Page 227
RI.
Type
R/W
Tag
00 2 Bytes CNF AITn 0 0 0 0 0 X11 X10 X9 X8 X7 X6 X5 X4 X3 X2 X1 X4 X3 X2 X1 = 0000 = 0001 = 0010 = 0011 X5 = 1 X6 = 1 X7 = 0 X7 = 1 X8 = 1 X11 X10 X9 = 000 = 001 = 010
01
Description Analog Input Type
Unit of Measure No Units Celsius Fahrenheit Percent Enable Square Root of Input Alarm on Unfiltered Value 0...10 Volts 0...2 Volts or 0...20 mA or RTD 20 % Suppression Linearization and Sensor Type Active Sensor (Linear) Nickel 1000 (Johnson Controls) Nickel 1000 Extended Range
= 011
A99 Sensor
= 100
PT1000 Sensor (DIN)
= 101
Nickel 1000 L&G (Version 1.1 or Later)
= 110
Nickel 1000 DIN (Version 1.1 or Later)
Number
CNF
HRn
High Range Input
02
Number
CNF
LRn
Low Range Input
03
Number
R/W (E)
HIAn
High Alarm Limit
04
Number
R/W(E)
LOAn
Low Alarm Limit
05
Number
CNF
FTCn
Filter Constant
06
Number
R/W (E)
ADFn
Differential on Alarm Limit [units]
07
Number
R
AIn
Analog Input Value
08
Number
R
AI%n
Analog Input Value in % of Range
09
2 Bytes
R
ADCn
Analog Input in Counts
10 0 0
1 Byte 0 0 X1 = 1
R AISTn X4 X3 X2 X1 AIHn
Analog Input Status High Alarm Condition
X2 = 1
AILn
Low Alarm Condition
X3 = 1
OVRn
Overrange Condition
X4 = 1
UNRn
Underrange Condition
Configuration Guides - DX-9100 Configuration Guide
227
Page 228
Analog Output Module Items Structure
Table 36: Analog Output Module Items Structure First
Decimal
Module Name
0540H
1344
Analog Output Module 1
0550H
1360
Analog Output Module 2
Version 2.0 or Later: 0900H
2304
Analog Output Module 9
0910H
2320
Analog Output Module 10
0920H
2336
Analog Output Module 11
0930H
2352
Analog Output Module 12
0940H
2368
Analog Output Module 13
0950H
2384
Analog Output Module 14
Note:
TAG AOTn is Analog Output Type of Module n.
RI.
Type
00 1 Byte X8 X7 0 0 X2 X1
228
R/W 0
Tag
CNF AOTn 0 X2 X1
Description Analog Output Type Output Signal
= 00
Output Disabled
= 01
Output 0 to 10 V
= 10
Output 0 to 20 mA
= 11
Output 4 to 20 mA Note: 20 mA outputs not available on Output Modules 11-14.
X7 = 0
Set Hold at Power Up
X7 = 1
Set Auto at Power Up
X8 = 1
Enable Hold/Auto Set at Power Up
01
Connection
CNF
AO@n
02
Connection
CNF
AOF@n
Output Forcing Logic Connection
03
Number
CNF
HROn
Output High Range
04
Number
CNF
LROn
Output Low Range
05
Number
CNF
OFLn
Output % Value in Forcing Mode
06
Number
R/W
OUTn
Output Module Output Value %
07 0 0
1 Byte X6 0 X1 = 1
R/W AOCn X4 X3 X2 X1 R/W OUHn
Source of Analog Output Module (analog)
Analog Output Control and Status Output in Hold Mode
X2 = 1
R
AOHn
Output at High Limit ... 100%
X3 = 1
R
AOLn
Output at Low Limit ... 0%
X4 = 1
R
AOFn
Output is Forced
X6 = 1
R
OULn
Logic Control Lock (INC@ = 1, DEC@ = 1)
08
Number
CNF
HLOn
High Limit on Output %
09
Number
CNF
LLOn
Low Limit on Output %
10
Connection
CNF
INC@n
Source of Increase Signal (logic)
11
Connection
CNF
DEC@n
Source of Decrease Signal (logic)
12
Connection
CNF
ENL@n
Enable Limits on Output
Configuration Guides - DX-9100 Configuration Guide
Page 229
Digital Output Module Items Structure
Table 37: Digital Output Module Items Structure First
Decimal
Module Name
0560H 0570H 0580H 0590H 05A0H 05B0H
1376 1392 1408 1424 1440 1456
Digital Output Module 3 (DO3) Digital Output Module 4 (DO4) Digital Output Module 5 (DO5) Digital Output Module 6 (DO6) Digital Output Module 7 (DO7) Digital Output Module 8 (DO8)
Note:
TAG DOTn is Digital Output Type of Module n.
RI.
Type
R/W
Tag
00 1 Byte CNF DOTn X8 X7 0 0 0 X3 X2 X1 X3 X2 X1 = 000 = 001 = 010 = 011 = 100 = 101 = 110 = 111 X7 = 0 X7 = 1 X8 = 1 01 Connection CNF DO@n 02 Connection CNF FB@n 03 Connection CNF DOF@n 04 Number CNF HROn 05 Number CNF LROn 06 Number CNF FSTn 07 Number CNF DBn 08 Number CNF HLOn 09 Number CNF LLOn 10 Number CNF OFLn 11 Number R/W OUTn 12 1 Byte R/W DOCn 0 0 X6 X5 X4 X3 X2 X1 X1 = 1 R/W OUHn X2 = 1 R DOHn X3 = 1 R DOLn X4 = 1 R DOF X5 = 1 R AFBn X6 = 1 R OULn 13 14 15
Connection Connection Connection
CNF CNF CNF
INC@n DEC@n ENL@n
Description Digital Output Type Digital Output Mode Output Disabled or Paired On/Off - Logic Source On/Off - Numeric Source DAT Output Type PAT without Feedback PAT with Feedback START/STOP PULSE TYPE Set Hold at Power Up Set Auto at Power Up Enable Hold/Auto Set at Power Up Source of DO Module (analog or digital) Source of Feedback Signal Output Forcing Logic Connection Output High Range Output Low Range PAT Output Full Stroke Time/DAT Cycle PAT Deadband/DAT Min. On/Off High Limit on Output % Low Limit on Output % Output % Value in Forcing Mode Output Module Output Value % Digital Output Control and Status Output in Hold Mode Output at High Limit ... 100% Output at Low Limit ... 0% Output is Forced Incorrect Feedback Logic Control Lock (INC@ = 1, DEC@ = 1) Source of Increase Signal (logic) Source of Decrease Signal (logic) Enable Limits on Output
Configuration Guides - DX-9100 Configuration Guide
229
Page 230
Extension Module Items Structure
Table 38: Extension Module Items Structure First
Decimal
Module Name
05C0H
1472
Extension Module 1
0610H
1552
Extension Module 2
0660H
1632
Extension Module 3
06B0H
1712
Extension Module 4
0700H
1792
Extension Module 5
0750H
1872
Extension Module 6
07A0H
1952
Extension Module 7
07F0H
2032
Extension Module 8
Note:
RI.
TAG XTnIOMAP is the Extension Module I/O Map of Module n.
Type
00 1 Byte X8 X7 X6 X5 X1 = 0
01 0 0
R/W
Tag
CNF XTnIOMAP X4 X3 X2 X1
Extension Module I/O Map XP1: I/O1 and I/O2 Not Used
X1 = 1
XP1: I/O1 and I/O2 Used
X2 = 0
XP1: I/O3 and I/O4 Not Used
X2 = 1
XP1: I/O3 and I/O4 Used
X3 = 0
XP1: I/O5 and I/O6 Not Used
X3 = 1
XP1: I/O5 and I/O6 Used
X4 = 0
XP1: I/O7 and I/O8 Not Used
X4 = 1
XP1: I/O7 and I/O8 Used
X5 = 0
XP2: I/O1 and I/O2 Not Used
X5 = 1
XP2: I/O1 and I/O2 Used
X6 = 0
XP2: I/O3 and I/O4 Not Used
X6 = 1
XP2: I/O3 and I/O4 Used
X7 = 0
XP2: I/O5 and I/O6 Not Used
X7 = 1
XP2: I/O5 and I/O6 Used
X8 = 0
XP2: I/O7 and I/O8 Not Used
X8 = 1
XP2: I/O7 and I/O8 Used
1 Byte 0 0 X1 = 0
CNF XTnIOTYP X4 X3 X2 X1
Extension Module I/O Type XP1: I/O1 and I/O2 Digital
X1 = 1
XP1: I/O1 and I/O2 Analog
X2 = 0
XP1: I/O3 and I/O4 Digital
X2 = 1
XP1: I/O3 and I/O4 Analog
X3 = 0
XP1: I/O5 and I/O6 Digital
X3 = 1
XP1: I/O5 and I/O6 Analog
X4 = 0
XP1: I/O7 and I/O8 Digital
X4 = 1
XP1: I/O7 and I/O8 Analog
Continued on next page . . .
230
Description
Configuration Guides - DX-9100 Configuration Guide
Page 231
RI. (Cont.) 02 X8
Type
1 Byte X7 X6 X5 X1 = 0
R/W
Tag
CNF XTnIOMOD X4 X3 X2 X1
Description Extension Module I/O Mode XP1: I/O1 and I/O2 Input
X1 = 1
XP1: I/O1 and I/O2 Output
X2 = 0
XP1: I/03 and I/O4 Input
X2 = 1
XP1: I/O3 and I/O4 Output
X3 = 0
XP1: I/O5 and I/O6 Input
X3 = 1
XP1: I/O5 and I/O6 Output
X4 = 0
XP1: I/O7 and I/O8 Input
X4 = 1
XP1: I/O7 and I/O8 Output
X5 = 0
XP2: I/O1 and I/O2 Input
X5 = 1
XP2: I/O1 and I/O2 Output
X6 = 0
XP2: I/O3 and I/O4 Input
X6 = 1
XP2: I/O3 and I/04 Output
X7 = 0
XP2: I/O5 and I/O6 Input
X7 = 1
XP2: I/O5 and I/O6 Output
X8 = 0
XP2: I/O7 and I/O8 Input
X8 = 1
XP2: I/O7 and I/O8 Output
03
1 Byte
CNF
XTnADX
Extension Module Address 1 to 255 (0 = not used)
04
Connection
CNF
XTnI1@
Point Connection - I1
05
Connection
CNF
XTnI2@
Point Connection - I2
06
Connection
CNF
XTnI3@
Point Connection - I3
07
Connection
CNF
XTnI4@
Point Connection - I4
08
Connection
CNF
XTnI5@
Point Connection - I5
09
Connection
CNF
XTnI6@
Point Connection - I6
10
Connection
CNF
XTnI7@
Point Connection - I7
11
Connection
CNF
XTnI8@
Point Connection - I8
Continued on next page . . .
Configuration Guides - DX-9100 Configuration Guide
231
Page 232
RI. (Cont.)
Type
R/W
Tag
12
Number
CNF
XTnAHR1
High Analog Range Point 1
13
Number
CNF
XTnALR1
Low Analog Range Point 1
14
Number
CNF
XTnAHR2
High Analog Range Point 2
15
Number
CNF
XTnALR2
Low Analog Range Point 2
16
Number
CNF
XTnAHR3
High Analog Range Point 3
17
Number
CNF
XTnALR3
Low Analog Range Point 3
18
Number
CNF
XTnAHR4
High Analog Range Point 4
19
Number
CNF
XTnALR4
Low Analog Range Point 4
20
Number
CNF
XTnAHR5
High Analog Range Point 5
21
Number
CNF
XTnALR5
Low Analog Range Point 5
22
Number
CNF
XTnAHR6
High Analog Range Point 6
23
Number
CNF
XTnALR6
Low Analog Range Point 6
24
Number
CNF
XTnAHR7
High Analog Range Point 7
25
Number
CNF
XTnALR7
Low Analog Range Point 7
26
Number
CNF
XTnAHR8
High Analog Range Point 8
27
Number
CNF
XTnALR8
Low Analog Range Point 8
28
Number
R/W (E)
XTnHIA1
High Alarm Limit Point 1 (*)
29
Number
R/W (E)
XTnLOA1
Low Alarm Limit Point 1 (*)
30
Number
R/W (E)
XTnHIA2
High Alarm Limit Point 2 (*)
31
Number
R/W (E)
XTnLOA2
Low Alarm Limit Point 2 (*)
32
Number
R/W (E)
XTnHIA3
High Alarm Limit Point 3 (*)
33
Number
R/W (E)
XTnLOA3
Low Alarm Limit Point 3 (*)
34
Number
R/W (E)
XTnHIA4
High Alarm Limit Point 4 (*)
35
Number
R/W (E)
XTnLOA4
Low Alarm Limit Point 4 (*)
36
Number
R/W (E)
XTnHIA5
High Alarm Limit Point 5 (*)
37
Number
R/W (E)
XTnLOA5
Low Alarm Limit Point 5 (*)
38
Number
R/W (E)
XTnHIA6
High Alarm Limit Point 6 (*)
39
Number
R/W (E)
XTnLOA6
Low Alarm Limit Point 6 (*)
40
Number
R/W (E)
XTnHIA7
High Alarm Limit Point 7 (*)
41
Number
R/W (E)
XTnLOA7
Low Alarm Limit Point 7 (*)
42
Number
R/W (E)
XTnHIA8
High Alarm Limit Point 8 (*)
43
Number
R/W (E)
XTnLOA8
Low Alarm Limit Point 8 (*)
Continued on next page . . .
232
Configuration Guides - DX-9100 Configuration Guide
Description
Page 233
RI. (Cont.)
Type
R/W
Tag
Description
44
2 Bytes
R
XTnAIS
Extension Module Analog Input Status
X16 X15 X14 X13 X12 X11 X10 X9 X8 X7 X6 X5 X4 X3 X2 X1 X1 = 1 XTnAIH1
High Alarm Status Point 1
X2 = 1
XTnAIL1
Low Alarm Status Point 1
X3 = 1
XTnAIH2
High Alarm Status Point 2
X4 = 1
XTnAIL2
Low Alarm Status Point 2
X5 = 1
XTnAIH3
High Alarm Status Point 3
X6 = 1
XTnAIL3
Low Alarm Status Point 3
X7 = 1
XTnAIH4
High Alarm Status Point 4
X8 = 1
XTnAIL4
Low Alarm Status Point 4
X9 = 1
XTnAIH5
High Alarm Status Point 5
X10 = 1
XTnAIL5
Low Alarm Status Point 5
X11 = 1
XTnAIH6
High Alarm Status Point 6
X12 = 1
XTnAIL6
Low Alarm Status Point 6
X13 = 1
XTnAIH7
High Alarm Status Point 7
X14 = 1
XTnAIL7
Low Alarm Status Point 7
X15 = 1
XTnAIH8
High Alarm Status Point 8
X16 = 1
XTnAIL8
Low Alarm Status Point 8
45
Number
R
XTnAI1
Analog Input Value 1
46
Number
R
XTnAI2
Analog Input Value 2
47
Number
R
XTnAI3
Analog Input Value 3
48
Number
R
XTnAI4
Analog Input Value 4
49
Number
R
XTnAI5
Analog Input Value 5
50
Number
R
XTnAI6
Analog Input Value 6
51
Number
R
XTnAI7
Analog Input Value 7
52
Number
R
XTnAI8
Analog Input Value 8
53
Number
R/W
XTnAO1
Analog Output Value Point 1 (*)
54
Number
R/W
XTnAO2
Analog Output Value Point 2 (*)
55
Number
R/W
XTnAO3
Analog Output Value Point 3 (*)
56
Number
R/W
XTnAO4
Analog Output Value Point 4 (*)
57
Number
R/W
XTnAO5
Analog Output Value Point 5 (*)
58
Number
R/W
XTnAO6
Analog Output Value Point 6 (*)
59
Number
R/W
XTnAO7
Analog Output Value Point 7 (*)
60
Number
R/W
XTnAO8
Analog Output Value Point 8 (*)
Continued on next page . . .
Configuration Guides - DX-9100 Configuration Guide
233
Page 234
RI. (Cont.)
Type
R/W
Tag
Description
61
4 Bytes
R/W
XTnCNT1
Digital Input 1 Pulse Count (*)
62
4 Bytes
R/W
XTnCNT2
Digital Input 2 Pulse Count (*)
63
4 Bytes
R/W
XTnCNT3
Digital Input 3 Pulse Count (*)
64
4 Bytes
R/W
XTnCNT4
Digital Input 4 Pulse Count (*)
65
4 Bytes
R/W
XTnCNT5
Digital Input 5 Pulse Count (*)
66
4 Bytes
R/W
XTnCNT6
Digital Input 6 Pulse Count (*)
67
4 Bytes
R/W
XTnCNT7
Digital Input 7 Pulse Count (*)
68
4 Bytes
R/W
XTnCNT8
Digital Input 8 Pulse Count (*)
69 1 Byte X8 X7 X6 X5 X1 = 1
R/W XTnHDC X4 X3 X2 X1 XTnOUH1
Extension Module Hold Control Output 1 in Hold
X2 = 1
XTnOUH2
Output 2 in Hold
X3 = 1
XTnOUH3
Output 3 in Hold
X4 = 1
XTnOUH4
Output 4 in Hold
X5 = 1
XTnOUH5
Output 5 in Hold
X6 = 1
XTnOUH6
Output 6 in Hold
X7 = 1
XTnOUH7
Output 7 in Hold
X8 = 1
XTnOUH8
Output 8 in Hold
70 1 Byte X8 X7 X6 X5 X1 = 1
R/W XTnDO X4 X3 X2 X1 XTnDO1
DO 1 is On
X2 = 1
XTnDO2
DO 2 is On
X3 = 1
XTnDO3
DO 3 is On
X4 = 1
XTnDO4
DO 4 is On
X5 = 1
XTnDO5
DO 5 is On
X6 = 1
XTnDO6
DO 6 is On
X7 = 1
XTnDO7
DO 7 is On
X8 = 1
XTnDO8
DO 8 is On
Continued on next page . . .
234
Configuration Guides - DX-9100 Configuration Guide
Digital Output Control and Status (*)
Page 235
RI. (Cont.)
Type
R/W
Tag
Description
71 1 Byte X8 X7 X6 X5 X1 = 1
R XTnDIS X4 X3 X2 X1 XTnDI1
X2 = 1
XTnDI2
DI 2 is On
X3 = 1
XTnDI3
DI 3 is On
X4 = 1
XTnDI4
DI 4 is On
X5 = 1
XTnDI5
DI 5 is On
X6 = 1
XTnDI6
DI 6 is On
X7 = 1
XTnDI7
DI 7 is On
X8 = 1
XTnDI8
DI 8 is On
72 1 Byte X8 X7 X6 X5 X1 = 0
R X4 X3 0
XTnST X1 XTnCOM
Digital Input Status DI 1 is On
Extension Module Local Status Communication Status OK
X1 = 1
XTnCOM
Module Not Answering
X3 = 1
XTnMIS
XT Databases in DX and XT/XTM do not match.
X4 = 1
XTnHARD
XT/XTM Hardware Failure
X5 = 1
XTnSEL
XT/XTM Selected on XT Bus
X6 = 1
XTnERR
Combined XT/XTM Error X1=1 or X3=1 or X4=1
X7 = 0
XTnFAIL
XT/XTM Fail Mode (Set outputs to 0 upon communication failure.)
X7 = 1
XTnFAIL
XT/XTM Fail Mode (Maintain output status upon communication failure.)
X8 = 1
XTnPWR
Loss of Power in XT/XTM Module (Momentary Indication)
(*) If the Item is modified the new value is retransmitted to the extension module.
Configuration Guides - DX-9100 Configuration Guide
235
Page 236
Time Scheduling Items Structure
Table 39: Time Scheduling Items Structure First
Decimal
Module Name
0840H
2112
Time Schedule 1
0850H
2128
Time Schedule 2
0860H
2144
Time Schedule 3
0870H
2160
Time Schedule 4
0880H
2176
Time Schedule 5
0890H
2192
Time Schedule 6
08A0H
2208
Time Schedule 7
08B0H
2224
Time Schedule 8
Note:
TAG TSnOPT is Time Schedule Options of Schedule n.
RI.
Type
00 0 0
1 Byte 0 0 X1 = 0
0
R/W
Tag
CNF 0 0
TSnOPT X1
Numeric Output Type (not implemented)
Connection
CNF
TSnEX@
External Extension Logical Connection
02
Connection
CNF
TSnON@
On Forcing Logical Connection
03
Connection
CNF
TSnOF@
Off Forcing Logical Connection
04
Number
R/W (E)
TSnXTM
Extension Time (min.)
05
Number
R
TSnTIM
Time to Next Event (min.)
06 1 Byte X8 X7 X6 X5 X1 = 1 X2
236
Time Schedule Options Logic Output Type
X1 = 1
01
Description
R/W TSnSTA X4 X3 X2 X1 R/W TSnHLD R/W
TSnOUT
Time Schedule Status Hold Mode Output Status and Control
X3 = 1
R/W
TSnEXT
Extension Command
X4
R
TSnNXO
Next Output
X5 = 1
R
TSnEXS
Extension (Keyboard/Serial Link)
X6 = 1
R
TSnXDI
Extension from DI
X7 = 1
R
TSnONF
Forced On Status
X8 = 1
R
TSnOFF
Forced Off Status
Configuration Guides - DX-9100 Configuration Guide