The text of a manual · part 23 of 31
DX-9100 Configuration Guide: Appendix A: SX Tool Item Description and Tables
Pages 211 to 216 of 288, from DX-9100 Configuration Guide
The original document is the PDF (1.3 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Johnson Controls DX-9100
Page 211
Appendix A: SX Tool Item Description and Tables Description of Items Item Address
A configuration is comprised of a set of parameters stored in a series of memory locations in the controller. These parameters are called Items. Each Item is assigned an Item address. Active parameters such as counter values are stored in RAM, and configuration parameters are stored in EEPROM. Data stored in EEPROM type memory is retained even when no battery power is available. A memory area with a certain range of Item addresses for its parameters or Items has been assigned to each module. Each Item within this range has been assigned a Relative Item (RI.) address from which its absolute address can be determined. The absolute address of an Item is the sum of the starting address of the module range and the relative Item address. When using the GX Tool for the DX-9100, the user refers to module tags and numbers, and Item tags or relative addresses. Absolute addresses are not normally required. Note: When using the GX Tool for the DX-9100, the user refers only to module and Item tags. Absolute and relative addresses are used in the SX Tool.
Configuration Guides - DX-9100 Configuration Guide
211
Page 212
Item Type
The information stored in the Items can have one of several formats: Floating Point Numerical Items are real numbers, with a +/- sign. They refer to input or output values, setpoint values, proportional band values, limit values, etc. They are displayed and entered as numbers, with a sign and a decimal point. These Items are shown in the Item List with Number in the Type column. Integer Items are positive whole numbers used as scale factors. These Items are shown in the All Item List with 1 Byte Int or 2 Byte Int in the Type column. Totalized Numerical Items are real positive numbers. They refer to totalized values such as pulse counters and accumulators. They are displayed and entered as whole numbers, without sign and decimal point. These Items are shown in the Item List with 4 Bytes in the Type column. Software Connections show to which Item or logic variable address the Item is connected. This information is entered as numbers representing the address of the connected Item or the index and bit position of a logic variable. A 0 de-selects the connection. These Items are shown in the Item List with Connection in the Type column. Destinations are 2-byte Items, which show the destination address and type of network analog and digital outputs. A 0 represents no destination. These Items are shown in the Item List with Destination in the Type column. Status Items are either 1-byte or 2-byte Items giving information on the actual status or configuration of the modules (Control, Logic, Calculation, Input, or Output), where each bit has a specific meaning as described in the Item List. These Items are shown in the Item List with the number of bytes in the Type column. Data is displayed and entered as bytes. In the list, the bytes are represented using X1-X8 or X1-X16: 1 Byte =
212
X8
X7
X6
X5
X4
X3
X2
X1
2 Bytes = X16 X8
X15 X7
X14 X6
X13 X5
X12 X4
X11 X3
X10 X2
X9 X1
Configuration Guides - DX-9100 Configuration Guide
Page 213
Read/Write Data
Item List
Symbols
The Items shown in the Item List can be divided into three basic categories: •
Input values and status of the controller that can be read but not changed by a BAS. These Items are shown in the Item List with an R in the R/W (Read/Write) column.
•
Variables in the controller that can be read and modified by the SX-9100 Service Module, GX-9100 Graphic Configuration Software, or BAS. These Items are shown on the Item List with an R/W in the R/W (Read/Write) column. (E) indicates that the Item is stored in EEPROM.
•
All other Items in the DX-9100 refer to configuration parameters of the controller and contain information such as analog ranges, module type, connections, etc., and they can only be changed using the SX-9120 Service Module or the GX-9100 Graphic Configuration Software Tool. These Items are shown in the Item List with a CNF in the R/W (Read/Write) column.
Each constant, variable, or value inside a DX-9100 Controller can be addressed through an Item code; the Item List describes all the possible Items. Table 25: Symbols Used in the Item List Symbol
Definition
RI.
Relative Item Index from the beginning of the module
Type
Item Type
R/W
Read/Write Conditions:
R
Read Only Item
R/W
Read/Write Item
R/W(E)
Read/Write Item (EEPROM)
CNF
Configuration Item (EEPROM)
Tag
Label for General Item or bit within an Item
PM Tag
Generic Label for Programmable Function Module Item or bit within an Item
Alg. Tag
Configured Label for Programmable Function Module Item or bit within an Item
Configuration Guides - DX-9100 Configuration Guide
213
Page 214
Item Type
The format of any DX-9100 Item is described by the following types: Number:
Floating point number (2 bytes)
1 Byte:
Unsigned 8-bit hexadecimal number used to transfer logic states or integer numbers 0-255.
2 Bytes:
Unsigned 16-bit hexadecimal number used to transfer logic states or unsigned integer numbers 0-65535.
4 Byte:
Unsigned 32-bit hexadecimal number used to transfer unsigned integer numbers (counters and accumulators).
Connection: Module input software connection (2 bytes). The numeric or logic variable used as a source (input) for a configurable module is defined via a word with the following format: Table 26: For a Logic Connection X16 X15 X8 X7 X8 ... X1 X11 X10 X9 X12 = 0 X13 = 0 X14 = 0 X15 = 1 X16 = 1
X14 X6
X13 X5
X12 X11 X10 X9 X4 X3 X2 X1 Index of Source as in Variable List (Hex.) bit Position (0-7)
Logic Connection Reverse Variable Value
Table 27: For an Analog Connection X16 X15 X8 X7 X12 ... X1 X15 = 0 X16 = 1
X14 X6
X13 X12 X11 X10 X9 X5 X4 X3 X2 X1 Item Address of Source as Listed In Items List Analog Connection Negate Variable Value
A 0 represents no connection. Destination (2 Bytes) The destination address for network outputs is defined via a word with the following format: Table 28: For a Network Digital Output Destination X16 X15 X14 X8 X7 X6 X8 ... X1 X13 ... X9 X15 X14 = 01 X16 = 1
214
X13 X5
X12 X11 X10 X9 X4 X3 X2 X1 Destination Controller Address (1-255) Destination Input Number (1-8) System 91 Device Digital Output
Configuration Guides - DX-9100 Configuration Guide
Page 215
Table 29: For a Network Analog Output Destination X16 X15 X8 X7 X8 ... X1 X13 ... X9 X15 X14 = 01 X16 = 0
X14 X6
X13 X5
X12 X11 X10 X9 X4 X3 X2 X1 Destination Controller Address (1-255) Destination Input Number (1-16) System 91 Device Analog Output
A 0 represents no destination. A DX-9100 floating point number consists of two bytes with following format:
Floating Point Numbers
Table 30: Floating Point Numbers 15 E3
14 E2
13 E1
12 E0 where:
11 S
10 9 M10 M9
8 M8
EEEE S MMMMMMMMMMM
7 M7
= = =
6 M6
5 M5
4 M4
3 M3
2 M2
1 M1
0 M0
4-bit exponent sign (1=negative) 11-bit mantissa
•
A number is normalized when the most significant bit is true (M10 = 1).
•
A number is zero when all bits of the mantissa are 0.
•
The value of a number is: <NUMBER> = <SIGN> * .<MANTISSA> * 2 exp <EXPONENT>
Table 31: Floating Point Number Examples 1 -1 100
EEPROM Items
= = =
1400H 1C00H 7640H or or or
B001H B801H B064H
When writing Items from a BAS, it is important to note that EEPROM Items can only be written approximately 10,000 times, so that cyclical processes in the BAS that result in a write command must be avoided.
Configuration Guides - DX-9100 Configuration Guide
215
Page 216
216
Configuration Guides - DX-9100 Configuration Guide