> Timer Period #4 Time Units #4

1 AIH1 2.0000 0 1 /AIH1 2.0000 0 1 AIH3 2.0000 0 1 /AIH3 2.000 0

TIMER #5 TYPE Input Connection #5--> Reset Connection #5--> Time Period #5 Time Units #5 TIMER #6 TYPE Input Connection #6--> Reset Connection #6--> Time Period #6 Time Units #6 TIMER #7 TYPE Input Connection #7--> Reset Connection #7--> Time Period #7 Time Units #7 TIMER #8 TYPE Input Connection #8--> Reset Connection #8--> Timer Period #8 Time Units #8

1 DI1 2.0000 0 1 DI2 2.0000 0 1

2.0000 0 1

2.000 0 dxcon055

Figure 53: Timer Logic Module Ladder Diagram - PLC2 User Name: ALT-DIAL Description: ALTERNATIVE DIAL METHOD

PM1TD01 PM1TC02 PM1TD03 PM1TD04 PM1TD05 PM1TD06

LRS1

L LRS1

DIAL SET

L dxcon056

Figure 54: Configuration Diagram Variation Configuration Guides - DX-9100 Configuration Guide

191

Page 192

Notes: If more than seven alarms are required, another line in the PLC could be added which would command an additional LRS. This LRS would then be used in conjunction with the first LRS to set the DIAL bit. The HTRR bit is only available in the PLC module (under Diagnostic) and cannot be used as a source to a Timer module. Trend Log (Versions 1.4, 2.3, 3.3, or Later)

Dial

When set to 1 by a set statement in the PLC, this causes the N2 Dialer to connect the N2 Bus to a BAS via telephone lines. The Dial bit will be reset to 0 by the BAS when the telephone line connection is successful.

Point History (Versions 1.4, 2.3, or Later)

The Trend Log module provides 12 trend log channels, each recording data from either 1 analog Item or from a set of 8 logic variables (logic variable byte). The trend can be used to provide data for Point History in DX controllers that are remote from the BAS or for a local DX LCD Display. Trend data cannot be displayed on the integral DX controller display panel, or on the GX or SX Tools.

Trend Log for DX LCD Display (Versions 2.3, 3.3, or Later)

When the DX controller is connected to a BAS by an NDM Dialer and telephone lines, the trend data may be read whenever a connection is made by the BAS. The data is stored in the point history file of AI, AOs, and BI objects when they are mapped to the Items being recorded. When the Point History option is selected for a trend log channel, only those Items that can be mapped to objects are allowed and the trend parameters are set by the GX Tool to recommended default values for the Point History feature. You may change these default values, but you must take into consideration the maximum number of values that Point History can display and the frequency of the connections to the BAS via dial-up. You must link the Historical Trend Read Request logic variable to the DIAL request logic variable in a PLC module to initiate a connection when a trend record buffer is full. As a DX Version 3.x cannot be connected to a BAS by the NDM Dialer and telephone lines, trend logs cannot be configured for Point History in these versions. Trend channels that are not used for Point History are freely configurable. For analog Items, the sampling rate may be entered and the stored values may be either the average, maximum, or minimum values during the sampling period, or the instantaneous value at the time of recording. Logic variables are recorded with a time and date stamp when there is a change of value. All channels may be displayed on the DX LCD Display.

192

Configuration Guides - DX-9100 Configuration Guide

Page 193

Note: When selecting a logic variable, choose the byte that contains the required variable. All variables in the set will be then available for Point History or for the DX LCD Display. Since a logic variable set is recorded when any one of its variables changes state, you are recommended to assign LRS logic variable bytes to trend log and to connect the source variables (the ones that you wish to trend) to the LRS variables in a PLC module. A channel of the trend log is defined by the following parameters: Table 21: Trend Log Parameters Parameter

Possible Values

Default/Point History Setting in GX Tool

Source Item or Logic Variable Index (byte)

See Appendix E: Analog Items and Logic Variables for the Trend Log Module.

None

Sampling Rate

5, 10, 15, 20, 30, 60 seconds or 1-1440 minutes

Analog (AI): 30 Analog (AOS): 180 Logic Variables (BI): 1 Note: Logic variable bytes are read each second, but only recorded when there has been a change-of-state in at least one bit.

Sampling Rate Units

Sec. (seconds) Min. (minutes)

Analog (AI and AOS): Min.

Read Request

Analog: 0 to 61 Logic Variables: 0 to 30

Analog (AI): 48 Analog (AOS): 10 Logic Variables (BI): 10 Note: When Point History is not selected: 0

Average Maximum Minimum Actual Logic Variable

Actual (Not applicable to logic variables)

None Day (midnight 00:00:00) Hour (xx:00:00) Minute (xx:xx:00)

Hour (Not applicable to logic variables)

(Period of time between records)

(Number of new samples to set HTRR) Note: A value of 0 disables the Read Request feature for the Item or logic variable. Sampling mode (Analog value to record at end of each period)

Synchronization (Exact time of the start of trend recording)

Configuration Guides - DX-9100 Configuration Guide

193

Page 194

Via the GX Tool

Click on PM in the Tool Bar, then select Trend and position the module on the screen. Double-click on the Trend Log module block. The Trend Log definition table with 12 rows, 1 for each channel, will appear. Highlight the channel, then select Data. In the dialog box check the Point History box if required, then enter the desired Tag Name of the Item or logic variable set to be recorded. Note: Point History is not available for DX Version 3.x as this controller cannot be monitored remotely with an NDM Dialer. One of two data windows will appear when a valid tag name has been entered, depending on whether an analog Item or logic variable set was selected. Refer to Appendix E: Analog Items and Logic Variables for the Trend Log Module for a list of the tag names available in Trend Log. Enter the desired values in the Data fields. Note: If Point History was checked, do not change the default values unless you have a good understanding of the Point History feature. For details, refer to the Point History Technical Bulletin (LIT-636112) in FAN 636. In any free line of a PLC module, add a LOAD element assigned to the logic variable HTRR (listed under DIAGNOSTIC) followed by a SET element assigned to the logic variable DIAL. If other logic variables have already been configured to set the DIAL variable, add the HTRR variable as an OR element to the ladder logic diagram. Refer to Dial-up Feature with an NDM - Configuring the Program earlier in this document for an example. Via the SX Tool

Trend log cannot be configured with the SX Tool. However, the following Items can be read in the General Module for diagnostic purposes. Item DIAG (RI.03) HTRR bit X4 = 1

Historical Trend Read Request (one of the Trend Read Request bits for Channels 1 to 12 is set)

Item TRSTA (RI.47) Trend Status bit Xn = 1

Trend Read Request for Channel n (n = 1 to 12)

Item PHMAP (RI.48) Point History Map bit Xn = 1 194

Trend Channel n used for Point History (n = 1 to 12)

Configuration Guides - DX-9100 Configuration Guide

Page 195

Supervisory Mode Control Settings (General Module)

Versions 1 and 2 of the DX-9100 Controller may be connected to a BAS using the RS-485 serial link (N2 Bus or Bus 91). The Version 3 Controller (DX-912x-8454) is connected to the NCM-350 via the LONWORKS N2 Bus. Supervisory mode control operates in the same way in all three versions.

Access to the Controller

For control access, the BAS must first set a BAS Active bit. To keep control access, the BAS must refresh that bit at a minimum of every 120 minutes. If the BAS fails or loses communication with the controller, and the bit is not refreshed, the controller returns automatically to its Standalone mode of operation. When the BAS bit is active, the BAS has access to the supervisory parameters of the controller. It can also change numerical and logic values by addressing the respective Items in the Item list. Items stored in EEPROM may only be written to on an occasional basis (maximum of once a day). The functions specifically related to the BAS control are as follows: •

Set a programmable function module, output module, extension module, or time schedule module to Hold mode.

•

Set the Shutoff mode.

•

Set the Startup mode.

•

Set a control module to Computer mode.

•

Enable supervisory control of digital outputs (triacs).

•

Set digital outputs (triacs) to On or Off.

Within a control module (PID or On/Off), the output may be overridden by BAS control with the following priorities: 1.

Hold mode

2.

Shutoff mode (when enabled)

3.

Startup mode (when enabled)

4.

Computer mode

Via the BAS

The BAS Active bit is automatically set by BAS when connected online.

Configuration Guides - DX-9100 Configuration Guide

195

Page 196

Via the GX Tool

As the GX Tool has no BAS functions, it is not necessary to set the BAS Active bit from the GX Tool. Via the SX Tool

Set the supervisory bit at bit X16 of Item SUP (RI.01) (General Module). Startup Mode

The Startup mode can operate properly only if a PID or On/Off Controller is configured in Programmable Function Module 1. To allow the Startup mode to be active in a particular module the Enable Startup mode must be set to 1. This mode is activated and de-activated by a BAS. It is also de-activated after 120 minutes when the communication with the BAS fails. For PID algorithms, the output will be set to a level between 0 and 100%, overriding the output limits of the control module. For On/Off algorithms, the output will be set to a level of 0 or 1. The Startup mode will remain active as long as the controller configured in the Programmable Function Module 1 has an absolute deviation greater than 5% of the PV range. A lower deviation will clear the startup command throughout all enabled modules. Via the BAS

Configure using the reference STUP. Via the GX Tool

To allow the Startup mode to be active, select PID or On/Off and then Data to call up the Data Window. Enter a value of 1 in the Ena. Startup field. (If you do not want it active, enter 0.) To set the startup commanded value, select On/Off or PID, and then Data to call up the Data Window. Enter the value at the Startup Out Level field.

196

Configuration Guides - DX-9100 Configuration Guide

Page 197

Via the SX Tool

Under Program Modules, set the Enable Startup mode via PM Item PMnOPT (RI.01) bit X3 (STAE). Set the PID startup output at Alg. Item STL (RI.52). Set On/Off startup output at PM Item PMnOPT (RI.01) bit X4 (STAL). Activate or de-activate under General Module, by setting bit X8 of Item SUP (RI.01) (STUP). The status of the mode can be seen under Program Modules at PM Item PMnST (RI.72) bit X10 (STA). Shutoff Mode

This mode is activated and deactivated by a BAS. It is also deactivated after 120 minutes when the communication with the BAS fails. For PID algorithms, the output will be set to a level between 0 and 100%, overriding the output limits of the control module. For On/Off algorithms, the output will be set to a level of 0 or 1. To allow the Shutoff mode to be active in a particular module, the Enable Shutoff mode must be set to 1. In PID algorithms, if Enable OFF Trans is set at 1 the Shutoff mode is changed to the Off mode if PV < WSP (Off mode) in a heating controller (PB is negative), and if PV > WSP (Off mode) in a cooling controller (PB is positive). In Shutoff mode, the control module will assume a configured output value of between 0 and 100%, overriding the output limits of the control module. Via the BAS/Companion/Facilitator

Configure using the reference SOFF. Via the GX Tool

To allow the Shutoff mode to be active, select PID or On/Off module, and then Data to call up the Data Window. Enter the value 1 in the Ena. Shutoff field. If you do not want the Shutoff mode to be active, leave it at 0. To set the output value, select On/Off or PID, and then Data to call up the Data Window. Enter the value at the Shutoff Out Level field. For the change described above, enter a 1 at Ena OFF Trans.

Configuration Guides - DX-9100 Configuration Guide

197

Page 198

Via the SX Tool

Under Program Modules, set the Enable Startup mode via PM Item PMnOPT (RI.01) bit X1. Set the PID output value under Program Modules at Alg. Item SOL (RI.51). Set the On/Off output value at PM Item PMnOPT (RI.01) bit X2 (SOFL). Activate and de-activate this mode under General Module by setting bit X7 of Item SUP (RI.01) (SOFF). Set Shutoff to Off change under Program Modules at PM Item PMnOPT (RI.01) bit X9 (SOTO). The status of the mode can be seen under Program Modules at PM Item PMnST (RI.72) bit X9 (SOF). Hold Mode

Each programmable function module, output module, time schedule module, or extension module can be commanded to operate in Hold mode by the BAS. It will remain active until the hold command is changed. Hold mode is not interrupted when the serial communication link fails. Overriding from the DX front panel (using the <A/M> key), also puts certain output and programmable modules in Hold mode. In Hold mode, the output of the module is not updated by the Control algorithm and can be directly controlled by the BAS. Refer also to Power Up Conditions - Hold Mode. Via the BAS/Companion/Facilitator

Hold modes are automatically set when overriding the output value of a programmable module, output module, or extension module. Via the GX Tool

Modules cannot be put in Hold mode directly by the GX Tool. Hold modes may, however, be set and reset by the PLC or on power up. Refer to Programmable Logic Control Configuration - PLC User-Defined Program, and Power Up Conditions - Hold Mode in this guide.

198

Configuration Guides - DX-9100 Configuration Guide

Page 199

Via the SX Tool

For each programmable function module, the control and status of Hold modes is available under Program Modules at PM Item PMnHDC (RI.70) bits X1-X8. For time schedule modules, the control of Hold mode is available under Time Sched TSnSTA (RI.06) bit X1 (TSnHLD). For analog output modules, the control of Hold mode is available under Output Modules at Item AOC (RI.07) bit X1 (OUH). For digital output modules, the control of Hold mode is available under Output Modules at Item DOC (RI.12) bit X1 (OUH). For extension module outputs, the control of Hold mode is available under XT Modules at Item XTnHDC (RI.69) bits X1-X8 (OUH1-8). Computer Mode

Each PID or On/Off controller can be commanded to operate in Computer mode by a BAS. It will remain active until the BAS changes the mode, or communication is lost for 120 minutes. In DX-9100 Version 1.1 or later, the Computer mode will be inactive during any period of serial link communication failure. See Serial Link Monitoring further in this document. The calculation of the WSP of a controller in Computer mode is no longer performed by the controller and the BAS must set the value of WSP. It is not possible to change the WSP from the DX front panel when Computer mode is active. In the DX-9100 controllers, Versions 1 and 2 (firmware Version 1.1 or later), the Computer mode will also be inactive during any period of serial link communication failure. This does not apply to the DX-912x Controller, Version 3. See Serial Link Monitoring further in this document. Via the BAS/Companion/Facilitator

The Computer mode is automatically set when overriding a Working Setpoint Value (WSP) in a programmable control module. Via the GX Tool

Modules cannot be put in Computer mode directly by the GX Tool. Computer modes may, however, be set and reset by the PLC. Refer to Programmable Logic Control Configuration - PLC User-Defined Program in this guide.

Configuration Guides - DX-9100 Configuration Guide

199

Page 200

Via the SX Tool

For each programmable function module configured as PID or On/Off controller, under Program Modules, set PM Item PMnHDC (RI.70) bit X2, then adjust WSP (RI.61). Controlling Digital Outputs

The BAS can control the status of the digital outputs to On or Off by directly overriding the triacs. Via the GX Tool

The override of digital outputs cannot be controlled directly by the GX Tool. Note: BAS commands to digital outputs do not pass through the Digital Output Modules, and therefore the DX front panel display does not follow the status of the output triac when supervisory control is enabled (see Figure 55).

Configuration Control (DO Source Connection)

Digital

Output

Output

Hardware

Module

(Triac)

Front Panel Display and Control

Supervisory System Override dxcon057

Figure 55: Controlling Digital Outputs by BAS Override For On/Off type digital outputs, it is possible to display the true status of the digital output when under BAS override control by connecting the status of the digital output hardware (triac) to the source connection of the digital output module via PLC logic (see Figure 56). When the digital output override is enabled by the BAS, the output module is controlled by the status of the hardware. When the digital output override is not enabled, the output module is controlled by the configured source.

200

Configuration Guides - DX-9100 Configuration Guide