DX-9100 Configuration Guide: Appendix C: Programmable Function Module Items, pages 255 to 262

Pages 255 to 262 of 288, from DX-9100 Configuration Guide

The original document is the PDF (1.3 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Johnson Controls DX-9100

Page 255

RI. PM Tag (Cont.)

Alg. Tag

Description

56

PMnK31

DH2

Deviation High Alarm Value

- Loop 2

57

PMnK32

DL2

Deviation Low Alarm Value

- Loop 2

58

PMnK33

DLL2

Deviation Low Low Alarm Value

- Loop 2

61

PMnOU2

WSP1

Working Setpoint

- Loop 1

62

PMnOU3

WSP2

Working Setpoint

- Loop 2

63

PMnOU4

PV

Actual Process Variable

64

PMnOU5

PVS

PV Gain (100/Span)

65

PMnOU6

PVL

PV Low Range

66

PMnOU7

RSP

Actual Remote Setpoint

67

PMnOU8

RV

Actual Reference Variable

70

PMnHDC HLD

Hold Mode Control/Status 0 0 0 0 0 0 X2 X1 X1 = 1 Hold Control/Status

CMP

X2 = 1

OCM

Logic Outputs Control and Status 0 0 0 0 X4 X3 0 X1 X1 Control Output (Active Loop)

OCM1

X3

Control Output

- Loop 1

OCM2

X4

Control Output

- Loop 2

71

72

PMnDO

PMnST

Computer Mode Request

Controller Status CML

X1 = 1

Controller Output at 0

CMH

X2 = 1

Controller Output at 1

LLDA

X5 = 1

Deviation Alarm Low Low

LDA

X6 = 1

Deviation Alarm Low

HDA

X7 = 1

Deviation Alarm High

HHDA

X8 = 1

Deviation Alarm High High

SOF

X9 = 1

Shutoff Mode Active

STA

X10= 1

Startup Mode Active

EF

X11= 1

External Forcing Active

OF

X12= 1

Off Mode Active

SB

X13= 1

Standby Mode Active

RA

X14= 1

Reverse Action Mode

HEAT

X15= 1

Heating Mode (RA)

Configuration Guides - DX-9100 Configuration Guide

255

Page 256

Algorithm 11 Average Calculation

Table 50: Algorithm 11 - Average Calculation RI.

PM Tag

Alg. Tag

Description

00

PMnTYP

TYP

Algorithm Type = 11

10

PMnI1@

I1@

Input 1 Analog Connection

11

PMnI2@

I2@

Input 2 Analog Connection

12

PMnI3@

I3@

Input 3 Analog Connection

13

PMnI4@

I4@

Input 4 Analog Connection

14

PMnI5@

I5@

Input 5 Analog Connection

15

PMnI6@

I6@

Input 6 Analog Connection

16

PMnI7@

I7@

Input 7 Analog Connection

17

PMnI8@

I8@

Input 8 Analog Connection

26

PMnK1

K0

Constant

27

PMnK2

K1

Constant

28

PMnK3

K2

Constant

29

PMnK4

K3

Constant

30

PMnK5

K4

Constant

31

PMnK6

K5

Constant

32

PMnK7

K6

Constant

33

PMnK8

K7

Constant

34

PMnK9

K8

Constant

36

PMnK11

HIL

Upper Limit of the Calculated Output

37

PMnK12

LOL

Lower Limit of the Calculated Output

60

PMnOU1

NCM

Calculated Output

70

PMnHDC HLD

Hold Mode Control/Status 0 0 0 0 0 0 X1 = 1 Hold Control/Status

72

PMnST

NML NMH

256

Configuration Guides - DX-9100 Configuration Guide

0

X1

Programmable Function Module Status 0 0 0 0 0 0 0 0 0 0 0 0 0 0 X2 X1 X1 = 1 Calculated Output at Low Limit X2 = 1 Calculated Output at High Limit

Page 257

Algorithm 12 Minimum Selection

Table 51: Algorithm 12 - Minimum Selection RI.

PM Tag

Alg. Tag

Description

00

PMnTYP

TYP

Algorithm Type = 12

10

PMnI1@

I1@

Input 1 Analog Connection

11

PMnI2@

I2@

Input 2 Analog Connection

12

PMnI3@

I3@

Input 3 Analog Connection

13

PMnI4@

I4@

Input 4 Analog Connection

14

PMnI5@

I5@

Input 5 Analog Connection

15

PMnI6@

I6@

Input 6 Analog Connection

16

PMnI7@

I7@

Input 7 Analog Connection

17

PMnI8@

I8@

Input 8 Analog Connection

26

PMnK1

K0

Constant

27

PMnK2

K1

Constant

28

PMnK3

K2

Constant

29

PMnK4

K3

Constant

30

PMnK5

K4

Constant

31

PMnK6

K5

Constant

32

PMnK7

K6

Constant

33

PMnK8

K7

Constant

34

PMnK9

K8

Constant

36

PMnK11

HIL

Upper Limit of the Calculated Output

37

PMnK12

LOL

Lower Limit of the Calculated Output

60

PMnOU1

NCM

Calculated Output

70

PMnHDC HLD

Hold Mode Control/Status 0 0 0 0 0 0 X1 = 1 Hold Control/Status

NML

Programmable Function Module Status 0 0 0 0 0 0 0 0 0 0 0 0 0 0 X2 X1 X1 = 1 Calculated Output at Low Limit

NMH

X2 = 1 Calculated Output at High Limit

72

PMnST

0

X1

Configuration Guides - DX-9100 Configuration Guide

257

Page 258

Algorithm 13 Maximum Selection

Table 52: Algorithm 13 - Maximum Selection RI.

PM Tag

Alg. Tag

Description

00

PMnTYP

TYP

Algorithm Type = 13

10

PMnI1@

I1@

Input 1 Analog Connection

11

PMnI2@

I2@

Input 2 Analog Connection

12

PMnI3@

I3@

Input 3 Analog Connection

13

PMnI4@

I4@

Input 4 Analog Connection

14

PMnI5@

I5@

Input 5 Analog Connection

15

PMnI6@

I6@

Input 6 Analog Connection

16

PMnI7@

I7@

Input 7 Analog Connection

17

PMnI8@

I8@

Input 8 Analog Connection

26

PMnK1

K0

Constant

27

PMnK2

K1

Constant

28

PMnK3

K2

Constant

29

PMnK4

K3

Constant

30

PMnK5

K4

Constant

31

PMnK6

K5

Constant

32

PMnK7

K6

Constant

33

PMnK8

K7

Constant

34

PMnK9

K8

Constant

36

PMnK11

HIL

Upper Limit of the Calculated Output

37

PMnK12

LOL

Lower Limit of the Calculated Output

60

PMnOU1

NCM

Calculated Output

70

PMnHDC HLD

Hold Mode Control/Status 0 0 0 0 0 0 X1 = 1 Hold Control/Status

NML

Programmable Function Module Status 0 0 0 0 0 0 0 0 0 0 0 0 0 0 X2 X1 X1 = 1 Calculated Output at Low Limit

NMH

X2 = 1 Calculated Output at High Limit

72

258

PMnST

Configuration Guides - DX-9100 Configuration Guide

0

X1

Page 259

Algorithm 14 Psychrometric Calculation °C

Table 53: Algorithm 14 - Psychrometric Calculation °C RI.

PM Tag

Alg. Tag

Description

00

PMnTYP

TYP

Algorithm Type = 14

02

PMnF1

FUN1

Function Channel 1 0 0 0 0 0 X3 X2 X1 X3 X2 X1 = 000 Not Used = 001

03

PMnF2

FUN2

Enthalpy

= 010

Wet Bulb

= 011

Dew Point

Function Channel 2 0 0 0 0 0 X3 X2 X1 X3 X2 X1 = 000 Not Used = 001

Enthalpy

10

PMnI1@

TM1@

Input 1 - Temperature Connection Channel 1

11

PMnI2@

RH1@

Input 2 - Humidity Connection Channel 1

12

PMnI3@

TM2@

Temperature Connection Channel 2

13

PMnI4@

RH2@

Relative Humidity Connection Channel 2

36

PMnK11

HIL1

Upper Limit of the Calculated Output Channel 1

37

PMnK12

LOL1

Lower Limit of the Calculated Output Channel 1

38

PMnK13

ATP1

Atmospheric Pressure Channel 1 (mbar)

53

PMnK28

HIL2

Upper Limit of the Calculated Output Channel 1

54

PMnK29

LOL2

Lower Limit of the Calculated Output Channel 1

55

PMnK30

ATP2

Atmospheric Pressure Channel 2 (mbar)

60

PMnOU1

NCM1

Calculated Output Channel 1

61

PMnOU2

NCM2

Calculated Output Channel 2

70

PMnHDC HLD1

Hold Mode Control/Status 0 0 0 0 0 0 X1 = 1 Hold Channel 1

HLD2

X2 = 1 Hold Channel 2

NML1

Programmable Function Module Status 0 0 0 0 0 0 0 0 0 0 0 0 X4 X3 X2 X1 X1 = 1 Calculated Output at Low Limit Channel 1

NMH1

X2 = 1 Calculated Output at High Limit Channel 1

NML2

X3 = 1 Calculated Output at Low Limit Channel 2

NMH2

X4 = 1 Calculated Output at High Limit Channel 2

72

Notes:

PMnST

X2 X1

Channel 2 is only available in the DX-9100, Version 1.1 or later, and provides only an enthalpy calculation. Only one Algorithm 14 or 15 may be configured in a DX controller.

Configuration Guides - DX-9100 Configuration Guide

259

Page 260

Algorithm 15 Psychrometric Calculation °F

Table 54: Algorithm 15 - Psychrometric Calculation °F RI.

PM Tag

Alg. Tag

Description

00

PMnTYP

TYP

Algorithm Type = 15

02

PMnF1

FUN1

Function Channel 1 0 0 0 0 0 X3 X2 X1 X3 X2 X1 = 000 Not Used = 001 Enthalpy = 010 Wet Bulb = 011 Dew Point

03

PMnF2

FUN2

Function Channel 2 0 0 0 0 0 X3 X2 X1 X3 X2 X1 = 000 Not Used = 001 Enthalpy

10 11 12 13

PMnI1@ PMnI2@ PMnI3@ PMnI4@

TM1@ RH1@ TM2@ RH2@

Input 1 - Temperature Connection Channel 1 Input 2 - Humidity Connection Channel 1 Temperature Connection Channel 2 Relative Humidity Connection Channel 2

36 37 38 53 54 55

PMnK11 PMnK12 PMnK13 PMnK28 PMnK29 PMnK30

HIL1 LOL1 ATP1 HIL2 LOL2 ATP2

Upper Limit of the Calculated Output Channel 1 Lower Limit of the Calculated Output Channel 1 Atmospheric Pressure Channel 1 (mbar) Upper Limit of the Calculated Output Channel 1 Lower Limit of the Calculated Output Channel 1 Atmospheric Pressure Channel 2 (mbar)

60 61

PMnOU1 PMnOU2

NCM1 NCM2

Calculated Output Channel 1 Calculated Output Channel 2

70

PMnHDC HLD1 HLD2

Hold Mode Control/Status 0 0 0 0 0 0 X2 X1 X1 = 1 Hold Channel 1 X2 = 1 Hold Channel 2

72

PMnST

NML1 NMH1 NML2 NMH2 Notes:

260

Programmable Function Module Status 0 0 0 0 0 0 0 0 0 0 0 0 X4 X3 X2 X1 X1 = 1 Calculated Output at Low Limit Channel 1 X2 = 1 Calculated Output at High Limit Channel 1 X3 = 1 Calculated Output at Low Limit Channel 2 X4 = 1 Calculated Output at High Limit Channel 2

Channel 2 is only available in the DX-9100, Version 1.1 or later, and provides only an enthalpy calculation. Only one Algorithm 14 or 15 may be configured in a DX controller.

Configuration Guides - DX-9100 Configuration Guide

Page 261

Algorithm 16 Line Segment Function

Table 55: Algorithm 16 - Line Segment Function RI.

PM Tag

Alg. Tag

Description

00

PMnTYP

TYP

Algorithm Type = 16

01

PMnOPT

OPT

NEXT

Algorithm Options X16 0 0 0 0 0 0 0 0 0 X16= 1

0 0

10

PMnI1@

I1@

Input Connection

26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60

PMnK1 PMnK2 PMnK3 PMnK4 PMnK5 PMnK6 PMnK7 PMnK8 PMnK9 PMnK10 PMnK11 PMnK12 PMnK13 PMnK14 PMnK15 PMnK16 PMnK17 PMnK18 PMnK19 PMnK20 PMnK21 PMnK22 PMnK23 PMnK24 PMnK25 PMnK26 PMnK27 PMnK28 PMnK29 PMnK30 PMnK31 PMnK32 PMnK33 PMnK34 PMnOU1

X0 Y0 X1 Y1 X2 Y2 X3 Y3 X4 Y4 X5 Y5 X6 Y6 X7 Y7 X8 Y8 X9 Y9 X10 Y10 X11 Y11 X12 Y12 X13 Y13 X14 Y14 X15 Y15 X16 Y16 NCM

Input Break Point Output Break Point Input Break Point Output Break Point Input Break Point Output Break Point Input Break Point Output Break Point Input Break Point Output Break Point Input Break Point Output Break Point Input Break Point Output Break Point Input Break Point Output Break Point Input Break Point Output Break Point Input Break Point Output Break Point Input Break Point Output Break Point Input Break Point Output Break Point Input Break Point Output Break Point Input Break Point Output Break Point Input Break Point Output Break Point Input Break Point Output Break Point Input Break Point Output Break Point Calculated Output

70

PMnHDC HLD

Hold Mode Control/Status 0 0 0 0 0 0 X1 = 1 Hold Control/Status

0 0 0 0 Chain to Next PM

0 0 1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 8 9 9 10 10 11 11 12 12 13 13 14 14 15 15 16 16

0

X1

Configuration Guides - DX-9100 Configuration Guide

261

Page 262

Algorithm 17 Input Selector

Table 56: Algorithm 17 - Input Selector RI.

PM Tag

Alg. Tag

Description

00

PMnTYP

TYP

Algorithm Type = 17

10

PMnI1@

I1@

Input 1 Analog Connection

11

PMnI2@

I2@

Input 2 Analog Connection

12

PMnI3@

I3@

Input 3 Analog Connection

13

PMnI4@

I4@

Input 4 Analog Connection

14

PMnI5@

I5@

Input 5 Logic Connection

15

PMnI6@

I6@

Input 6 Logic Connection

26

PMnK1

K1

Constant

27

PMnK2

C1

Constant

28

PMnK3

K2

Constant

29

PMnK4

C2

Constant

30

PMnK5

K3

Constant

31

PMnK6

C3

Constant

32

PMnK7

K4

Constant

33

PMnK8

C4

Constant

36

PMnK11

HIL

Upper Limit of the Calculated Output

37

PMnK12

LOL

Lower Limit of the Calculated Output

60

PMnOU1

NCM

Calculated Output

70

PMnHDC HLD

Hold Mode Control/Status 0 0 0 0 0 0 X1 = 1 Hold Control/Status

NML

Programmable Function Module Status 0 0 0 0 0 0 0 0 0 0 0 0 0 0 X2 X1 X1 = 1 Calculated Output at Low Limit

NMH

X2 = 1 Calculated Output at High Limit

72

262

PMnST

Configuration Guides - DX-9100 Configuration Guide

0

X1