Page 217

Appendix B: Item Structure General Module Items Structure

Table 32: Module First

Decimal

Module Name

0000H

0000

General Control Module

Table 33: Description RI.

Type

R/W

Tag

Description

00

1 Byte

R

UNIT

Device Model: Version 1.x 05H Version 2.x 15H Version 3.x 25H Supervisory Central Control

01 2 Bytes R/W SUP X16 0 X14 X13 X12 X11 X10 X9 X8 X7 X6 X5 X4 X3 X2 X1 X1 = 1 DO3C X2 = 1 DO4C X3 = 1 DO5C X4 = 1 DO6C X5 = 1 DO7C X6 = 1 DO8C X7 = 1 SOFF (SOFC) X8 = 1 STUP (STAC) X9 = 1 DO3E X10 = 1 DO4E X11 = 1 DO5E X12 = 1 DO6E X13 = 1 DO7E X14 = 1 DO8E X15 = DIAL X16 = 1 SSA 02 1 Byte R/W MNT 0 0 0 0 0 0 X2 X1 X1 = 1 X2 = 1 03 0 0 0 0

2 Byte R DIAG 0 0 0 0 0 0 0 X5 0 X3 X2 X1 X1 = 1 EEPROM X2 = 1 BATLOW Continued on next page . . .

Set Output 3 On Set Output 4 On Set Output 5 On Set Output 6 On Set Output 7 On Set Output 8 On Shutoff Mode Command Startup Mode Command Enable Output 3 Supervisory Control Enable Output 4 Supervisory Control Enable Output 5 Supervisory Control Enable Output 6 Supervisory Control Enable Output 7 Supervisory Control Enable Output 8 Supervisory Control Dial-Up Flag BAS Active Maintenance Control Maintenance Started Maintenance Stopped Diagnostics

EEPROM Failure (Version 2.0 or Later) Battery Backup Low

Configuration Guides - DX-9100 Configuration Guide

217

Page 218

RI. (Cont.)

Type

R/W

Tag

Description

X3 = 1

EPROM

EPROM Checksum Failure (Version 2.0 or Later)

X4 = 1

HTRR

Historical Trend Read Request (Versions 1.4, 2.3, or Later)

X5 = 1

SLF

Serial Link Failure (not active and Computer Mode disabled)

X6=1

DWNLD

Download Mode is active

X7=1

DEVRST

Device Reset has occurred

X8=1

PASS

Password Protection is active

DICT

Digital Input Counters

04

1 Byte

X8

X7 X6 X5 X1 = 1

X4 X3 X2 X1 DIC1

Count Transition on DI1

X2 = 1

DIC2

Count Transition on DI2

X3 = 1

DIC3

Count Transition on DI3

X4 = 1

DIC4

Count Transition on DI4

X5 = 1

DIC5

Count Transition on DI5

X6 = 1

DIC6

Count Transition on DI6

X7 = 1

DIC7

Count Transition on DI7

X8 = 1

DIC8

Count Transition on DI8

TOS

TRIAC Output Status

05 0

1 Byte 0

X6 X5 X1 = 1

R

R

X4 X3 X2 X1 DO3

Output 3 is On

X2 = 1

DO4

Output 4 is On

X3 = 1

DO5

Output 5 is On

X4 = 1

DO6

Output 6 is On

X5 = 1

DO7

Output 7 is On

X6 = 1

DO8

Output 8 is On

X8=1

XTERR

Failure in any connected XT/XTM (only versions 1.5, 2.5, 3.5 or later)

06

1 Byte

DIS

Digital Input Status

X8

X7 X6 X5 X1 = 1

X4 X3 X2 X1 DI1

R

Digital Input 1 is On

X2 = 1

DI2

Digital Input 2 is On

X3 = 1

DI3

Digital Input 3 is On

X4 = 1

DI4

Digital Input 4 is On

X5 = 1

DI5

Digital Input 5 is On

X6 = 1

DI6

Digital Input 6 is On

X7 = 1

DI7

Digital Input 7 is On

X8 = 1

DI8

Digital Input 8 is On

Continued on next page . . .

218

Configuration Guides - DX-9100 Configuration Guide

Page 219

RI. (Cont.)

Type

R/W

Tag

Description

07

2 Byte

R

AIS

Analog Input Status

X16 X15 X14 X13 X12 X11 X10 X9 X8 X7 X6 X5 X4 X3 X2 X1 X1 = 1 AIH1

08

High Alarm Condition

X2 = 1

AIL1

X3 = 1

AIH2

Low Alarm Condition High Alarm Condition

X4 = 1

AIL2

Low Alarm Condition

X5 = 1

AIH3

High Alarm Condition

X6 = 1

AIL3

Low Alarm Condition

X7 = 1

AIH4

High Alarm Condition

X8 = 1

AIL4

Low Alarm Condition

X9 = 1

AIH5

High Alarm Condition

X10 = 1

AIL5

Low Alarm Condition

X11 = 1

AIH6

High Alarm Condition

X12 = 1

AIL6

Low Alarm Condition

X13 = 1

AIH7

High Alarm Condition

X14 = 1

AIL7

Low Alarm Condition

X15 = 1

AIH8

High Alarm Condition

X16 = 1

AIL8

Low Alarm Condition

LRST1

Logic Results

2 Byte

R

X16 X15 X14 X13 X12 X11 X10 X9 X8 X7 X6 X5 X4 X3 X2 X1 X1 = 1 LRS1

Logic Result Status 1 is On

X2 = 1

LRS2

Logic Result Status 2 is On

X3 = 1

LRS3

Logic Result Status 3 is On

X4 = 1

LRS4

Logic Result Status 4 is On

X5 = 1

LRS5

Logic Result Status 5 is On

X6 = 1

LRS6

Logic Result Status 6 is On

X7 = 1

LRS7

Logic Result Status 7 is On

X8 = 1

LRS8

Logic Result Status 8 is On

X9 = 1

LRS9

Logic Result Status 9 is On

X10 = 1

LRS10

Logic Result Status 10 is On

X11 = 1

LRS11

Logic Result Status 11 is On

X12 = 1

LRS12

Logic Result Status 12 is On

X13 = 1

LRS13

Logic Result Status 13 is On

X14 = 1

LRS14

Logic Result Status 14 is On

X15 = 1

LRS15

Logic Result Status 15 is On

X16 = 1

LRS16

Logic Result Status 16 is On

Continued on next page . . .

Configuration Guides - DX-9100 Configuration Guide

219

Page 220

RI. (Cont.)

Type

R/W

Tag

Description

09

2 Byte

R

LRST2

Logic Results

X16 X15 X14 X13 X12 X11 X10 X9 X8 X7 X6 X5 X4 X3 X2 X1 LRS17 LRS32 10

2 Byte

R/W

LCOS1

X16 X15 X14 X13 X12 X11 X10 X9 X8 X7 X6 X5 X4 X3 X2 X1 X1 = 1 DCO1

11

Logic Constants

Digital Constant 1 is On

X2 = 1

DCO2

Digital Constant 2 is On

X3 = 1

DCO3

Digital Constant 3 is On

X4 = 1

DCO4

Digital Constant 4 is On

X5 = 1

DCO5

Digital Constant 5 is On

X6 = 1

DCO6

Digital Constant 6 is On

X7 = 1

DCO7

Digital Constant 7 is On

X8 = 1

DCO8

Digital Constant 8 is On

X9 = 1

DCO9

Digital Constant 9 is On

X10 = 1

DCO10

Digital Constant 10 is On

X11 = 1

DCO11

Digital Constant 11 is On

X12 = 1

DCO12

Digital Constant 12 is On

X13 = 1

DCO13

Digital Constant 13 is On

X14 = 1

DCO14

Digital Constant 14 is On

X15 = 1

DCO15

Digital Constant 15 is On

X16 = 1

DCO16

Digital Constant 16 is On

LCOS2

Logic Constants

2 Byte

R/W

X16 X15 X14 X13 X12 X11 X10 X9 X8 X7 X6 X5 X4 X3 X2 X1 DCO17 DCO32 Continued on next page . . .

220

Logic Result Status 17-32

Configuration Guides - DX-9100 Configuration Guide

Digital Constant 17-32

Page 221

RI. (Cont.)

Type

R/W

Tag

12

2 Byte Int

R

VER

Version Level of Firmware

13

4 Bytes

R/W

CNTR1

DI1 Pulse Count

14

4 Bytes

R/W

CNTR2

DI2 Pulse Count

15

4 Bytes

R/W

CNTR3

DI3 Pulse Count

16

4 Bytes

R/W

CNTR4

DI4 Pulse Count

17

4 Bytes

R/W

CNTR5

DI5 Pulse Count

18

4 Bytes

R/W

CNTR6

DI6 Pulse Count

19

4 Bytes

R/W

CNTR7

DI7 Pulse Count

20

4 Bytes

R/W

CNTR8

DI8 Pulse Count

21

2 Bytes

CNF spare

22

1 Byte Int

CNF

PC1

Prescaler DI1 Counter

23

1 Byte Int

CNF

PC2

Prescaler DI2 Counter

24

1 Byte Int

CNF

PC3

Prescaler DI3 Counter

25

1 Byte Int

CNF

PC4

Prescaler DI4 Counter

26

1 Byte Int

CNF

PC5

Prescaler DI5 Counter

27

1 Byte Int

CNF

PC6

Prescaler DI6 Counter

28

1 Byte Int

CNF

PC7

Prescaler DI7 Counter

29

1 Byte Int

CNF

PC8

Prescaler DI8 Counter

30

1 Byte

CNF spare

31

Connection

CNF

ALD@

Alarm Disable Condition Source

32

1 Byte

CNF

DXS1

DX9100 Type Settings

X8

X7 X6 X5 X4 = 0

X4 0

0

Description

0 15-bit Counters

X4 = 1

4-byte Counters

X6 X5

Extension Bus Timing

= 00

XT-9100 Default

= 01

XTM-905 Default

=10

200 msec

=11

300 msec

X7 = 0

50 Hz Power Line

X7 = 1

60 Hz Power Line

X8 = 1

Initialize on Power Up

33

2 Byte Int

CNF

ALG

Algorithm (Configuration) Number

34

Number

R/W

ACO1

Analog Constant 1

35

Number

R/W

ACO2

Analog Constant 2

36

Number

R/W

ACO3

Analog Constant 3

37

Number

R/W

ACO4

Analog Constant 4

38

Number

R/W

ACO5

Analog Constant 5

Continued on next page . . .

Configuration Guides - DX-9100 Configuration Guide

221

Page 222

RI. (Cont.)

Type

R/W

Tag

Description

39

Number

R/W

ACO6

Analog Constant 6

40

Number

R/W

ACO7

Analog Constant 7

41

Number

R/W

ACO8

Analog Constant 8

42

1 Byte

R/W

PLCNT

PLC Control and Status

X8

X7 0 0 X1 = 1

0

X3 X2 X1 Set Hold Mode

X2 = 1

Set Single-step Mode

X3 = 1

Execute One PLC Step

X7 = 1

Program Error

X8 = 1

PLC Partial Result

43

2 Bytes

R

PLCPC

PLC Program Counter

44

2 Bytes

R/W

LRST3

Logic Results (Version 1.1 or Later)

X16 X15 X14 X13 X12 X11 X10 X9 X8 X7 X6 X5 X4 X3 X2 X1 LRS33 LRS48 45

2 Bytes

R/W

LRST4

X16 X15 X14 X13 X12 X11 X10 X9 X8 X7 X6 X5 X4 X3 X2 X1 LRS49 LRS64

Logic Result Status 33-48

Logic Results (Version 1.1 or Later)

Logic Result Status 49-64

Versions 1.4, 2.3, 3.3, or Later: 46

2 Bytes

47

2 Bytes

0 X8

0 0 0 X7 X6 X5 X1 = 1

R/W

DXS2

DX-9100 Type Settings (not used)

R

TRSTA

Trend Status

X12 X11 X10 X9 X4 X3 X2 X1

X2 = 1

Trend Read Request 2

X3 = 1

Trend Read Request 3

X4 = 1

Trend Read Request 4

X5 = 1

Trend Read Request 5

X6 = 1

Trend Read Request 6

X7 = 1

Trend Read Request 7

X8 = 1

Trend Read Request 8

X9 = 1

Trend Read Request 9

X10 = 1

Trend Read Request 10

X11 = 1

Trend Read Request 11

X12 = 1

Trend Read Request 12

Continued on next page . . .

222

Trend Read Request 1

Configuration Guides - DX-9100 Configuration Guide

Page 223

Programmable Function Module Items Structure

RI. (Cont.)

Type

48

2 Bytes

0 X8

0 0 0 X7 X6 X5 X1 = 1

R/W

Tag

Description

R/W

PHMAP

Point History Map

X12 X11 X10 X9 X4 X3 X2 X1 Trend 1 used for Point History

X2 = 1

Trend 2 used for Point History

X3 = 1

Trend 3 used for Point History

X4 = 1

Trend 4 used for Point History

X5 = 1

Trend 5 used for Point History

X6 = 1

Trend 6 used for Point History

X7 = 1

Trend 7 used for Point History

X8 = 1

Trend 8 used for Point History

X9 = 1

Trend 9 used for Point History

X10 = 1

Trend 10 used for Point History

X11 = 1

Trend 11 used for Point History

X12 = 1

Trend 12 used for Point History

Table 34: Programmable Function Module Items Structure First

Decimal

Module Name

0040H

0064

Programmable Function Module 01

00A0H

0160

Programmable Function Module 02

0100H

0256

Programmable Function Module 03

0160H

0352

Programmable Function Module 04

01C0H

0448

Programmable Function Module 05

0220H

0544

Programmable Function Module 06

0280H

0640

Programmable Function Module 07

02E0H

0736

Programmable Function Module 08

0340H

0832

Programmable Function Module 09

03A0H

0928

Programmable Function Module 10

0400H

1024

Programmable Function Module 11

0460H

1120

Programmable Function Module 12

Note:

TAG PMnTYP is programmable function module type of Module n.

Configuration Guides - DX-9100 Configuration Guide

223

Page 224

RI.

Type

R/W

Tag

Description

00

1 Byte

CNF

PMnTYP

Programmable Function Module Type

01

2 Bytes

CNF

PMnOPT

Programmable Function Module Options

02

1 Byte

CNF

PMnF1

Function Channel 1 - F1

03

1 Byte

CNF

PMnF2

Function Channel 2 - F2

04

1 Byte

CNF

PMnF3

Function Channel 3 - F3

05

1 Byte

CNF

PMnF4

Function Channel 4 - F4

06

1 Byte

CNF

PMnF5

Function Channel 5 - F5

07

1 Byte

CNF

PMnF6

Function Channel 6 - F6

08

1 Byte

CNF

PMnF7

Function Channel 7 - F7

09

1 Byte

CNF

PMnF8

Function Channel 8 - F8

10

Connection

CNF

PMnI1@

Input Connection - I@1

11

Connection

CNF

PMnI2@

Input Connection - I@2

12

Connection

CNF

PMnI3@

Input Connection - I@3

13

Connection

CNF

PMnI4@

Input Connection - I@4

14

Connection

CNF

PMnI5@

Input Connection - I@5

15

Connection

CNF

PMnI6@

Input Connection - I@6

16

Connection

CNF

PMnI7@

Input Connection - I@7

17

Connection

CNF

PMnI8@

Input Connection - I@8

18

Connection

CNF

PMnI9@

Input Connection - I@9

19

Connection

CNF

PMnI10@

Input Connection - I@10

20

Connection

CNF

PMnI11@

Input Connection - I@11

21

Connection

CNF

PMnI12@

Input Connection - I@12

22

Connection

CNF

PMnI13@

Input Connection - I@13

23

Connection

CNF

PMnI14@

Input Connection - I@14

24

Connection

CNF

PMnI15@

Input Connection - I@15

25

Connection

CNF

PMnI16@

Input Connection - I@16

26

Number

R/W (E)

PMnK1

Module Constant - K1

27

Number

R/W (E)

PMnK2

Module Constant - K2

28

Number

R/W (E)

PMnK3

Module Constant - K3

29

Number

R/W (E)

PMnK4

Module Constant - K4

30

Number

R/W (E)

PMnK5

Module Constant - K5

31

Number

R/W (E)

PMnK6

Module Constant - K6

32

Number

R/W (E)

PMnK7

Module Constant - K7

33

Number

R/W (E)

PMnK8

Module Constant - K8

34

Number

R/W (E)

PMnK9

Module Constant - K9

35

Number

R/W (E)

PMnK10

Module Constant - K10

36

Number

R/W (E)

PMnK11

Module Constant - K11

37

Number

R/W (E)

PMnK12

Module Constant - K12

38

Number

R/W (E)

PMnK13

Module Constant - K13

39

Number

R/W (E)

PMnK14

Module Constant - K14

40

Number

R/W (E)

PMnK15

Module Constant - K15

41

Number

R/W (E)

PMnK16

Module Constant - K16

Continued on next page . . .

224

Configuration Guides - DX-9100 Configuration Guide

Page 225

RI. (Cont.)

Type

R/W

Tag

Description

42

Number

R/W (E)

PMnK17

Module Constant - K17

43

Number

R/W (E)

PMnK18

Module Constant - K18

44

Number

R/W (E)

PMnK19

Module Constant - K19

45

Number

R/W (E)

PMnK20

Module Constant - K20

46

Number

R/W (E)

PMnK21

Module Constant - K21

47

Number

R/W (E)

PMnK22

Module Constant - K22

48

Number

R/W (E)

PMnK23

Module Constant - K23

49

Number

R/W (E)

PMnK24

Module Constant - K24

50

Number

R/W (E)

PMnK25

Module Constant - K25

51

Number

R/W (E)

PMnK26

Module Constant - K26

52

Number

R/W (E)

PMnK27

Module Constant - K27

53

Number

R/W (E)

PMnK28

Module Constant - K28

54

Number

R/W (E)

PMnK29

Module Constant - K29

55

Number

R/W (E)

PMnK30

Module Constant - K30

56

Number

R/W (E)

PMnK31

Module Constant - K31

57

Number

R/W (E)

PMnK32

Module Constant - K32

58

Number

R/W (E)

PMnK33

Module Constant - K33

59 60 61 62 63 64 65 66 67 68 69 70 X8

Number Number Number Number Number Number Number Number Number Number Number 1 Byte X7 X6 X5 X1 = 1 X2 = 1 X3 = 1 X4 = 1 X5 = 1 X6 = 1 X7 = 1 X8 = 1

R/W (E) R/W R/W R/W R/W R/W R/W R/W R/W R R R/W X4 X3 X2

PMnK34 PMnOU1 PMnOU2 PMnOU3 PMnOU4 PMnOU5 PMnOU6 PMnOU7 PMnOU8 PMnAX1 PMnAX2 PMnHDC X1

Module Constant - K34 Output - Channel 1 Output - Channel 2 Output - Channel 3 Output - Channel 4 Output - Channel 5 Output - Channel 6 Output - Channel 7 Output - Channel 8 Auxiliary Output 1 Auxiliary Output 2 Hold Mode Control/Status

71 X8

Hold Channel 1 Hold Channel 2 Hold Channel 3 Hold Channel 4 Hold Channel 5 Hold Channel 6 Hold Channel 7 Hold Channel 8

1 Byte R/W PMnDO X7 X6 X5 X4 X3 X2 X1 X1 = 1 X2 = 1 X3 = 1 X4 = 1 Continued on next page . . .

Logic Outputs Control and Status DO Channel 1 is On DO Channel 2 is On DO Channel 3 is On DO Channel 4 is On

Configuration Guides - DX-9100 Configuration Guide

225

Page 226

RI. (Cont.)

Analog Input Module Items Structure

R

Tag

PMnST

X15 X14 X13 X12 X11 X10 X9 X7 X6 X5 X4 X3 X2 X1 4 Bytes R/W PMnAC1

Description DO Channel 5 is On DO Channel 6 is On DO Channel 7 is On DO Channel 8 is On Programmable Function Module Status

Accumulator 1

74

4 Bytes

R/W

PMnAC2

Accumulator 2

75

4 Bytes

R/W

PMnAC3

Accumulator 3

76

4 Bytes

R/W

PMnAC4

Accumulator 4

77

4 Bytes

R/W

PMnAC5

Accumulator 5

78

4 Bytes

R/W

PMnAC6

Accumulator 6

79

4 Bytes

R/W

PMnAC7

Accumulator 7

80

4 Bytes

R/W

PMnAC8

Accumulator 8

Table 35: Analog Input Module Items Structure First

Decimal

Module Name

04C0H

1216

Analog Input Module 1

04D0H

1232

Analog Input Module 2

04E0H

1248

Analog Input Module 3

04F0H

1264

Analog Input Module 4

0500H

1280

Analog Input Module 5

0510H

1296

Analog Input Module 6

0520H

1312

Analog Input Module 7

0530H

1328

Analog Input Module 8

Note:

226

R/W

X5 = 1 X6 = 1 X7 = 1 X8 = 1 2 Bytes

72 X16 X8 73

Type

TAG AITn is Analog Input Type of Module n.