Page 201

DOn

DOnE

LRSn

DOnE DO Source

DOn Status

PLC Logic

LRSn

Digital Output Module

Output Hardware (Triac) dxcon058

Figure 56: Display of True Digital Output Status on DX Front Panel when under BAS Override Control Via the SX Tool

First, the SX may enable control of the six digital (triac) outputs of the controller by setting bits X9 to X14 of Item SUP (RI.01) under General Module. Control the triacs On or Off by setting bits X1 to X6 of Item SUP (RI.01) (under General Module) to 1 or 0, respectively. The status of the triacs can be seen under General Module at Item TOS (RI.05) X1=D03...X6=D08. Maintenance Control

When any parameter is changed in the controller, Maintenance Started (under General Module, bit X1 of Item MNT (RI.02)) will be set as the change is started and Maintenance Stopped, bit X2 of Item MNT (RI.02), will be set as the change is completed. Changes can be made from the front panel, a service module, or the DX LCD Display. These bits can only be reset by a command from BASs and are used to alert a remote operator that changes have been made. Via the BAS

Configure using the reference MNT. (Not available on Companion/Facilitator Systems.) Via GX Tool (Versions 1.4, 2.3, 3.3, or Later)

In the PLC, the MNT variable is listed under DIAGNOSTIC and represents Maintenance Stopped. Via SX Tool

The logic variables may be seen under General Module as follows: Item MNT (RI.02) X1 = 1 Maintenance Started X2 = 1 Maintenance Stopped Configuration Guides - DX-9100 Configuration Guide

201

Page 202

Counter Size

Four bytes have been allocated for counter data in the controller and a value of up to 9,999,999 can be displayed on the front panel of the controller. Certain BASs (Metasys system, for example) only read the least significant 15 bits and provide extensive facilities to store counter data in computer memory, on diskette, or tape. To enable the synchronization of the DX-9100 display panel with BASs, the reset of counter values can be configured as follows: Via the GX Tool

Select Edit-Global Data. Under Counter Type, mark the 15-bit (Metasys system) or 4-byte field. Via the SX Tool

Under General Module, Item DXS1 (RI.32), set bit X4 as follows: X4 = 0 Select 15-bit counters (Counter resets at 32,767) X4 = 1 Select 4-byte counters (Counter resets at 9,999,999) Serial Link Monitoring

There are two logic variables available in the Version 1 or 2 controller, which indicate the status of the BAS and the serial link. They may be used in the PLC to enable standalone control sequencers or local time schedules, for example. Only the logic variable SSA is available in the Version 3 controller. The logic variable SSA (BAS Active) is set by the BAS to enable the supervisory functions of the controller. This logic variable must be set by the BAS at least every two hours as the controller will automatically reset the bit two hours after the last update. The SSA bit indicates that the BAS has been active within the last two hours, or that the BAS has not been active for a period of more than two hours. When the SSA bit is not set, the following BAS control modes are automatically cancelled: Shutoff mode

Computer mode

Startup mode

Digital Outputs Enable and Command

The logic variable SLF (Serial Link Failure) (not available in the Version 3 controller) indicates the status of the serial link independently of any BAS functions. In a Version 1 or 2 DX-9100, the bit is reset when the N2 Bus serial link communications are good, and set when the N2 Bus serial link communications have been absent or unreadable for a period of more than one minute. In a DX-912x (Firmware Version 3), the SLF bit is not used and is always reset. When the SLF bit is set, the following BAS Control mode is not active: Computer mode (Firmware Version 1.1 or later) 202

Configuration Guides - DX-9100 Configuration Guide

Page 203

Via GX Tool

In the PLC, the SSA variable is listed under SUPERV and the SLF variable is listed under DIAGNOSTIC. Note: DIAGNOSTIC will be available in GX Tool versions later than Version 3.0. Via SX Tool

The logic variables may be seen in the General Module as follows: Item SUP (RI.01) X16 = 0

SSA

X16 = 1

BAS Not Active (after two hours) BAS Active

Item DIAG (RI.03)

GX Labels

X5

= 0

X5

= 1

SLF

Serial Link OK Serial Link Failure (after one minute)

Points for PLC

DOnC

A 1 when the BAS has commanded the digital output to be On.

DOnE

A 1 when the BAS has taken control of the digital output.

MNT

A 1 when an Item has been change from the front panel, service module or DX LCD Display.

SLF

Serial Link Failure. Set to 1 60 seconds after the last message from the BAS.

SOFF

A 1 when the BAS has commanded the Shutoff mode.

SSA

A 1 when the BAS is active, and returns to 0 two hours after the last command from the BAS.

STUP

A 1 when the BAS has commanded the Startup mode.

SLF

Serial Link Failure. Set to 1 60 seconds after the last message from the BAS.

Configuration Guides - DX-9100 Configuration Guide

203

Page 204

Controller Diagnostics

There are four logic variables available in the controller to provide diagnostic information. The first is the serial link failure condition (SLF) described above. The second indicates when the internal lithium battery has discharged to approximately 20% of its initial capacity (BATLOW). The third indicates that a trend log buffer has reached its read request limit (HTRR) as described under Trend Log. The fourth is the Maintenance Control Item described above.

Logic Variables

Via GX Tool

In the SLF, BATLOW, HTRR, and MNT variables are listed under DIAGNOSTIC. Note: DIAGNOSTIC will be available in the GX Tool versions later than Version 3.0. Via SX Tool

The logic variables may be seen in the General Module under Item DIAG (RI.03): X2 = 0

BATLOW lithium battery OK

X2 = 1

BATLOW lithium battery low charge

X4 = 1

HTRR one or more trend log buffers are full

X5 = 0

SLF serial link OK

X5 = 1

SLF serial link failure (after one minute)

The MNT variable may be seen in the General Module under Item MNT (RI.02). GX Labels

BATLOW

A 1 when the DX lithium battery needs to be replaced.

HTRR

A 1 when one or more trend log buffers is full.

MNT

A 1 when an Item has been change from the front panel, service module or DX LCD Display.

SLF

Serial Link Failure. Set to 1 60 seconds after the last message from the BAS.

Power Up Conditions

When the controller is powered up after a 24 VAC power interruption, various operating modes can be set or reset to allow a predetermined startup sequence of control operations.

Hold Mode

At power up, output modules can be set to Hold mode, reset from Hold mode (set to 0), or may retain the last mode before power failure. These commands take priority over the Supervisory mode command initialization described in the next section, Supervisory Mode Commands Initialization.

204

Configuration Guides - DX-9100 Configuration Guide

Page 205

Via the GX Tool

For analog outputs, select AOn and then Data to call up the Data Window. For digital outputs, select DOn and then Data to call up the Data Window (only for PAT or DAT modules). Note: The Hold mode for DO On/Off, PULSE, or STA/STO modules can only be configured via the SX Tool. At the Hold on Powerup (0=N) field, when 1 is entered, the module will be put in hold on power up. The Hold mode can be released back to auto control from a BAS, the SX, the PLC, or via the DX front panel. At the Auto on Powerup (0=N) field, when 1 is entered, the module will release this module’s Hold mode on power up. If both are 1, then the Hold setting takes precedence. If both are 0, the Hold mode status will not be changed on Power Up (it will remain in the same state as prior to the power failure), unless the Init. On PowerUp has been set (as described under Supervisory Mode Commands Initialization below). Via the SX Tool

Table 22: Configuration Bits for Hold Mode Power Up Control Module

Configuration Bits

Analog Output Modules (RI.00)

(AOTn, X7, X8) Under Output Modules.

Digital Output Modules (RI.00)

(DOTn, X7, X8) Under Output Modules.

The desired settings are made in the Item and bits shown above.

Supervisory Mode Commands Initialization bit X8 = 0

The Hold mode is not altered after a power failure. (See the DX-9100 Global Data section in the beginning of this document.)

bit X8 = 1

The Hold mode is set at power up to the status set in bit X7.

bit X7 = 0

The Hold mode is set to hold at power up if bit X8 is set.

bit X7 = 1

The Hold mode is reset (set to 0) at power up if bit X8 is set.

The BAS control settings can be programmed to remain set after a power failure or to be initialized to Off after a power failure. The Hold on Power Up and Auto on Power Up take priority for AO, DAT, and PAT modules over the Init. on Power Up command.

Configuration Guides - DX-9100 Configuration Guide

205

Page 206

Via the GX Tool

Select Edit-Global Data. Under Init. On PowerUp, select maintained or cancelled. maintained=

Retain BAS commands cancelled =

Release BAS commands

Via the SX Tool

Under General Module DX-9100 Type Settings, set bit X8 of Item DXS1 (RI.32) as follows:

Programmable Logic Controller (PLC)

X8 = 0

No initialization on power up

X8 = 1

Initialize on power up

At power up, the PLC always runs from the first instruction in the program. Special power up routines should therefore be configured at the beginning of the program. These routines will not be executed in subsequent program cycles when the address of the first non-power up instruction is entered in the END instruction. In the GX-9100 Tool, the location of the first non-power up instruction is marked by the RSR element in the ladder diagram. Power up routines may be used, for example, to set or reset Hold modes based upon prevailing conditions at the time of power up, to set timers to provide a sequential startup of equipment, or to prevent the startup of equipment until building conditions have stabilized after the return of power. Refer to the Programmable Logic Control Configuration section of this document, as well as to the Programmable Logic Control section in the DX-9100 Extended Digital Controller Technical Bulletin (LIT 6364020) in FAN 636.4 or 1628.4.

Download/ Upload Download via the N2 Bus (Versions 1 and 2 Only)

Via the GX Tool

Connect an RS-232-C/RS-485 converter (type MM-CVT101-x in North America and type IU-9100-810x in Europe) to one of the serial communication ports (COM1 or COM2) of the personal computer on which the GX Tool is running. Connect the N2 Bus of the DX-9100 to the converter unit connected to the PC. Set the address switches and jumpers on the DX-9100 and XT/XTM/XP devices (if used) as required, and connect the XT/XTM/XP devices to the XT Bus of the DX-9100.

206

Configuration Guides - DX-9100 Configuration Guide

Page 207

If the DX-9100 (and XT/XTM/XP devices) are installed and wired, verify all field wiring and sensor voltage/current signals. It is recommended that controlled devices be isolated during download and initial startup. Note: Do not download an untested configuration into an installed device. Test the configuration on a simulator panel before downloading. Apply 24 VAC power to the DX-9100 and the XT/XTM/XP devices, if connected. On the GX Tool, with the needed configuration on screen, select Action - Download, and then the Item to be downloaded, as in Table 23. Table 23: Downloading, Versions 1 and 2 Configuration

Items to be Downloaded

DX and XT/XTM

Downloads complete configuration to DX and all configured XT/XTMs (all configured XT/XTMs must be online). Note: This option must be selected when downloading a DX with XT//XTMs for the first time.

DX

Downloads all configuration information required by DX (all configured XT/XTMs must be online, but XT/XTM information is not downloaded).

XT/XTM

Downloads all configuration information required by XT/XTM (excludes DX information).

Calibration

Downloads calibration information only. Note: Ensure that the correct calibration information for the connected controller is contained in the configuration on screen.

Time

Downloads the current PC clock time.

Enter the DX-9100 address (0-255) in the Address field. Under Port, select the PC serial communication port (Com 1 or 2). DX Version 1.4, 2.3, 3.3, or later: Enter the password code if the configuration in the controller has been protected by a password. Click on OK to confirm entries. Checks are made before the data is downloaded to the controller. The user may abort the download process by selecting CANCEL. Download via RS-232-C Port (Versions 2 and 3 Only)

Via the GX Tool

Connect the serial communication port of the PC directly to the RS-232-C port of the DX-9100 Controller. See DX-9100 Extended Digital Controller Technical Bulletin (LIT-6364020) in FAN 636.4 or 1628.4 for details. Proceed as above in the Download via the N2 Bus (Versions 1 and 2 Only) section.

Configuration Guides - DX-9100 Configuration Guide

207

Page 208

Version 3 Only

Select the Item to be downloaded, as in the table below. Table 24: Downloading, Version 3

Upload via the N2 Bus or RS-232-C Port

Configuration

Items to be Downloaded

DX, XT/XTM, Network

Downloads complete configuration to DX, including LONW ORKS Network input/output information, and to all configured XT/XTMs (all configured XT/XTMs must be online). Note: This option must be selected when downloading a Version 3 DX with or without XT/XTMs for the first time.

DX

Downloads all configuration information required by DX, excluding LONW ORKS Network input/output information, and XT/XTM information.

XT/XTM

Downloads all configuration information required by XT/XTM (excludes DX information).

Network

Downloads LONW ORKS Network input/output information only.

Calibration

Downloads calibration information only. Note: Ensure that the correct calibration information for the connected controller is contained in the configuration on screen.

Time

Downloads the current PC clock time.

Via the GX Tool

Only complete DX-9100/XT-9100/XTM-905 configurations should be uploaded from the DX-9100. Select Action - Upload, and then the Item to be uploaded, for example, DX and XT/XTM. Enter the DX-9100 address (0-255) in the Address field. Under Port, select the PC serial communication port (Com 1 or 2). DX Version 1.4, 2.3, 3.3, or later: Enter the password code if the configuration in the controller has been protected by a password. Click on OK to confirm entries. If the configuration in the controller matches that on the GX Tool screen, the parameters will be uploaded from the controller and replace those in the GX Tool configuration. If the configuration does not match that on the GX Tool screen, the user will be prompted to save the displayed GX Tool configuration and save the uploaded configuration to another file. Via the SX Tool

The configuration entered into the DX-9100 Controller may be stored in the service module as an algorithm for transfer to another controller when not protected by a password. Refer to the SX-9120 Service Module User’s Guide (LIT-6364070) in FAN 636.4 for further details.

208

Configuration Guides - DX-9100 Configuration Guide

Page 209

Calibration Values

Each DX-9100 Controller has a set of unique calibration values, which are set in the factory before delivery. These calibration values are stored in EEPROM and it will not normally be necessary to change or reenter these values during the life of the controller. If the user wishes to secure the calibration data on diskette, the calibration values may be uploaded and downloaded using the GX Tool. If it becomes necessary to recalibrate the inputs and outputs of a controller, this can be done using the SX Tool. See the SX-9100 Service Module User’s Guide (LIT-6364070) in FAN 636.4.

Upload/ Download

Via the GX Tool

Connect the DX-9100 Controller to the PC as described under Download/Upload. To upload the calibration values, on the GX Tool select File, then New to clear the PC screen. Select Action, then Upload. Select Calibration and PC Port (1 or 2). Enter the DX-9100 Controller address (0-255). Press Enter. When the upload is complete, press Enter, reselect File and then Save. Save the uploaded calibration values in a file unique for this controller. To download calibration values, select File and then Open. Open the file with the calibration values unique to this controller. Select Action and Download. Select Calibration and PC Port (1 or 2). Enter the DX-9100 Controller address (0-255). Press Enter. For more details, refer to the GX-9100 Software Configuration Tool User’s Guide (LIT-6364060) in FAN 636.4 or 1628.4.

Configuration Guides - DX-9100 Configuration Guide

209

Page 210

210

Configuration Guides - DX-9100 Configuration Guide