Page 247
Appendix C: Programmable Function Module Items Algorithm 1 PID Controller
Table 46: Algorithm 1 - PID Controller RI.
PM Tag
Alg. Tag
Description
00 01
PMnTYP PMnOPT
TYP OPT
10 11 12 13 14 15 16 17 20 22
PMnI1@ PMnI2@ PMnI3@ PMnI4@ PMnI5@ PMnI6@ PMnI7@ PMnI8@ PMnI11@ PMnI13@
SOFE STAE SYME PIDP REM SOTO PV@ RS@ RV@ PB@ OF@ SB@ RA@ EF@ OB@ MNWS@
23
PMnI14@
MXWS@
26 27 28 29 30 31 32 33 34 35 36 37 38 39
PMnK1 PMnK2 PMnK3 PMnK4 PMnK5 PMnK6 PMnK7 PMnK8 PMnK9 PMnK10 PMnK11 PMnK12 PMnK13 PMnK14
LSP PB TI TD BSB BOF SBC EDB OB MNWS HIL LOL DHH DH
Algorithm Type = 01 Controller Options 0 0 0 0 0 0 0 X X8 X7 0 X5 0 X3 0 X X1 = 1 Enable Shutoff Mode X3 = 1 Enable Startup Mode X5 = 1 Enable Symmetric Mode X7 = 1 Enable PID to P Change X8 = 1 Remote Mode X9 = 1 Enable Shutoff to Off Change Process Variable Connection Remote Setpoint Connection Reference Variable Connection Proportional Band Connection Off Mode Logic Control Connection Standby Mode Logic Control Connection Reverse Acting Logic Control Connection External Forcing Logic Control Connection Output Bias Connection Minimum Working Setpoint Connection (Version 1.1 or Later) Maximum Working Setpoint Connection (Version 1.1 or Later) Local Setpoint Proportional Band Reset Action Rate Action Change of Setpoint During Standby Change of Setpoint During Off Symmetry Band Error Deadband Output Bias Minimum Working Setpoint (Version 1.1 or Later) Upper Limit of the Control Output Lower Limit of the Control Output Deviation High High Alarm Value Deviation High Alarm Value
Continued on next page . . .
Configuration Guides - DX-9100 Configuration Guide
247
Page 248
RI. (Cont.)
PM Tag
Alg. Tag
Description
40
PMnK15
DL
Deviation Low Alarm Value
41
PMnK16
DLL
Deviation Low Low Alarm Value
42
PMnK17
MXWS
Maximum Working Setpoint (Version 1.1 or Later)
51
PMnK26
SOL
Shutoff Output Level
52
PMnK27
STL
Startup Output Level
59
PMnK34
EFL
External Force Output Level
60
PMnOU1
OCM
Control Output
61
PMnOU2
WSP
Working Setpoint
63
PMnOU4
PV
Actual Process Variable
64
PMnOU5
PVS
PV Gain (100/Span)
65
PMnOU6
PVL
PV Low Range
66
PMnOU7
RSP
Actual Remote Setpoint
67
PMnOU8
RV
Actual Reference Variable
70
PMnHDC HLD
Hold Mode Control/Status 0 0 0 0 0 0 X2 X X1 = 1 Hold Control/Status
CMP
X2 = 1
CML
Controller Status 0 X1 X1 X1 X1 X1 X1 X X8 X7 X6 X5 X4 X3 X2 X X1 = 1 Controller Output at Low Limit
CMH
X2 = 1
Controller Output at High Limit
FORC
X3 = 1
Force-Back to OCM Active
LLDA
X5 = 1
Deviation Alarm Low Low
LDA
X6 = 1
Deviation Alarm Low
HDA
X7 = 1
Deviation Alarm High
HHDA
X8 = 1
Deviation Alarm High High
SOF
X9 = 1
Shutoff Mode Active
STA
X10 = 1
Startup Mode Active
EF
X11 = 1
External Forcing Active
OF
X12 = 1
Off Mode Active
SB
X13 = 1
Standby Mode Active
RA
X14 = 1
Reverse Action Mode
HEAT
X15 = 1
72
PMnST
Computer Mode Request
Heating Mode (RA) or PV Below Symmetrical Band Center
248
Configuration Guides - DX-9100 Configuration Guide
Page 249
Algorithm 2 On/Off Controller
Table 47: Algorithm 2 - On/Off Controller RI.
PM Tag
Alg. Tag
Description
00
PMnTYP
TYP
Algorithm Type = 02
01
PMnOPT
OPT
SOFE
Controller Options 0 0 0 0 0 0 0 0 X8 0 X6 X5 X4 X3 X2 X1 X1 = 1 Enable Shutoff Mode
SOFL
X2 = 0
Shutoff Out Level = 0
SOFL
X2 = 1
Shutoff Out Level = 1
STAE
X3 = 1
Enable Startup Mode
STAL
X4 = 0
Startup Out Level = 0
STAL
X4 = 1
Startup Out Level = 1
SYME
X5 = 1
Enable Symmetric Mode
EFL
X6 = 0
External Forcing Out Level = 0
EFL
X6 = 1
External Forcing Out Level = 1
REM
X8 = 1
Remote Mode
10
PMnI1@
PV@
Process Variable Connection
11
PMnI2@
RS@
Remote Setpoint Connection
12
PMnI3@
RV@
Reference Variable Connection
14
PMnI5@
OF@
Off Mode Logic Control Connection
15
PMnI6@
SB@
Standby Mode Logic Control Connection
16
PMnI7@
RA@
Reverse Acting Logic Control Connection
17
PMnI8@
EF@
External Forcing Logic Control Connection
22
PMnI13@
MNWS@
Minimum Working Setpoint Connection (Version 1.1 or Later)
23
PMnI14@
MXWS@
Maximum Working Setpoint Connection (Version 1.1 or Later)
26
PMnK1
LSP
Local Setpoint
27
PMnK2
ACT
Action Mode
28
PMnK3
DIF
Differential
30
PMnK5
BSB
Change of Setpoint During Standby
31
PMnK6
BOF
Change of Setpoint During Off
32
PMnK7
SBC
Symmetry Band
35
PMnK10
MNWS
Minimum Working Setpoint (Version 1.1 or Later)
38
PMnK13
DHH
Deviation High High Alarm Value
39
PMnK14
DH
Deviation High Alarm Value
40
PMnK15
DL
Deviation Low Alarm Value
41
PMnK16
DLL
Deviation Low Low Alarm Value
42
PMnK17
MXWS
Maximum Working Setpoint (Version 1.1 or Later)
Continued on next page . . .
Configuration Guides - DX-9100 Configuration Guide
249
Page 250
RI. (Cont.)
PM Tag
Alg. Tag
Description
61
PMnOU2
WSP
Working Setpoint
63
PMnOU4
PV
Actual Process Variable
64
PMnOU5
PVS
PV Gain (100/Span)
65
PMnOU6
PVL
PV Low Range
66
PMnOU7
RSP
Actual Remote Setpoint
67
PMnOU8
RV
Actual Reference Variable
HLD
0 0 X1 = 1
CMP
X2 = 1
OCM
Logic Outputs Control and Status 0 0 0 0 0 0 0 X1 X1 Control Output
LLDA
Controller Status 0 X15 X14 X13 X12 X11 X10 X9 X8 X7 X6 X5 0 0 X2 X1 X5 = 1 Deviation Alarm Low Low
LDA
X6 = 1
Deviation Alarm Low
HDA
X7 = 1
Deviation Alarm High
HHDA
X8 = 1
Deviation Alarm High High
SOF
X9 = 1
Shutoff Mode Active
STA
X10= 1
Startup Mode Active
EF
X11= 1
External Forcing Active
OF
X12= 1
Off Mode Active
SB
X13= 1
Standby Mode Active
RA
X14= 1
Reverse Action Mode
HEAT
X15 = 1
71
72
PMnDO
PMnST
0
0 0 0 X2 X1 Hold Control/Status Computer Mode Request
Heating Mode (RA) or PV Below Symmetrical Band Center
250
Configuration Guides - DX-9100 Configuration Guide
Page 251
Algorithm 3 Heating/Cooling PID Controller
Table 48: Algorithm 3 - Heating/Cooling PID Controller RI.
PM Tag
Alg. Tag
Description
00 01
PMnTYP PMnOPT
TYP OPT
Algorithm Type = 03 Controller Options 0 0 0 0 0 0 0 X9 X8 X7 0 0 0 X3 0 X1 X1 = 1 Enable Shutoff Mode X3 = 1 Enable Startup Mode X7 = 1 Enable PID to P Change X8 = 1 Remote Mode X9 = 1 Enable Shutoff to Off Change X10 = 1 Enable Zero Output Changeover (Versions 1.4, 2.3, 3.3 or Later) Process Variable Connection Remote Setpoint Connection Reference Variable Connection Proportional Band Connection Off Mode Logic Control Connection Standby Mode Logic Control Connection Reverse Acting Logic Control Connection External Forcing Logic Control Connection Second Loop Remote Setpoint Connection Second Loop Reference Variable Connection Output Bias Connection Second Loop Output Bias Connection Minimum Working Setpoint Connection (Version 1.1 or Later) Maximum Working Setpoint Connection (Version 1.1 or Later) Local Setpoint - Loop 1 Proportional Band - Loop 1 Reset Action - Loop 1 Rate Action - Loop 1 Change of Setpoint During - Loop 1 Standby Change of Setpoint During Off - Loop 1 Error Deadband - Loop 1 Output Bias - Loop 1
SOFE STAE PIDP REM SOTO EZCO 10 11 12 13 14 15 16 17 18 19 20 21 22
PMnI1@ PMnI2@ PMnI3@ PMnI4@ PMnI5@ PMnI6@ PMnI7@ PMnI8@ PMnI9@ PMnI10@ PMnI11@ PMnI12@ PMnI13@
PV@ RS1@ RV1@ PB@ OF@ SB@ RA@ EF@ RS2@ RV2@ OB1@ OB2@ MNWS@
23
PMnI14@
MXWS@
26 27 28 29 30
PMnK1 PMnK2 PMnK3 PMnK4 PMnK5
LSP1 PB1 TI1 TD1 BSB1
31 33 34
PMnK6 PMnK8 PMnK9
BOF1 EDB1 OB1
35
PMnK10
MNWS
Minimum Working Setpoint (Version 1.1 or Later)
36 37 38 39 40
PMnK11 PMnK12 PMnK13 PMnK14 PMnK15
HIL1 LOL1 DHH1 DH1 DL1
Upper Limit of the Control Output Lower Limit of the Control Output Deviation High High Alarm Value Deviation High Alarm Value Deviation Low Alarm Value
- Loop 1 - Loop 1 - Loop 1 - Loop 1 - Loop 1
Continued on next page . . .
Configuration Guides - DX-9100 Configuration Guide
251
Page 252
RI. (Cont.)
PM Tag
Alg. Tag
Description
41 42
PMnK16 PMnK17
DLL1 MXWS
Deviation Low Low Alarm Value - Loop 1 Maximum Working Setpoint (Version 1.1 or Later)
43
PMnK18
LSP2
Local Setpoint
- Loop 2
44
PMnK19
PB2
Proportional Band
- Loop 2
45
PMnK20
TI2
Reset Action
- Loop 2
46
PMnK21
TD2
Rate Action
- Loop 2
47
PMnK22
BSB2
Change of Setpoint During Standby
- Loop 2
48
PMnK23
BOF2
Change of Setpoint During Off
- Loop 2
49
PMnK24
EDB2
Error Deadband
- Loop 2
50
PMnK25
OB2
Output Bias
- Loop 2
51
PMnK26
SOL
Shutoff Output Level
52
PMnK27
STL
Startup Output Level
53
PMnK28
HIL2
Upper Limit of the Control Output
- Loop 2
54
PMnK29
LOL2
Lower Limit of the Control Output
- Loop 2
55
PMnK30
DHH2
Deviation High High Alarm Value
- Loop 2
56
PMnK31
DH2
Deviation High Alarm Value
- Loop 2
57
PMnK32
DL2
Deviation Low Alarm Value
- Loop 2
58
PMnK33
DLL2
Deviation Low Low Alarm Value
- Loop 2
59
PMnK34
EFL
External Force Output Level
60
PMnOU1
OCM
Control Output (Active Loop)
61
PMnOU2
WSP1
Working Setpoint
- Loop 1
62
PMnOU3
WSP2
Working Setpoint
- Loop 2
63
PMnOU4
PV
Actual Process Variable
64
PMnOU5
PVS
PV Gain (100/Span)
65
PMnOU6
PVL
PV Low Range
66
PMnOU7
RSP
Actual Remote Setpoint
67
PMnOU8
RV
Actual Reference Variable
68
PMnAX1
OCM1
Control Output
- Loop 1
69
PMnAX2
OCM2
Control Output
- Loop 2
70
PMnHDC HLD
Hold Mode Control/Status 0 0 0 0 0 0 X1 = 1
CMP
X2 = 1
Continued on next page . . .
252
Configuration Guides - DX-9100 Configuration Guide
X2 X1
Page 253
RI. PM Tag (Cont.) 72
Algorithm 4 Heating/Cooling On/Off Controller
Alg. Tag
PMnST
Description
CML
Controller Status 0 X15 X14 X13 X12 X11 X10 X9 X8 X7 X6 X5 0 X3 X2 X1 X1 = 1 Controller Output at Low Limit
CMH
X2 = 1
Controller Output at High Limit
FORC
X3 = 1
Force-Back to OCM Active
LLDA
X5 = 1
Deviation Alarm Low Low
LDA
X6 = 1
Deviation Alarm Low
HDA
X7 = 1
Deviation Alarm High
HHDA
X8 = 1
Deviation Alarm High High
SOF
X9 = 1
Shutoff Mode Active
STA
X10= 1
Startup Mode Active
EF
X11= 1
External Forcing Active
OF
X12= 1
Off Mode Active
SB
X13= 1
Standby Mode Active
RA
X14= 1
Reverse Action Mode
HEAT
X15= 1
Heating Mode (RA)
Table 49: Algorithm 4 - Heating/Cooling On/Off Controller RI.
PM Tag
Alg. Tag
Description
00
PMnTYP
TYP
Algorithm Type = 04
01
PMnOPT
OPT
SOFE
Controller Options 0 0 0 0 0 0 0 0 X8 0 X6 0 X4 X3 X2 X1 X1 = 1 Enable Shutoff Mode
SOFL
X2 = 0
Shutoff Out Level = 0
SOFL
X2 = 1
Shutoff Out Level = 1
STAE
X3 = 1
Enable Startup Mode
STAL
X4 = 0
Startup Out Level = 0
STAL
X4 = 1
Startup Out Level = 1
EFL
X6 = 0
External Forcing Out Level = 0
EFL
X6 = 1
External Forcing Out Level = 1
REM
X8 = 1
Remote Mode
SOTO
X9 = 1
Enable Shutoff to Off Change
Continued on next page . . .
Configuration Guides - DX-9100 Configuration Guide
253
Page 254
RI. PM Tag (Cont.)
Alg. Tag
Description
10 11 12 14
PMnI1@ PMnI2@ PMnI3@ PMnI5@
PV@ RS1@ RV1@ OF@
15
PMnI6@
SB@
16
PMnI7@
RA@
17
PMnI8@
EF@
18 19 22
PMnI9@ PMnI10@ PMnI13@
RS2@ RV2@ MNWS@
23
PMnI14@
MXWS@
26 27 28 30
PMnK01 PMnK02 PMnK03 PMnK05
LSP1 ACT1 DIF1 BSB1
31 35
PMnK06 PMnK10
BOF1 MNWS
38 39 40 41 42
PMnK13 PMnK14 PMnK15 PMnK16 PMnK17
DHH1 DH1 DL1 DLL1 MXWS
43 44 45 47
PMnK18 PMnK19 PMnK20 PMnK22
LSP2 ACT2 DIF2 BSB2
48 55
PMnK23 PMnK30
BOF2 DHH2
Process Variable Connection Remote Setpoint Connection Reference Variable Connection Off Mode Logic Control Connection Standby Mode Logic Control Connection Reverse Acting Logic Control Connection External Forcing Logic Control Connection Remote Setpoint Connection Reference Variable Connection Minimum Working Setpoint Connection (Version 1.1 or Later) Maximum Working Setpoint Connection (Version 1.1 or Later) Local Setpoint Action Mode Differential Change of Setpoint During Standby Change of Setpoint During Off Minimum Working Setpoint (Version 1.1 or Later) Deviation High High Alarm Value Deviation High Alarm Value Deviation Low Alarm Value Deviation Low Low Alarm Value Maximum Working Setpoint (Version 1.1 or Later) Local Setpoint Action Mode Differential Change of Setpoint During Standby Change of Setpoint During Off Deviation High High Alarm Value
Continued on next page . . .
254
Configuration Guides - DX-9100 Configuration Guide
- Loop 1 - Loop 1
- Loop 2 - Loop 2
- Loop 1 - Loop 1 - Loop 1 - Loop 1
- Loop 1 - Loop 1 - Loop 1 - Loop 1
- Loop 2 - Loop 2 - Loop 2 - Loop 2 - Loop 2 - Loop 2