Page 237
Optimal Start/Stop Items Structure
Table 40: Optimal Start/Stop Items Structure First
Decimal
Module Name
08C0H
2240
Optimal Start/Stop Module 1
08E0H
2272
Optimal Start/Stop Module 2
Note:
TAG OSnOPT is Module Options of Module n.
RI.
Type
R/W
00 0 0
1 Byte 0 0 X1 = 1
CNF OSnOPT 0 X2 X1
0
Tag
Description Module Options Heating Mode
X2 = 1
Cooling Mode
X2 = 1x1=1
Heating and Cooling Mode
01
Connection
CNF
OSnZT@
Zone Temperature Connection
02
Connection
CNF
OSnOT@
Outdoor Temperature Connection
03
Connection
CNF
OSnSP@
Zone Temperature Setpoint Connection
04
Connection
CNF
OSnOB@
Off Setpoint Bias Connection
05
Connection
CNF
OSnDI@
Disable Module Connection
06
Connection
CNF
OSnDA@
Disable Adaptive Action Connection
07
Connection
CNF
OSnTS@
Connection at Time Schedule Output
08
Connection
CNF
OSnNX@
Connection at Next Output
09
Connection
CNF
OSnTIM@
Connection at Time to Next Output
10
Number
CNF
OSnPURGE
Minimum Cool/Heat Time [min]
11
Number
CNF
OSnMAXST
Maximum Startup Time [min]
12
Number
CNF
OSnMAXSO
Maximum Optimal Stop Time [min]
13
Number
CNF
OSnBHK
Start Mode Building Factor (Heating)
14
Number
CNF
OSnBCK
Start Mode Building Factor (Cooling)
15
Number
CNF
OSnSBHK
Stop Mode Building Factor (Heating)
16
Number
CNF
OSnSBCK
Stop Mode Building Factor (Cooling)
17
Number
CNF
OSnFW
Percentage Adaptive Control (Filter Weight)
18
Number
CNF
OSnHTD
Outdoor Design Temperature (Heating)
19
Number
CNF
OSnCTD
Outdoor Design temperature (Cooling)
20
Number
CNF
OSnCRNG
Control Range
Continued on next page . . .
Configuration Guides - DX-9100 Configuration Guide
237
Page 238
RI. (Cont.)
Type
R/W
Tag
21
Number
R/W
OSnSP
Zone Temperature On Setpoint
22
Number
R/W
OSnOB
Zone Temperature Stop Mode Bias
23
Number
R
OSnTIM
Calculated Optimal Startup Time
24 1 Byte X8 X7 X6 X5 X1 = 1
Network Information Module Items Structure
238
Description
R/W OSnSTA X4 X3 X2 X1 R/W OSnHLD
Operating Status Set Hold Mode
X2
R/W
OSnOUT
Output Status and Control
X3 = 1
R
OSnHEAT
Operating Mode (1=Heat)
X4 = 1
R
OSnPRE
Preheating or Precooling
X5 = 1
R
OSnSTO
Optimal Stop Active
X6
R
OSnIN
Value of the Command Input
X7 = 1
R
OSnADP
Adapting Algorithm Disabled
X8 = 1
R
OSnDAS
Module Disabled
Table 41: Network Information Module Items Structure First
Decimal
Module Name
0960H
2400
Network Information Module
RI.
Type
R/W
Tag
Description
00
2 Byte Int.
CNF
NVADX
Network Unit Identifier (DX Address)
01
2 Byte Int
CNF
NDON
No. of Network Digital Output Modules (0-8)
02
2 Byte Int
CNF
NAON
No. of Network Analog Output Modules (016)
03
2 Byte Int
CNF
NDIN
No. of Network Digital Input Modules (0/1)
04
2 Byte Int
CNF
NAIN
No. of Network Analog Input Modules (0/1)
05
2 Byte Int
CNF
NPTN
No. of Programmable Table Entries
Configuration Guides - DX-9100 Configuration Guide
Page 239
Network Digital Output Module Items Structure
Table 42: Network Digital Output Module Items Structure First
Decimal
Module Name
0970H
2416
Network Digital Output Module 1
09A0H
2464
Network Digital Output Module 2
09D0H
2512
Network Digital Output Module 3
0A00H
2560
Network Digital Output Module 4
0A30H
2608
Network Digital Output Module 5
0A60H
2656
Network Digital Output Module 6
0A90H
2704
Network Digital Output Module 7
0AC0H
2752
Network Digital Output Module 8
Note:
TAG NDOn-1 is Digital Output 1 of Module n.
RI.
Type
R/W
Tag
00
2 Bytes
R
NDOnCHG
X1 = 1
01 X16 X8
2 Bytes X X X X X1 = 1
Description Digital Output Module Change Digital Output Module Connection Change
NDOn X X X X X X NDOn-1
Digital Output Status
X2 = 1
NDOn-2
Digital Output 2 is On
X3 = 1
NDOn-3
Digital Output 3 is On
X4 = 1
NDOn-4
Digital Output 4 is On
X5 = 1
NDOn-5
Digital Output 5 is On
X6 = 1
NDOn-6
Digital Output 6 is On
X7 = 1
NDOn-7
Digital Output 7 is On
X8 = 1
NDOn-8
Digital Output 8 is On
X9 = 1
NDOn-9
Digital Output 9 is On
X10 = 1
NDOn-10
Digital Output 10 is On
X11 = 1
NDOn-11
Digital Output 11 is On
X12 = 1
NDOn-12
Digital Output 12 is On
X13 = 1
NDOn-13
Digital Output 13 is On
X14 = 1
NDOn-14
Digital Output 14 is On
X15 = 1
NDOn-15
Digital Output 15 is On
X16 = 1
NDOn-16
Digital Output 16 is On
X X
R X X
Digital Output 1 is On
Continued on next page . . .
Configuration Guides - DX-9100 Configuration Guide
239
Page 240
RI. (Cont.)
Type
R/W
Tag
02 X16 X8
2 Bytes R NDOnSTA X15 X14 X13 X12 X11 X10 X9 X7 X6 X5 X4 X3 X2 X1 X1 = 1
Digital Output 1 Failure
X2 = 1
Digital Output 2 Failure
X3 = 1
Digital Output 3 Failure
X4 = 1
Digital Output 4 Failure
X5 = 1
Digital Output 5 Failure
X6 = 1
Digital Output 6 Failure
X7 = 1
Digital Output 7 Failure
X8 = 1
Digital Output 8 Failure
Digital Output Failure Status
X9 = 1
Digital Output 9 Failure
X10 = 1
Digital Output 10 Failure
X11 = 1
Digital Output 11 Failure
X12 = 1
Digital Output 12 Failure
X13 = 1
Digital Output 13 Failure
X14 = 1
Digital Output 14 Failure
X15 = 1
Digital Output 15 Failure
X16 = 1
Digital Output 16 Failure
03
2 Byte Int
CNF
NDOnTYP
Digital Output Type (= 83 [53 H] if used)
04
Destination
CNF
NDOn>1
Destination Output 1
05
Destination
CNF
NDOn>2
Destination Output 2
06
Destination
CNF
NDOn>3
Destination Output 3
07
Destination
CNF
NDOn>4
Destination Output 4
08
Destination
CNF
NDOn>5
Destination Output 5
09
Destination
CNF
NDOn>6
Destination Output 6
10
Destination
CNF
NDOn>7
Destination Output 7
11
Destination
CNF
NDOn>8
Destination Output 8
12
Destination
CNF
NDOn>9
Destination Output 9
13
Destination
CNF
NDOn>10
Destination Output 10
14
Destination
CNF
NDOn>11
Destination Output 11
15
Destination
CNF
NDOn>12
Destination Output 12
16
Destination
CNF
NDOn>13
Destination Output 13
17
Destination
CNF
NDOn>14
Destination Output 14
18
Destination
CNF
NDOn>15
Destination Output 15
19
Destination
CNF
NDOn>16
Destination Output 16
Continued on next page . . .
240
Description
Configuration Guides - DX-9100 Configuration Guide
Page 241
Network Analog Output Module Items Structure
RI. (Cont.)
Type
R/W
Tag
Description
20
Connection
CNF
NDOn-1@
Source of Output 1
21
Connection
CNF
NDOn-2@
Source of Output 2
22
Connection
CNF
NDOn-3@
Source of Output 3
23
Connection
CNF
NDOn-4@
Source of Output 4
24
Connection
CNF
NDOn-5@
Source of Output 5
25
Connection
CNF
NDOn-6@
Source of Output 6
26
Connection
CNF
NDOn-7@
Source of Output 7
27
Connection
CNF
NDOn-8@
Source of Output 8
28
Connection
CNF
NDOn-9@
Source of Output 9
29
Connection
CNF
NDOn-10@
Source of Output 10
30
Connection
CNF
NDOn-11@
Source of Output 11
31
Connection
CNF
NDOn-12@
Source of Output 12
32
Connection
CNF
NDOn-13@
Source of Output 13
33
Connection
CNF
NDOn-14@
Source of Output 14
34
Connection
CNF
NDOn-15@
Source of Output 15
35
Connection
CNF
NDOn-16@
Source of Output 16
Table 43: Network Analog Output Module Items Structure First
Decimal
Module Name
0AF0H
2800
Network Analog Output Module 1
0B10H
2832
Network Analog Output Module 2
0B30H
2864
Network Analog Output Module 3
0B50H
2896
Network Analog Output Module 4
0B70H
2928
Network Analog Output Module 5
0B90H
2960
Network Analog Output Module 6
0BB0H
2992
Network Analog Output Module 7
0BD0H
3024
Network Analog Output Module 8
0BF0H
3056
Network Analog Output Module 9
0C10H
3088
Network Analog Output Module 10
0C30H
3120
Network Analog Output Module 11
0C50H
3152
Network Analog Output Module 12
0C70H
3184
Network Analog Output Module 13
0C90H
3216
Network Analog Output Module 14
0CB0H
3248
Network Analog Output Module 15
0CD0H
3280
Network Analog Output Module 16
Note:
TAG NAOnOUT is the value of the Analog Output of Module n.
Configuration Guides - DX-9100 Configuration Guide
241
Page 242
RI.
Type
R/W
Tag
00
2 Bytes
R
NAOnCHG
X1 = 1 01 02 X16 X8
242
Number
Description Analog Output Module Change Analog Output Module Connection Change
R
NAOn
2 Bytes R NAOnSTA X15 X14 X13 X12 X11 X10 X9 X7 X6 X5 X4 X3 X2 X1 X1 = 1
Analog Output Value Analog Output Failure Status
Analog Output 1 Failure
X2 = 1
Analog Output 2 Failure
X3 = 1
Analog Output 3 Failure
X4 = 1
Analog Output 4 Failure
X5 = 1
Analog Output 5 Failure
X6 = 1
Analog Output 6 Failure
X7 = 1
Analog Output 7 Failure
X8 = 1
Analog Output 8 Failure
X9 = 1
Analog Output 9 Failure
X10 = 1
Analog Output 10 Failure
X11 = 1
Analog Output 11 Failure
X12 = 1
Analog Output 12 Failure
X13 = 1
Analog Output 13 Failure
X14 = 1
Analog Output 14 Failure
X15 = 1
Analog Output 15 Failure
X16 = 1
Analog Output 16 Failure
03
Destination
CNF
NAOnDIM
Analog Output Value Dimension (units) (=55 [37H] if used)
04
Destination
CNF
NAOn>1
Destination Output 1
05
Destination
CNF
NAOn>2
Destination Output 2
06
Destination
CNF
NAOn>3
Destination Output 3
07
Destination
CNF
NAOn>4
Destination Output 4
08
Destination
CNF
NAOn>5
Destination Output 5
09
Destination
CNF
NAOn>6
Destination Output 6
10
Destination
CNF
NAOn>7
Destination Output 7
11
Destination
CNF
NAOn>8
Destination Output 8
12
Destination
CNF
NAOn>9
Destination Output 9
13
Destination
CNF
NAOn>10
Destination Output 10
14
Destination
CNF
NAOn>11
Destination Output 11
15
Destination
CNF
NAOn>12
Destination Output 12
16
Destination
CNF
NAOn>13
Destination Output 13
17
Destination
CNF
NAOn>14
Destination Output 14
18
Destination
CNF
NAOn>15
Destination Output 15
19
Destination
CNF
NAOn>16
Destination Output 16
20
Connection
CNF
NAOn@
Analog Output Source
Configuration Guides - DX-9100 Configuration Guide
Page 243
Network Digital Input Module Items Structure
Table 44: Network Digital Input Module Items Structure First
Decimal
Module Name
0CF0H
3312
Network Digital Input Module
RI.
Type
R/W
Tag
00
2 Bytes
R
NDICHG
X1 = 1
Description Digital Input Module Change Digital Input Module Type Change
01 2 Bytes R NDI1 X16 X15 X14 X13 X12 X11 X10 X9 X8 X7 X6 X5 X4 X3 X2 X1 X1 = 1 NDI1-1
Digital Input Module 1 Status
Digital Input 1 is On
X2 = 1
NDI1-2
Digital Input 2 is On
X3 = 1
NDI1-3
Digital Input 3 is On
X4 = 1
NDI1-4
Digital Input 4 is On
X5 = 1
NDI1-5
Digital Input 5 is On
X6 = 1
NDI1-6
Digital Input 6 is On
X7 = 1
NDI1-7
Digital Input 7 is On
X8 = 1
NDI1-8
Digital Input 8 is On
X9 = 1
NDI1-9
Digital Input 9 is On
X10 = 1
NDI1-10
Digital Input 10 is On
X11 = 1
NDI1-11
Digital Input 11 is On
X12 = 1
NDI1-12
Digital Input 12 is On
X13 = 1
NDI1-13
Digital Input 13 is On
X14 = 1
NDI1-14
Digital Input 14 is On
X15 = 1
NDI1-15
Digital Input 15 is On
X16 = 1
NDI1-16
Digital Input 16 is On
02
2 Bytes
R
NDI2
Digital Input Module 2 Status
03
2 Bytes
R
NDI3
Digital Input Module 3 Status
04
2 Bytes
R
NDI4
Digital Input Module 4 Status
05
2 Bytes
R
NDI5
Digital Input Module 5 Status
06
2 Bytes
R
NDI6
Digital Input Module 6 Status
07
2 Bytes
R
NDI7
Digital Input Module 7 Status
08
2 Bytes
R
NDI8
Digital Input Module 8 Status
09 2 Bytes R NDISTA X16 X15 X14 X13 X12 X11 X10 X9 X8 X7 X6 X5 X4 X3 X2 X1 X1 = 1 NDIU1
Digital Input Reliability Status
Digital Input Module 1 Unreliable
X2 = 1
NDIU2
Digital Input Module 2 Unreliable
X3 = 1
NDIU3
Digital Input Module 3 Unreliable
X4 = 1
NDIU4
Digital Input Module 4 Unreliable
X5 = 1
NDIU5
Digital Input Module 5 Unreliable
X6 = 1
NDIU6
Digital Input Module 6 Unreliable
X7 = 1
NDIU7
Digital Input Module 7 Unreliable
Continued on next page . . .
Configuration Guides - DX-9100 Configuration Guide
243
Page 244
RI. (Cont.)
Type
R/W
Tag NDIU8
Digital Input Module 8 Unreliable
10
2 Byte Int
CNF
NDI1TYP
Digital Input Module 1 Type (=83 [53H] if used)
11
2 Byte Int
CNF
NDI2TYP
Digital Input Module 2 Type (=83 [53H] if used)
12
2 Byte Int
CNF
NDI3TYP
Digital Input Module 3 Type (=83 [53H] if used)
13
2 Byte Int
CNF
NDI4TYP
Digital Input Module 4 Type (=83 [53H] if used)
14
2 Byte Int
CNF
NDI5TYP
Digital Input Module 5 Type (=83 [53H] if used)
15
2 Byte Int
CNF
NDI6TYP
Digital Input Module 6 Type (=83 [53H] if used)
16
2 Byte Int
CNF
NDI7TYP
Digital Input Module 7 Type (=83 [53H] if used)
17
2 Byte Int
CNF
NDI8TYP
Digital Input Module 8 Type (=83 [53H] if used)
X8 = 1
Network Analog Input Module Items Structure
Table 45: Network Analog Input Module Items Structure First
Decimal
Module Name
0D10H
3344
Network Analog Input Module
RI.
Type
R/W
Tag
00
2 Bytes
R
NAICHNG
X1 = 1
Description Analog Input Module Change Analog Input Module Dimension Change
01
Number
R
NAI1
Analog Input 1 Value
02
Number
R
NAI2
Analog Input 2 Value
03
Number
R
NAI3
Analog Input 3 Value
04
Number
R
NAI4
Analog Input 4 Value
05
Number
R
NAI5
Analog Input 5 Value
06
Number
R
NAI6
Analog Input 6 Value
07
Number
R
NAI7
Analog Input 7 Value
08
Number
R
NAI8
Analog Input 8 Value
09
Number
R
NAI9
Analog Input 9 Value
10
Number
R
NAI10
Analog Input 10 Value
11
Number
R
NAI11
Analog Input 11 Value
12
Number
R
NAI12
Analog Input 12 Value
13
Number
R
NAI13
Analog Input 13 Value
14
Number
R
NAI14
Analog Input 14 Value
15
Number
R
NAI15
Analog Input 15 Value
16
Number
R
NAI16
Analog Input 16 Value
Continued on next page . . .
244
Description
Configuration Guides - DX-9100 Configuration Guide
Page 245
RI. (Cont.) 17 X16 X8
18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33
Type
R/W
Tag
Description
2 Bytes R NAISTA Analog Input Reliability Status X15 X14 X13 X12 X11 X10 X9 X7 X6 X5 X4 X3 X2 X1 X1 = 1 NAIU1 Analog Input 1 Unreliable X2 = 1 NAIU2 Analog Input 2 Unreliable X3 = 1 NAIU3 Analog Input 3 Unreliable X4 = 1 NAIU4 Analog Input 4 Unreliable X5 = 1 NAIU5 Analog Input 5 Unreliable X6 = 1 NAIU6 Analog Input 6 Unreliable X7 = 1 NAIU7 Analog Input 7 Unreliable X8 = 1 NAIU8 Analog Input 8 Unreliable X9 = 1 NAIU9 Analog Input 9 Unreliable X10 = 1 NAIU10 Analog Input 10 Unreliable X11 = 1 NAIU11 Analog Input 11 Unreliable X12 = 1 NAIU12 Analog Input 12 Unreliable X13 = 1 NAIU13 Analog Input 13 Unreliable X14 = 1 NAIU14 Analog Input 14 Unreliable X15 = 1 NAIU15 Analog Input 15 Unreliable X16 = 1 NAIU16 Analog Input 16 Unreliable 2 Byte Int CNF NAI1DIM Analog Input 1 Value Dimension (=55 [37H] if used) 2 Byte Int CNF NAI2DIM Analog Input 2 Value Dimension (=55 [37H] if used) 2 Byte Int CNF NAI3DIM Analog Input 3 Value Dimension (=55 [37H] if used) 2 Byte Int CNF NAI4DIM Analog Input 4 Value Dimension (=55 [37H] if used) 2 Byte Int CNF NAI5DIM Analog Input 5 Value Dimension (=55 [37H] if used) 2 Byte Int CNF NAI6DIM Analog Input 6 Value Dimension (=55 [37H] if used) 2 Byte Int CNF NAI7DIM Analog Input 7 Value Dimension (=55 [37H] if used) 2 Byte Int CNF NAI8DIM Analog Input 8 Value Dimension (=55 [37H] if used) 2 Byte Int CNF NAI9DIM Analog Input 9 Value Dimension (=55 [37H] if used) 2 Byte Int CNF NAI10DIM Analog Input 10 Value Dimension (=55 [37H] if used) 2 Byte Int CNF NAI11DIM Analog Input 11 Value Dimension (=55 [37H] if used) 2 Byte Int CNF NAI12DIM Analog Input 12 Value Dimension (=55 [37H] if used) 2 Byte Int CNF NAI13DIM Analog Input 13 Value Dimension (=55 [37H] if used) 2 Byte Int CNF NAI14DIM Analog Input 14 Value Dimension (=55 [37H] if used) 2 Byte Int CNF NAI15DIM Analog Input 15 Value Dimension (=55 [37H] if used) 2 Byte Int CNF NAI16DIM Analog Input 16 Value Dimension (=55 [37H] if used)
Configuration Guides - DX-9100 Configuration Guide
245
Page 246
246
Configuration Guides - DX-9100 Configuration Guide