Page 217
Appendix B: Item Structure General Module Items Structure
Table 32: Module First
Decimal
Module Name
0000H
0000
General Control Module
Table 33: Description RI.
Type
R/W
Tag
Description
00
1 Byte
R
UNIT
Device Model: Version 1.x 05H Version 2.x 15H Version 3.x 25H Supervisory Central Control
01 2 Bytes R/W SUP X16 0 X14 X13 X12 X11 X10 X9 X8 X7 X6 X5 X4 X3 X2 X1 X1 = 1 DO3C X2 = 1 DO4C X3 = 1 DO5C X4 = 1 DO6C X5 = 1 DO7C X6 = 1 DO8C X7 = 1 SOFF (SOFC) X8 = 1 STUP (STAC) X9 = 1 DO3E X10 = 1 DO4E X11 = 1 DO5E X12 = 1 DO6E X13 = 1 DO7E X14 = 1 DO8E X15 = DIAL X16 = 1 SSA 02 1 Byte R/W MNT 0 0 0 0 0 0 X2 X1 X1 = 1 X2 = 1 03 0 0 0 0
2 Byte R DIAG 0 0 0 0 0 0 0 X5 0 X3 X2 X1 X1 = 1 EEPROM X2 = 1 BATLOW Continued on next page . . .
Set Output 3 On Set Output 4 On Set Output 5 On Set Output 6 On Set Output 7 On Set Output 8 On Shutoff Mode Command Startup Mode Command Enable Output 3 Supervisory Control Enable Output 4 Supervisory Control Enable Output 5 Supervisory Control Enable Output 6 Supervisory Control Enable Output 7 Supervisory Control Enable Output 8 Supervisory Control Dial-Up Flag BAS Active Maintenance Control Maintenance Started Maintenance Stopped Diagnostics
EEPROM Failure (Version 2.0 or Later) Battery Backup Low
Configuration Guides - DX-9100 Configuration Guide
217
Page 218
RI. (Cont.)
Type
R/W
Tag
Description
X3 = 1
EPROM
EPROM Checksum Failure (Version 2.0 or Later)
X4 = 1
HTRR
Historical Trend Read Request (Versions 1.4, 2.3, or Later)
X5 = 1
SLF
Serial Link Failure (not active and Computer Mode disabled)
X6=1
DWNLD
Download Mode is active
X7=1
DEVRST
Device Reset has occurred
X8=1
PASS
Password Protection is active
DICT
Digital Input Counters
04
1 Byte
X8
X7 X6 X5 X1 = 1
X4 X3 X2 X1 DIC1
Count Transition on DI1
X2 = 1
DIC2
Count Transition on DI2
X3 = 1
DIC3
Count Transition on DI3
X4 = 1
DIC4
Count Transition on DI4
X5 = 1
DIC5
Count Transition on DI5
X6 = 1
DIC6
Count Transition on DI6
X7 = 1
DIC7
Count Transition on DI7
X8 = 1
DIC8
Count Transition on DI8
TOS
TRIAC Output Status
05 0
1 Byte 0
X6 X5 X1 = 1
R
R
X4 X3 X2 X1 DO3
Output 3 is On
X2 = 1
DO4
Output 4 is On
X3 = 1
DO5
Output 5 is On
X4 = 1
DO6
Output 6 is On
X5 = 1
DO7
Output 7 is On
X6 = 1
DO8
Output 8 is On
X8=1
XTERR
Failure in any connected XT/XTM (only versions 1.5, 2.5, 3.5 or later)
06
1 Byte
DIS
Digital Input Status
X8
X7 X6 X5 X1 = 1
X4 X3 X2 X1 DI1
R
Digital Input 1 is On
X2 = 1
DI2
Digital Input 2 is On
X3 = 1
DI3
Digital Input 3 is On
X4 = 1
DI4
Digital Input 4 is On
X5 = 1
DI5
Digital Input 5 is On
X6 = 1
DI6
Digital Input 6 is On
X7 = 1
DI7
Digital Input 7 is On
X8 = 1
DI8
Digital Input 8 is On
Continued on next page . . .
218
Configuration Guides - DX-9100 Configuration Guide
Page 219
RI. (Cont.)
Type
R/W
Tag
Description
07
2 Byte
R
AIS
Analog Input Status
X16 X15 X14 X13 X12 X11 X10 X9 X8 X7 X6 X5 X4 X3 X2 X1 X1 = 1 AIH1
08
High Alarm Condition
X2 = 1
AIL1
X3 = 1
AIH2
Low Alarm Condition High Alarm Condition
X4 = 1
AIL2
Low Alarm Condition
X5 = 1
AIH3
High Alarm Condition
X6 = 1
AIL3
Low Alarm Condition
X7 = 1
AIH4
High Alarm Condition
X8 = 1
AIL4
Low Alarm Condition
X9 = 1
AIH5
High Alarm Condition
X10 = 1
AIL5
Low Alarm Condition
X11 = 1
AIH6
High Alarm Condition
X12 = 1
AIL6
Low Alarm Condition
X13 = 1
AIH7
High Alarm Condition
X14 = 1
AIL7
Low Alarm Condition
X15 = 1
AIH8
High Alarm Condition
X16 = 1
AIL8
Low Alarm Condition
LRST1
Logic Results
2 Byte
R
X16 X15 X14 X13 X12 X11 X10 X9 X8 X7 X6 X5 X4 X3 X2 X1 X1 = 1 LRS1
Logic Result Status 1 is On
X2 = 1
LRS2
Logic Result Status 2 is On
X3 = 1
LRS3
Logic Result Status 3 is On
X4 = 1
LRS4
Logic Result Status 4 is On
X5 = 1
LRS5
Logic Result Status 5 is On
X6 = 1
LRS6
Logic Result Status 6 is On
X7 = 1
LRS7
Logic Result Status 7 is On
X8 = 1
LRS8
Logic Result Status 8 is On
X9 = 1
LRS9
Logic Result Status 9 is On
X10 = 1
LRS10
Logic Result Status 10 is On
X11 = 1
LRS11
Logic Result Status 11 is On
X12 = 1
LRS12
Logic Result Status 12 is On
X13 = 1
LRS13
Logic Result Status 13 is On
X14 = 1
LRS14
Logic Result Status 14 is On
X15 = 1
LRS15
Logic Result Status 15 is On
X16 = 1
LRS16
Logic Result Status 16 is On
Continued on next page . . .
Configuration Guides - DX-9100 Configuration Guide
219
Page 220
RI. (Cont.)
Type
R/W
Tag
Description
09
2 Byte
R
LRST2
Logic Results
X16 X15 X14 X13 X12 X11 X10 X9 X8 X7 X6 X5 X4 X3 X2 X1 LRS17 LRS32 10
2 Byte
R/W
LCOS1
X16 X15 X14 X13 X12 X11 X10 X9 X8 X7 X6 X5 X4 X3 X2 X1 X1 = 1 DCO1
11
Logic Constants
Digital Constant 1 is On
X2 = 1
DCO2
Digital Constant 2 is On
X3 = 1
DCO3
Digital Constant 3 is On
X4 = 1
DCO4
Digital Constant 4 is On
X5 = 1
DCO5
Digital Constant 5 is On
X6 = 1
DCO6
Digital Constant 6 is On
X7 = 1
DCO7
Digital Constant 7 is On
X8 = 1
DCO8
Digital Constant 8 is On
X9 = 1
DCO9
Digital Constant 9 is On
X10 = 1
DCO10
Digital Constant 10 is On
X11 = 1
DCO11
Digital Constant 11 is On
X12 = 1
DCO12
Digital Constant 12 is On
X13 = 1
DCO13
Digital Constant 13 is On
X14 = 1
DCO14
Digital Constant 14 is On
X15 = 1
DCO15
Digital Constant 15 is On
X16 = 1
DCO16
Digital Constant 16 is On
LCOS2
Logic Constants
2 Byte
R/W
X16 X15 X14 X13 X12 X11 X10 X9 X8 X7 X6 X5 X4 X3 X2 X1 DCO17 DCO32 Continued on next page . . .
220
Logic Result Status 17-32
Configuration Guides - DX-9100 Configuration Guide
Digital Constant 17-32
Page 221
RI. (Cont.)
Type
R/W
Tag
12
2 Byte Int
R
VER
Version Level of Firmware
13
4 Bytes
R/W
CNTR1
DI1 Pulse Count
14
4 Bytes
R/W
CNTR2
DI2 Pulse Count
15
4 Bytes
R/W
CNTR3
DI3 Pulse Count
16
4 Bytes
R/W
CNTR4
DI4 Pulse Count
17
4 Bytes
R/W
CNTR5
DI5 Pulse Count
18
4 Bytes
R/W
CNTR6
DI6 Pulse Count
19
4 Bytes
R/W
CNTR7
DI7 Pulse Count
20
4 Bytes
R/W
CNTR8
DI8 Pulse Count
21
2 Bytes
CNF spare
22
1 Byte Int
CNF
PC1
Prescaler DI1 Counter
23
1 Byte Int
CNF
PC2
Prescaler DI2 Counter
24
1 Byte Int
CNF
PC3
Prescaler DI3 Counter
25
1 Byte Int
CNF
PC4
Prescaler DI4 Counter
26
1 Byte Int
CNF
PC5
Prescaler DI5 Counter
27
1 Byte Int
CNF
PC6
Prescaler DI6 Counter
28
1 Byte Int
CNF
PC7
Prescaler DI7 Counter
29
1 Byte Int
CNF
PC8
Prescaler DI8 Counter
30
1 Byte
CNF spare
31
Connection
CNF
ALD@
Alarm Disable Condition Source
32
1 Byte
CNF
DXS1
DX9100 Type Settings
X8
X7 X6 X5 X4 = 0
X4 0
0
Description
0 15-bit Counters
X4 = 1
4-byte Counters
X6 X5
Extension Bus Timing
= 00
XT-9100 Default
= 01
XTM-905 Default
=10
200 msec
=11
300 msec
X7 = 0
50 Hz Power Line
X7 = 1
60 Hz Power Line
X8 = 1
Initialize on Power Up
33
2 Byte Int
CNF
ALG
Algorithm (Configuration) Number
34
Number
R/W
ACO1
Analog Constant 1
35
Number
R/W
ACO2
Analog Constant 2
36
Number
R/W
ACO3
Analog Constant 3
37
Number
R/W
ACO4
Analog Constant 4
38
Number
R/W
ACO5
Analog Constant 5
Continued on next page . . .
Configuration Guides - DX-9100 Configuration Guide
221
Page 222
RI. (Cont.)
Type
R/W
Tag
Description
39
Number
R/W
ACO6
Analog Constant 6
40
Number
R/W
ACO7
Analog Constant 7
41
Number
R/W
ACO8
Analog Constant 8
42
1 Byte
R/W
PLCNT
PLC Control and Status
X8
X7 0 0 X1 = 1
0
X3 X2 X1 Set Hold Mode
X2 = 1
Set Single-step Mode
X3 = 1
Execute One PLC Step
X7 = 1
Program Error
X8 = 1
PLC Partial Result
43
2 Bytes
R
PLCPC
PLC Program Counter
44
2 Bytes
R/W
LRST3
Logic Results (Version 1.1 or Later)
X16 X15 X14 X13 X12 X11 X10 X9 X8 X7 X6 X5 X4 X3 X2 X1 LRS33 LRS48 45
2 Bytes
R/W
LRST4
X16 X15 X14 X13 X12 X11 X10 X9 X8 X7 X6 X5 X4 X3 X2 X1 LRS49 LRS64
Logic Result Status 33-48
Logic Results (Version 1.1 or Later)
Logic Result Status 49-64
Versions 1.4, 2.3, 3.3, or Later: 46
2 Bytes
47
2 Bytes
0 X8
0 0 0 X7 X6 X5 X1 = 1
R/W
DXS2
DX-9100 Type Settings (not used)
R
TRSTA
Trend Status
X12 X11 X10 X9 X4 X3 X2 X1
X2 = 1
Trend Read Request 2
X3 = 1
Trend Read Request 3
X4 = 1
Trend Read Request 4
X5 = 1
Trend Read Request 5
X6 = 1
Trend Read Request 6
X7 = 1
Trend Read Request 7
X8 = 1
Trend Read Request 8
X9 = 1
Trend Read Request 9
X10 = 1
Trend Read Request 10
X11 = 1
Trend Read Request 11
X12 = 1
Trend Read Request 12
Continued on next page . . .
222
Trend Read Request 1
Configuration Guides - DX-9100 Configuration Guide
Page 223
Programmable Function Module Items Structure
RI. (Cont.)
Type
48
2 Bytes
0 X8
0 0 0 X7 X6 X5 X1 = 1
R/W
Tag
Description
R/W
PHMAP
Point History Map
X12 X11 X10 X9 X4 X3 X2 X1 Trend 1 used for Point History
X2 = 1
Trend 2 used for Point History
X3 = 1
Trend 3 used for Point History
X4 = 1
Trend 4 used for Point History
X5 = 1
Trend 5 used for Point History
X6 = 1
Trend 6 used for Point History
X7 = 1
Trend 7 used for Point History
X8 = 1
Trend 8 used for Point History
X9 = 1
Trend 9 used for Point History
X10 = 1
Trend 10 used for Point History
X11 = 1
Trend 11 used for Point History
X12 = 1
Trend 12 used for Point History
Table 34: Programmable Function Module Items Structure First
Decimal
Module Name
0040H
0064
Programmable Function Module 01
00A0H
0160
Programmable Function Module 02
0100H
0256
Programmable Function Module 03
0160H
0352
Programmable Function Module 04
01C0H
0448
Programmable Function Module 05
0220H
0544
Programmable Function Module 06
0280H
0640
Programmable Function Module 07
02E0H
0736
Programmable Function Module 08
0340H
0832
Programmable Function Module 09
03A0H
0928
Programmable Function Module 10
0400H
1024
Programmable Function Module 11
0460H
1120
Programmable Function Module 12
Note:
TAG PMnTYP is programmable function module type of Module n.
Configuration Guides - DX-9100 Configuration Guide
223
Page 224
RI.
Type
R/W
Tag
Description
00
1 Byte
CNF
PMnTYP
Programmable Function Module Type
01
2 Bytes
CNF
PMnOPT
Programmable Function Module Options
02
1 Byte
CNF
PMnF1
Function Channel 1 - F1
03
1 Byte
CNF
PMnF2
Function Channel 2 - F2
04
1 Byte
CNF
PMnF3
Function Channel 3 - F3
05
1 Byte
CNF
PMnF4
Function Channel 4 - F4
06
1 Byte
CNF
PMnF5
Function Channel 5 - F5
07
1 Byte
CNF
PMnF6
Function Channel 6 - F6
08
1 Byte
CNF
PMnF7
Function Channel 7 - F7
09
1 Byte
CNF
PMnF8
Function Channel 8 - F8
10
Connection
CNF
PMnI1@
Input Connection - I@1
11
Connection
CNF
PMnI2@
Input Connection - I@2
12
Connection
CNF
PMnI3@
Input Connection - I@3
13
Connection
CNF
PMnI4@
Input Connection - I@4
14
Connection
CNF
PMnI5@
Input Connection - I@5
15
Connection
CNF
PMnI6@
Input Connection - I@6
16
Connection
CNF
PMnI7@
Input Connection - I@7
17
Connection
CNF
PMnI8@
Input Connection - I@8
18
Connection
CNF
PMnI9@
Input Connection - I@9
19
Connection
CNF
PMnI10@
Input Connection - I@10
20
Connection
CNF
PMnI11@
Input Connection - I@11
21
Connection
CNF
PMnI12@
Input Connection - I@12
22
Connection
CNF
PMnI13@
Input Connection - I@13
23
Connection
CNF
PMnI14@
Input Connection - I@14
24
Connection
CNF
PMnI15@
Input Connection - I@15
25
Connection
CNF
PMnI16@
Input Connection - I@16
26
Number
R/W (E)
PMnK1
Module Constant - K1
27
Number
R/W (E)
PMnK2
Module Constant - K2
28
Number
R/W (E)
PMnK3
Module Constant - K3
29
Number
R/W (E)
PMnK4
Module Constant - K4
30
Number
R/W (E)
PMnK5
Module Constant - K5
31
Number
R/W (E)
PMnK6
Module Constant - K6
32
Number
R/W (E)
PMnK7
Module Constant - K7
33
Number
R/W (E)
PMnK8
Module Constant - K8
34
Number
R/W (E)
PMnK9
Module Constant - K9
35
Number
R/W (E)
PMnK10
Module Constant - K10
36
Number
R/W (E)
PMnK11
Module Constant - K11
37
Number
R/W (E)
PMnK12
Module Constant - K12
38
Number
R/W (E)
PMnK13
Module Constant - K13
39
Number
R/W (E)
PMnK14
Module Constant - K14
40
Number
R/W (E)
PMnK15
Module Constant - K15
41
Number
R/W (E)
PMnK16
Module Constant - K16
Continued on next page . . .
224
Configuration Guides - DX-9100 Configuration Guide
Page 225
RI. (Cont.)
Type
R/W
Tag
Description
42
Number
R/W (E)
PMnK17
Module Constant - K17
43
Number
R/W (E)
PMnK18
Module Constant - K18
44
Number
R/W (E)
PMnK19
Module Constant - K19
45
Number
R/W (E)
PMnK20
Module Constant - K20
46
Number
R/W (E)
PMnK21
Module Constant - K21
47
Number
R/W (E)
PMnK22
Module Constant - K22
48
Number
R/W (E)
PMnK23
Module Constant - K23
49
Number
R/W (E)
PMnK24
Module Constant - K24
50
Number
R/W (E)
PMnK25
Module Constant - K25
51
Number
R/W (E)
PMnK26
Module Constant - K26
52
Number
R/W (E)
PMnK27
Module Constant - K27
53
Number
R/W (E)
PMnK28
Module Constant - K28
54
Number
R/W (E)
PMnK29
Module Constant - K29
55
Number
R/W (E)
PMnK30
Module Constant - K30
56
Number
R/W (E)
PMnK31
Module Constant - K31
57
Number
R/W (E)
PMnK32
Module Constant - K32
58
Number
R/W (E)
PMnK33
Module Constant - K33
59 60 61 62 63 64 65 66 67 68 69 70 X8
Number Number Number Number Number Number Number Number Number Number Number 1 Byte X7 X6 X5 X1 = 1 X2 = 1 X3 = 1 X4 = 1 X5 = 1 X6 = 1 X7 = 1 X8 = 1
R/W (E) R/W R/W R/W R/W R/W R/W R/W R/W R R R/W X4 X3 X2
PMnK34 PMnOU1 PMnOU2 PMnOU3 PMnOU4 PMnOU5 PMnOU6 PMnOU7 PMnOU8 PMnAX1 PMnAX2 PMnHDC X1
Module Constant - K34 Output - Channel 1 Output - Channel 2 Output - Channel 3 Output - Channel 4 Output - Channel 5 Output - Channel 6 Output - Channel 7 Output - Channel 8 Auxiliary Output 1 Auxiliary Output 2 Hold Mode Control/Status
71 X8
Hold Channel 1 Hold Channel 2 Hold Channel 3 Hold Channel 4 Hold Channel 5 Hold Channel 6 Hold Channel 7 Hold Channel 8
1 Byte R/W PMnDO X7 X6 X5 X4 X3 X2 X1 X1 = 1 X2 = 1 X3 = 1 X4 = 1 Continued on next page . . .
Logic Outputs Control and Status DO Channel 1 is On DO Channel 2 is On DO Channel 3 is On DO Channel 4 is On
Configuration Guides - DX-9100 Configuration Guide
225
Page 226
RI. (Cont.)
Analog Input Module Items Structure
R
Tag
PMnST
X15 X14 X13 X12 X11 X10 X9 X7 X6 X5 X4 X3 X2 X1 4 Bytes R/W PMnAC1
Description DO Channel 5 is On DO Channel 6 is On DO Channel 7 is On DO Channel 8 is On Programmable Function Module Status
Accumulator 1
74
4 Bytes
R/W
PMnAC2
Accumulator 2
75
4 Bytes
R/W
PMnAC3
Accumulator 3
76
4 Bytes
R/W
PMnAC4
Accumulator 4
77
4 Bytes
R/W
PMnAC5
Accumulator 5
78
4 Bytes
R/W
PMnAC6
Accumulator 6
79
4 Bytes
R/W
PMnAC7
Accumulator 7
80
4 Bytes
R/W
PMnAC8
Accumulator 8
Table 35: Analog Input Module Items Structure First
Decimal
Module Name
04C0H
1216
Analog Input Module 1
04D0H
1232
Analog Input Module 2
04E0H
1248
Analog Input Module 3
04F0H
1264
Analog Input Module 4
0500H
1280
Analog Input Module 5
0510H
1296
Analog Input Module 6
0520H
1312
Analog Input Module 7
0530H
1328
Analog Input Module 8
Note:
226
R/W
X5 = 1 X6 = 1 X7 = 1 X8 = 1 2 Bytes
72 X16 X8 73
Type
TAG AITn is Analog Input Type of Module n.
Configuration Guides - DX-9100 Configuration Guide