Page 237

Optimal Start/Stop Items Structure

Table 40: Optimal Start/Stop Items Structure First

Decimal

Module Name

08C0H

2240

Optimal Start/Stop Module 1

08E0H

2272

Optimal Start/Stop Module 2

Note:

TAG OSnOPT is Module Options of Module n.

RI.

Type

R/W

00 0 0

1 Byte 0 0 X1 = 1

CNF OSnOPT 0 X2 X1

0

Tag

Description Module Options Heating Mode

X2 = 1

Cooling Mode

X2 = 1x1=1

Heating and Cooling Mode

01

Connection

CNF

OSnZT@

Zone Temperature Connection

02

Connection

CNF

OSnOT@

Outdoor Temperature Connection

03

Connection

CNF

OSnSP@

Zone Temperature Setpoint Connection

04

Connection

CNF

OSnOB@

Off Setpoint Bias Connection

05

Connection

CNF

OSnDI@

Disable Module Connection

06

Connection

CNF

OSnDA@

Disable Adaptive Action Connection

07

Connection

CNF

OSnTS@

Connection at Time Schedule Output

08

Connection

CNF

OSnNX@

Connection at Next Output

09

Connection

CNF

OSnTIM@

Connection at Time to Next Output

10

Number

CNF

OSnPURGE

Minimum Cool/Heat Time [min]

11

Number

CNF

OSnMAXST

Maximum Startup Time [min]

12

Number

CNF

OSnMAXSO

Maximum Optimal Stop Time [min]

13

Number

CNF

OSnBHK

Start Mode Building Factor (Heating)

14

Number

CNF

OSnBCK

Start Mode Building Factor (Cooling)

15

Number

CNF

OSnSBHK

Stop Mode Building Factor (Heating)

16

Number

CNF

OSnSBCK

Stop Mode Building Factor (Cooling)

17

Number

CNF

OSnFW

Percentage Adaptive Control (Filter Weight)

18

Number

CNF

OSnHTD

Outdoor Design Temperature (Heating)

19

Number

CNF

OSnCTD

Outdoor Design temperature (Cooling)

20

Number

CNF

OSnCRNG

Control Range

Continued on next page . . .

Configuration Guides - DX-9100 Configuration Guide

237

Page 238

RI. (Cont.)

Type

R/W

Tag

21

Number

R/W

OSnSP

Zone Temperature On Setpoint

22

Number

R/W

OSnOB

Zone Temperature Stop Mode Bias

23

Number

R

OSnTIM

Calculated Optimal Startup Time

24 1 Byte X8 X7 X6 X5 X1 = 1

Network Information Module Items Structure

238

Description

R/W OSnSTA X4 X3 X2 X1 R/W OSnHLD

Operating Status Set Hold Mode

X2

R/W

OSnOUT

Output Status and Control

X3 = 1

R

OSnHEAT

Operating Mode (1=Heat)

X4 = 1

R

OSnPRE

Preheating or Precooling

X5 = 1

R

OSnSTO

Optimal Stop Active

X6

R

OSnIN

Value of the Command Input

X7 = 1

R

OSnADP

Adapting Algorithm Disabled

X8 = 1

R

OSnDAS

Module Disabled

Table 41: Network Information Module Items Structure First

Decimal

Module Name

0960H

2400

Network Information Module

RI.

Type

R/W

Tag

Description

00

2 Byte Int.

CNF

NVADX

Network Unit Identifier (DX Address)

01

2 Byte Int

CNF

NDON

No. of Network Digital Output Modules (0-8)

02

2 Byte Int

CNF

NAON

No. of Network Analog Output Modules (016)

03

2 Byte Int

CNF

NDIN

No. of Network Digital Input Modules (0/1)

04

2 Byte Int

CNF

NAIN

No. of Network Analog Input Modules (0/1)

05

2 Byte Int

CNF

NPTN

No. of Programmable Table Entries

Configuration Guides - DX-9100 Configuration Guide

Page 239

Network Digital Output Module Items Structure

Table 42: Network Digital Output Module Items Structure First

Decimal

Module Name

0970H

2416

Network Digital Output Module 1

09A0H

2464

Network Digital Output Module 2

09D0H

2512

Network Digital Output Module 3

0A00H

2560

Network Digital Output Module 4

0A30H

2608

Network Digital Output Module 5

0A60H

2656

Network Digital Output Module 6

0A90H

2704

Network Digital Output Module 7

0AC0H

2752

Network Digital Output Module 8

Note:

TAG NDOn-1 is Digital Output 1 of Module n.

RI.

Type

R/W

Tag

00

2 Bytes

R

NDOnCHG

X1 = 1

01 X16 X8

2 Bytes X X X X X1 = 1

Description Digital Output Module Change Digital Output Module Connection Change

NDOn X X X X X X NDOn-1

Digital Output Status

X2 = 1

NDOn-2

Digital Output 2 is On

X3 = 1

NDOn-3

Digital Output 3 is On

X4 = 1

NDOn-4

Digital Output 4 is On

X5 = 1

NDOn-5

Digital Output 5 is On

X6 = 1

NDOn-6

Digital Output 6 is On

X7 = 1

NDOn-7

Digital Output 7 is On

X8 = 1

NDOn-8

Digital Output 8 is On

X9 = 1

NDOn-9

Digital Output 9 is On

X10 = 1

NDOn-10

Digital Output 10 is On

X11 = 1

NDOn-11

Digital Output 11 is On

X12 = 1

NDOn-12

Digital Output 12 is On

X13 = 1

NDOn-13

Digital Output 13 is On

X14 = 1

NDOn-14

Digital Output 14 is On

X15 = 1

NDOn-15

Digital Output 15 is On

X16 = 1

NDOn-16

Digital Output 16 is On

X X

R X X

Digital Output 1 is On

Continued on next page . . .

Configuration Guides - DX-9100 Configuration Guide

239

Page 240

RI. (Cont.)

Type

R/W

Tag

02 X16 X8

2 Bytes R NDOnSTA X15 X14 X13 X12 X11 X10 X9 X7 X6 X5 X4 X3 X2 X1 X1 = 1

Digital Output 1 Failure

X2 = 1

Digital Output 2 Failure

X3 = 1

Digital Output 3 Failure

X4 = 1

Digital Output 4 Failure

X5 = 1

Digital Output 5 Failure

X6 = 1

Digital Output 6 Failure

X7 = 1

Digital Output 7 Failure

X8 = 1

Digital Output 8 Failure

Digital Output Failure Status

X9 = 1

Digital Output 9 Failure

X10 = 1

Digital Output 10 Failure

X11 = 1

Digital Output 11 Failure

X12 = 1

Digital Output 12 Failure

X13 = 1

Digital Output 13 Failure

X14 = 1

Digital Output 14 Failure

X15 = 1

Digital Output 15 Failure

X16 = 1

Digital Output 16 Failure

03

2 Byte Int

CNF

NDOnTYP

Digital Output Type (= 83 [53 H] if used)

04

Destination

CNF

NDOn>1

Destination Output 1

05

Destination

CNF

NDOn>2

Destination Output 2

06

Destination

CNF

NDOn>3

Destination Output 3

07

Destination

CNF

NDOn>4

Destination Output 4

08

Destination

CNF

NDOn>5

Destination Output 5

09

Destination

CNF

NDOn>6

Destination Output 6

10

Destination

CNF

NDOn>7

Destination Output 7

11

Destination

CNF

NDOn>8

Destination Output 8

12

Destination

CNF

NDOn>9

Destination Output 9

13

Destination

CNF

NDOn>10

Destination Output 10

14

Destination

CNF

NDOn>11

Destination Output 11

15

Destination

CNF

NDOn>12

Destination Output 12

16

Destination

CNF

NDOn>13

Destination Output 13

17

Destination

CNF

NDOn>14

Destination Output 14

18

Destination

CNF

NDOn>15

Destination Output 15

19

Destination

CNF

NDOn>16

Destination Output 16

Continued on next page . . .

240

Description

Configuration Guides - DX-9100 Configuration Guide

Page 241

Network Analog Output Module Items Structure

RI. (Cont.)

Type

R/W

Tag

Description

20

Connection

CNF

NDOn-1@

Source of Output 1

21

Connection

CNF

NDOn-2@

Source of Output 2

22

Connection

CNF

NDOn-3@

Source of Output 3

23

Connection

CNF

NDOn-4@

Source of Output 4

24

Connection

CNF

NDOn-5@

Source of Output 5

25

Connection

CNF

NDOn-6@

Source of Output 6

26

Connection

CNF

NDOn-7@

Source of Output 7

27

Connection

CNF

NDOn-8@

Source of Output 8

28

Connection

CNF

NDOn-9@

Source of Output 9

29

Connection

CNF

NDOn-10@

Source of Output 10

30

Connection

CNF

NDOn-11@

Source of Output 11

31

Connection

CNF

NDOn-12@

Source of Output 12

32

Connection

CNF

NDOn-13@

Source of Output 13

33

Connection

CNF

NDOn-14@

Source of Output 14

34

Connection

CNF

NDOn-15@

Source of Output 15

35

Connection

CNF

NDOn-16@

Source of Output 16

Table 43: Network Analog Output Module Items Structure First

Decimal

Module Name

0AF0H

2800

Network Analog Output Module 1

0B10H

2832

Network Analog Output Module 2

0B30H

2864

Network Analog Output Module 3

0B50H

2896

Network Analog Output Module 4

0B70H

2928

Network Analog Output Module 5

0B90H

2960

Network Analog Output Module 6

0BB0H

2992

Network Analog Output Module 7

0BD0H

3024

Network Analog Output Module 8

0BF0H

3056

Network Analog Output Module 9

0C10H

3088

Network Analog Output Module 10

0C30H

3120

Network Analog Output Module 11

0C50H

3152

Network Analog Output Module 12

0C70H

3184

Network Analog Output Module 13

0C90H

3216

Network Analog Output Module 14

0CB0H

3248

Network Analog Output Module 15

0CD0H

3280

Network Analog Output Module 16

Note:

TAG NAOnOUT is the value of the Analog Output of Module n.

Configuration Guides - DX-9100 Configuration Guide

241

Page 242

RI.

Type

R/W

Tag

00

2 Bytes

R

NAOnCHG

X1 = 1 01 02 X16 X8

242

Number

Description Analog Output Module Change Analog Output Module Connection Change

R

NAOn

2 Bytes R NAOnSTA X15 X14 X13 X12 X11 X10 X9 X7 X6 X5 X4 X3 X2 X1 X1 = 1

Analog Output Value Analog Output Failure Status

Analog Output 1 Failure

X2 = 1

Analog Output 2 Failure

X3 = 1

Analog Output 3 Failure

X4 = 1

Analog Output 4 Failure

X5 = 1

Analog Output 5 Failure

X6 = 1

Analog Output 6 Failure

X7 = 1

Analog Output 7 Failure

X8 = 1

Analog Output 8 Failure

X9 = 1

Analog Output 9 Failure

X10 = 1

Analog Output 10 Failure

X11 = 1

Analog Output 11 Failure

X12 = 1

Analog Output 12 Failure

X13 = 1

Analog Output 13 Failure

X14 = 1

Analog Output 14 Failure

X15 = 1

Analog Output 15 Failure

X16 = 1

Analog Output 16 Failure

03

Destination

CNF

NAOnDIM

Analog Output Value Dimension (units) (=55 [37H] if used)

04

Destination

CNF

NAOn>1

Destination Output 1

05

Destination

CNF

NAOn>2

Destination Output 2

06

Destination

CNF

NAOn>3

Destination Output 3

07

Destination

CNF

NAOn>4

Destination Output 4

08

Destination

CNF

NAOn>5

Destination Output 5

09

Destination

CNF

NAOn>6

Destination Output 6

10

Destination

CNF

NAOn>7

Destination Output 7

11

Destination

CNF

NAOn>8

Destination Output 8

12

Destination

CNF

NAOn>9

Destination Output 9

13

Destination

CNF

NAOn>10

Destination Output 10

14

Destination

CNF

NAOn>11

Destination Output 11

15

Destination

CNF

NAOn>12

Destination Output 12

16

Destination

CNF

NAOn>13

Destination Output 13

17

Destination

CNF

NAOn>14

Destination Output 14

18

Destination

CNF

NAOn>15

Destination Output 15

19

Destination

CNF

NAOn>16

Destination Output 16

20

Connection

CNF

NAOn@

Analog Output Source

Configuration Guides - DX-9100 Configuration Guide

Page 243

Network Digital Input Module Items Structure

Table 44: Network Digital Input Module Items Structure First

Decimal

Module Name

0CF0H

3312

Network Digital Input Module

RI.

Type

R/W

Tag

00

2 Bytes

R

NDICHG

X1 = 1

Description Digital Input Module Change Digital Input Module Type Change

01 2 Bytes R NDI1 X16 X15 X14 X13 X12 X11 X10 X9 X8 X7 X6 X5 X4 X3 X2 X1 X1 = 1 NDI1-1

Digital Input Module 1 Status

Digital Input 1 is On

X2 = 1

NDI1-2

Digital Input 2 is On

X3 = 1

NDI1-3

Digital Input 3 is On

X4 = 1

NDI1-4

Digital Input 4 is On

X5 = 1

NDI1-5

Digital Input 5 is On

X6 = 1

NDI1-6

Digital Input 6 is On

X7 = 1

NDI1-7

Digital Input 7 is On

X8 = 1

NDI1-8

Digital Input 8 is On

X9 = 1

NDI1-9

Digital Input 9 is On

X10 = 1

NDI1-10

Digital Input 10 is On

X11 = 1

NDI1-11

Digital Input 11 is On

X12 = 1

NDI1-12

Digital Input 12 is On

X13 = 1

NDI1-13

Digital Input 13 is On

X14 = 1

NDI1-14

Digital Input 14 is On

X15 = 1

NDI1-15

Digital Input 15 is On

X16 = 1

NDI1-16

Digital Input 16 is On

02

2 Bytes

R

NDI2

Digital Input Module 2 Status

03

2 Bytes

R

NDI3

Digital Input Module 3 Status

04

2 Bytes

R

NDI4

Digital Input Module 4 Status

05

2 Bytes

R

NDI5

Digital Input Module 5 Status

06

2 Bytes

R

NDI6

Digital Input Module 6 Status

07

2 Bytes

R

NDI7

Digital Input Module 7 Status

08

2 Bytes

R

NDI8

Digital Input Module 8 Status

09 2 Bytes R NDISTA X16 X15 X14 X13 X12 X11 X10 X9 X8 X7 X6 X5 X4 X3 X2 X1 X1 = 1 NDIU1

Digital Input Reliability Status

Digital Input Module 1 Unreliable

X2 = 1

NDIU2

Digital Input Module 2 Unreliable

X3 = 1

NDIU3

Digital Input Module 3 Unreliable

X4 = 1

NDIU4

Digital Input Module 4 Unreliable

X5 = 1

NDIU5

Digital Input Module 5 Unreliable

X6 = 1

NDIU6

Digital Input Module 6 Unreliable

X7 = 1

NDIU7

Digital Input Module 7 Unreliable

Continued on next page . . .

Configuration Guides - DX-9100 Configuration Guide

243

Page 244

RI. (Cont.)

Type

R/W

Tag NDIU8

Digital Input Module 8 Unreliable

10

2 Byte Int

CNF

NDI1TYP

Digital Input Module 1 Type (=83 [53H] if used)

11

2 Byte Int

CNF

NDI2TYP

Digital Input Module 2 Type (=83 [53H] if used)

12

2 Byte Int

CNF

NDI3TYP

Digital Input Module 3 Type (=83 [53H] if used)

13

2 Byte Int

CNF

NDI4TYP

Digital Input Module 4 Type (=83 [53H] if used)

14

2 Byte Int

CNF

NDI5TYP

Digital Input Module 5 Type (=83 [53H] if used)

15

2 Byte Int

CNF

NDI6TYP

Digital Input Module 6 Type (=83 [53H] if used)

16

2 Byte Int

CNF

NDI7TYP

Digital Input Module 7 Type (=83 [53H] if used)

17

2 Byte Int

CNF

NDI8TYP

Digital Input Module 8 Type (=83 [53H] if used)

X8 = 1

Network Analog Input Module Items Structure

Table 45: Network Analog Input Module Items Structure First

Decimal

Module Name

0D10H

3344

Network Analog Input Module

RI.

Type

R/W

Tag

00

2 Bytes

R

NAICHNG

X1 = 1

Description Analog Input Module Change Analog Input Module Dimension Change

01

Number

R

NAI1

Analog Input 1 Value

02

Number

R

NAI2

Analog Input 2 Value

03

Number

R

NAI3

Analog Input 3 Value

04

Number

R

NAI4

Analog Input 4 Value

05

Number

R

NAI5

Analog Input 5 Value

06

Number

R

NAI6

Analog Input 6 Value

07

Number

R

NAI7

Analog Input 7 Value

08

Number

R

NAI8

Analog Input 8 Value

09

Number

R

NAI9

Analog Input 9 Value

10

Number

R

NAI10

Analog Input 10 Value

11

Number

R

NAI11

Analog Input 11 Value

12

Number

R

NAI12

Analog Input 12 Value

13

Number

R

NAI13

Analog Input 13 Value

14

Number

R

NAI14

Analog Input 14 Value

15

Number

R

NAI15

Analog Input 15 Value

16

Number

R

NAI16

Analog Input 16 Value

Continued on next page . . .

244

Description

Configuration Guides - DX-9100 Configuration Guide

Page 245

RI. (Cont.) 17 X16 X8

18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33

Type

R/W

Tag

Description

2 Bytes R NAISTA Analog Input Reliability Status X15 X14 X13 X12 X11 X10 X9 X7 X6 X5 X4 X3 X2 X1 X1 = 1 NAIU1 Analog Input 1 Unreliable X2 = 1 NAIU2 Analog Input 2 Unreliable X3 = 1 NAIU3 Analog Input 3 Unreliable X4 = 1 NAIU4 Analog Input 4 Unreliable X5 = 1 NAIU5 Analog Input 5 Unreliable X6 = 1 NAIU6 Analog Input 6 Unreliable X7 = 1 NAIU7 Analog Input 7 Unreliable X8 = 1 NAIU8 Analog Input 8 Unreliable X9 = 1 NAIU9 Analog Input 9 Unreliable X10 = 1 NAIU10 Analog Input 10 Unreliable X11 = 1 NAIU11 Analog Input 11 Unreliable X12 = 1 NAIU12 Analog Input 12 Unreliable X13 = 1 NAIU13 Analog Input 13 Unreliable X14 = 1 NAIU14 Analog Input 14 Unreliable X15 = 1 NAIU15 Analog Input 15 Unreliable X16 = 1 NAIU16 Analog Input 16 Unreliable 2 Byte Int CNF NAI1DIM Analog Input 1 Value Dimension (=55 [37H] if used) 2 Byte Int CNF NAI2DIM Analog Input 2 Value Dimension (=55 [37H] if used) 2 Byte Int CNF NAI3DIM Analog Input 3 Value Dimension (=55 [37H] if used) 2 Byte Int CNF NAI4DIM Analog Input 4 Value Dimension (=55 [37H] if used) 2 Byte Int CNF NAI5DIM Analog Input 5 Value Dimension (=55 [37H] if used) 2 Byte Int CNF NAI6DIM Analog Input 6 Value Dimension (=55 [37H] if used) 2 Byte Int CNF NAI7DIM Analog Input 7 Value Dimension (=55 [37H] if used) 2 Byte Int CNF NAI8DIM Analog Input 8 Value Dimension (=55 [37H] if used) 2 Byte Int CNF NAI9DIM Analog Input 9 Value Dimension (=55 [37H] if used) 2 Byte Int CNF NAI10DIM Analog Input 10 Value Dimension (=55 [37H] if used) 2 Byte Int CNF NAI11DIM Analog Input 11 Value Dimension (=55 [37H] if used) 2 Byte Int CNF NAI12DIM Analog Input 12 Value Dimension (=55 [37H] if used) 2 Byte Int CNF NAI13DIM Analog Input 13 Value Dimension (=55 [37H] if used) 2 Byte Int CNF NAI14DIM Analog Input 14 Value Dimension (=55 [37H] if used) 2 Byte Int CNF NAI15DIM Analog Input 15 Value Dimension (=55 [37H] if used) 2 Byte Int CNF NAI16DIM Analog Input 16 Value Dimension (=55 [37H] if used)

Configuration Guides - DX-9100 Configuration Guide

245

Page 246

246

Configuration Guides - DX-9100 Configuration Guide