The text of a manual · part 28 of 31
DX-9100 Configuration Guide: Appendix C: Programmable Function Module Items, pages 255 to 262
Pages 255 to 262 of 288, from DX-9100 Configuration Guide
The original document is the PDF (1.3 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Johnson Controls DX-9100
Page 255
RI. PM Tag (Cont.)
Alg. Tag
Description
56
PMnK31
DH2
Deviation High Alarm Value
- Loop 2
57
PMnK32
DL2
Deviation Low Alarm Value
- Loop 2
58
PMnK33
DLL2
Deviation Low Low Alarm Value
- Loop 2
61
PMnOU2
WSP1
Working Setpoint
- Loop 1
62
PMnOU3
WSP2
Working Setpoint
- Loop 2
63
PMnOU4
PV
Actual Process Variable
64
PMnOU5
PVS
PV Gain (100/Span)
65
PMnOU6
PVL
PV Low Range
66
PMnOU7
RSP
Actual Remote Setpoint
67
PMnOU8
RV
Actual Reference Variable
70
PMnHDC HLD
Hold Mode Control/Status 0 0 0 0 0 0 X2 X1 X1 = 1 Hold Control/Status
CMP
X2 = 1
OCM
Logic Outputs Control and Status 0 0 0 0 X4 X3 0 X1 X1 Control Output (Active Loop)
OCM1
X3
Control Output
- Loop 1
OCM2
X4
Control Output
- Loop 2
71
72
PMnDO
PMnST
Computer Mode Request
Controller Status CML
X1 = 1
Controller Output at 0
CMH
X2 = 1
Controller Output at 1
LLDA
X5 = 1
Deviation Alarm Low Low
LDA
X6 = 1
Deviation Alarm Low
HDA
X7 = 1
Deviation Alarm High
HHDA
X8 = 1
Deviation Alarm High High
SOF
X9 = 1
Shutoff Mode Active
STA
X10= 1
Startup Mode Active
EF
X11= 1
External Forcing Active
OF
X12= 1
Off Mode Active
SB
X13= 1
Standby Mode Active
RA
X14= 1
Reverse Action Mode
HEAT
X15= 1
Heating Mode (RA)
Configuration Guides - DX-9100 Configuration Guide
255
Page 256
Algorithm 11 Average Calculation
Table 50: Algorithm 11 - Average Calculation RI.
PM Tag
Alg. Tag
Description
00
PMnTYP
TYP
Algorithm Type = 11
10
PMnI1@
I1@
Input 1 Analog Connection
11
PMnI2@
I2@
Input 2 Analog Connection
12
PMnI3@
I3@
Input 3 Analog Connection
13
PMnI4@
I4@
Input 4 Analog Connection
14
PMnI5@
I5@
Input 5 Analog Connection
15
PMnI6@
I6@
Input 6 Analog Connection
16
PMnI7@
I7@
Input 7 Analog Connection
17
PMnI8@
I8@
Input 8 Analog Connection
26
PMnK1
K0
Constant
27
PMnK2
K1
Constant
28
PMnK3
K2
Constant
29
PMnK4
K3
Constant
30
PMnK5
K4
Constant
31
PMnK6
K5
Constant
32
PMnK7
K6
Constant
33
PMnK8
K7
Constant
34
PMnK9
K8
Constant
36
PMnK11
HIL
Upper Limit of the Calculated Output
37
PMnK12
LOL
Lower Limit of the Calculated Output
60
PMnOU1
NCM
Calculated Output
70
PMnHDC HLD
Hold Mode Control/Status 0 0 0 0 0 0 X1 = 1 Hold Control/Status
72
PMnST
NML NMH
256
Configuration Guides - DX-9100 Configuration Guide
0
X1
Programmable Function Module Status 0 0 0 0 0 0 0 0 0 0 0 0 0 0 X2 X1 X1 = 1 Calculated Output at Low Limit X2 = 1 Calculated Output at High Limit
Page 257
Algorithm 12 Minimum Selection
Table 51: Algorithm 12 - Minimum Selection RI.
PM Tag
Alg. Tag
Description
00
PMnTYP
TYP
Algorithm Type = 12
10
PMnI1@
I1@
Input 1 Analog Connection
11
PMnI2@
I2@
Input 2 Analog Connection
12
PMnI3@
I3@
Input 3 Analog Connection
13
PMnI4@
I4@
Input 4 Analog Connection
14
PMnI5@
I5@
Input 5 Analog Connection
15
PMnI6@
I6@
Input 6 Analog Connection
16
PMnI7@
I7@
Input 7 Analog Connection
17
PMnI8@
I8@
Input 8 Analog Connection
26
PMnK1
K0
Constant
27
PMnK2
K1
Constant
28
PMnK3
K2
Constant
29
PMnK4
K3
Constant
30
PMnK5
K4
Constant
31
PMnK6
K5
Constant
32
PMnK7
K6
Constant
33
PMnK8
K7
Constant
34
PMnK9
K8
Constant
36
PMnK11
HIL
Upper Limit of the Calculated Output
37
PMnK12
LOL
Lower Limit of the Calculated Output
60
PMnOU1
NCM
Calculated Output
70
PMnHDC HLD
Hold Mode Control/Status 0 0 0 0 0 0 X1 = 1 Hold Control/Status
NML
Programmable Function Module Status 0 0 0 0 0 0 0 0 0 0 0 0 0 0 X2 X1 X1 = 1 Calculated Output at Low Limit
NMH
X2 = 1 Calculated Output at High Limit
72
PMnST
0
X1
Configuration Guides - DX-9100 Configuration Guide
257
Page 258
Algorithm 13 Maximum Selection
Table 52: Algorithm 13 - Maximum Selection RI.
PM Tag
Alg. Tag
Description
00
PMnTYP
TYP
Algorithm Type = 13
10
PMnI1@
I1@
Input 1 Analog Connection
11
PMnI2@
I2@
Input 2 Analog Connection
12
PMnI3@
I3@
Input 3 Analog Connection
13
PMnI4@
I4@
Input 4 Analog Connection
14
PMnI5@
I5@
Input 5 Analog Connection
15
PMnI6@
I6@
Input 6 Analog Connection
16
PMnI7@
I7@
Input 7 Analog Connection
17
PMnI8@
I8@
Input 8 Analog Connection
26
PMnK1
K0
Constant
27
PMnK2
K1
Constant
28
PMnK3
K2
Constant
29
PMnK4
K3
Constant
30
PMnK5
K4
Constant
31
PMnK6
K5
Constant
32
PMnK7
K6
Constant
33
PMnK8
K7
Constant
34
PMnK9
K8
Constant
36
PMnK11
HIL
Upper Limit of the Calculated Output
37
PMnK12
LOL
Lower Limit of the Calculated Output
60
PMnOU1
NCM
Calculated Output
70
PMnHDC HLD
Hold Mode Control/Status 0 0 0 0 0 0 X1 = 1 Hold Control/Status
NML
Programmable Function Module Status 0 0 0 0 0 0 0 0 0 0 0 0 0 0 X2 X1 X1 = 1 Calculated Output at Low Limit
NMH
X2 = 1 Calculated Output at High Limit
72
258
PMnST
Configuration Guides - DX-9100 Configuration Guide
0
X1
Page 259
Algorithm 14 Psychrometric Calculation °C
Table 53: Algorithm 14 - Psychrometric Calculation °C RI.
PM Tag
Alg. Tag
Description
00
PMnTYP
TYP
Algorithm Type = 14
02
PMnF1
FUN1
Function Channel 1 0 0 0 0 0 X3 X2 X1 X3 X2 X1 = 000 Not Used = 001
03
PMnF2
FUN2
Enthalpy
= 010
Wet Bulb
= 011
Dew Point
Function Channel 2 0 0 0 0 0 X3 X2 X1 X3 X2 X1 = 000 Not Used = 001
Enthalpy
10
PMnI1@
TM1@
Input 1 - Temperature Connection Channel 1
11
PMnI2@
RH1@
Input 2 - Humidity Connection Channel 1
12
PMnI3@
TM2@
Temperature Connection Channel 2
13
PMnI4@
RH2@
Relative Humidity Connection Channel 2
36
PMnK11
HIL1
Upper Limit of the Calculated Output Channel 1
37
PMnK12
LOL1
Lower Limit of the Calculated Output Channel 1
38
PMnK13
ATP1
Atmospheric Pressure Channel 1 (mbar)
53
PMnK28
HIL2
Upper Limit of the Calculated Output Channel 1
54
PMnK29
LOL2
Lower Limit of the Calculated Output Channel 1
55
PMnK30
ATP2
Atmospheric Pressure Channel 2 (mbar)
60
PMnOU1
NCM1
Calculated Output Channel 1
61
PMnOU2
NCM2
Calculated Output Channel 2
70
PMnHDC HLD1
Hold Mode Control/Status 0 0 0 0 0 0 X1 = 1 Hold Channel 1
HLD2
X2 = 1 Hold Channel 2
NML1
Programmable Function Module Status 0 0 0 0 0 0 0 0 0 0 0 0 X4 X3 X2 X1 X1 = 1 Calculated Output at Low Limit Channel 1
NMH1
X2 = 1 Calculated Output at High Limit Channel 1
NML2
X3 = 1 Calculated Output at Low Limit Channel 2
NMH2
X4 = 1 Calculated Output at High Limit Channel 2
72
Notes:
PMnST
X2 X1
Channel 2 is only available in the DX-9100, Version 1.1 or later, and provides only an enthalpy calculation. Only one Algorithm 14 or 15 may be configured in a DX controller.
Configuration Guides - DX-9100 Configuration Guide
259
Page 260
Algorithm 15 Psychrometric Calculation °F
Table 54: Algorithm 15 - Psychrometric Calculation °F RI.
PM Tag
Alg. Tag
Description
00
PMnTYP
TYP
Algorithm Type = 15
02
PMnF1
FUN1
Function Channel 1 0 0 0 0 0 X3 X2 X1 X3 X2 X1 = 000 Not Used = 001 Enthalpy = 010 Wet Bulb = 011 Dew Point
03
PMnF2
FUN2
Function Channel 2 0 0 0 0 0 X3 X2 X1 X3 X2 X1 = 000 Not Used = 001 Enthalpy
10 11 12 13
PMnI1@ PMnI2@ PMnI3@ PMnI4@
TM1@ RH1@ TM2@ RH2@
Input 1 - Temperature Connection Channel 1 Input 2 - Humidity Connection Channel 1 Temperature Connection Channel 2 Relative Humidity Connection Channel 2
36 37 38 53 54 55
PMnK11 PMnK12 PMnK13 PMnK28 PMnK29 PMnK30
HIL1 LOL1 ATP1 HIL2 LOL2 ATP2
Upper Limit of the Calculated Output Channel 1 Lower Limit of the Calculated Output Channel 1 Atmospheric Pressure Channel 1 (mbar) Upper Limit of the Calculated Output Channel 1 Lower Limit of the Calculated Output Channel 1 Atmospheric Pressure Channel 2 (mbar)
60 61
PMnOU1 PMnOU2
NCM1 NCM2
Calculated Output Channel 1 Calculated Output Channel 2
70
PMnHDC HLD1 HLD2
Hold Mode Control/Status 0 0 0 0 0 0 X2 X1 X1 = 1 Hold Channel 1 X2 = 1 Hold Channel 2
72
PMnST
NML1 NMH1 NML2 NMH2 Notes:
260
Programmable Function Module Status 0 0 0 0 0 0 0 0 0 0 0 0 X4 X3 X2 X1 X1 = 1 Calculated Output at Low Limit Channel 1 X2 = 1 Calculated Output at High Limit Channel 1 X3 = 1 Calculated Output at Low Limit Channel 2 X4 = 1 Calculated Output at High Limit Channel 2
Channel 2 is only available in the DX-9100, Version 1.1 or later, and provides only an enthalpy calculation. Only one Algorithm 14 or 15 may be configured in a DX controller.
Configuration Guides - DX-9100 Configuration Guide
Page 261
Algorithm 16 Line Segment Function
Table 55: Algorithm 16 - Line Segment Function RI.
PM Tag
Alg. Tag
Description
00
PMnTYP
TYP
Algorithm Type = 16
01
PMnOPT
OPT
NEXT
Algorithm Options X16 0 0 0 0 0 0 0 0 0 X16= 1
0 0
10
PMnI1@
I1@
Input Connection
26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60
PMnK1 PMnK2 PMnK3 PMnK4 PMnK5 PMnK6 PMnK7 PMnK8 PMnK9 PMnK10 PMnK11 PMnK12 PMnK13 PMnK14 PMnK15 PMnK16 PMnK17 PMnK18 PMnK19 PMnK20 PMnK21 PMnK22 PMnK23 PMnK24 PMnK25 PMnK26 PMnK27 PMnK28 PMnK29 PMnK30 PMnK31 PMnK32 PMnK33 PMnK34 PMnOU1
X0 Y0 X1 Y1 X2 Y2 X3 Y3 X4 Y4 X5 Y5 X6 Y6 X7 Y7 X8 Y8 X9 Y9 X10 Y10 X11 Y11 X12 Y12 X13 Y13 X14 Y14 X15 Y15 X16 Y16 NCM
Input Break Point Output Break Point Input Break Point Output Break Point Input Break Point Output Break Point Input Break Point Output Break Point Input Break Point Output Break Point Input Break Point Output Break Point Input Break Point Output Break Point Input Break Point Output Break Point Input Break Point Output Break Point Input Break Point Output Break Point Input Break Point Output Break Point Input Break Point Output Break Point Input Break Point Output Break Point Input Break Point Output Break Point Input Break Point Output Break Point Input Break Point Output Break Point Input Break Point Output Break Point Calculated Output
70
PMnHDC HLD
Hold Mode Control/Status 0 0 0 0 0 0 X1 = 1 Hold Control/Status
0 0 0 0 Chain to Next PM
0 0 1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 8 9 9 10 10 11 11 12 12 13 13 14 14 15 15 16 16
0
X1
Configuration Guides - DX-9100 Configuration Guide
261
Page 262
Algorithm 17 Input Selector
Table 56: Algorithm 17 - Input Selector RI.
PM Tag
Alg. Tag
Description
00
PMnTYP
TYP
Algorithm Type = 17
10
PMnI1@
I1@
Input 1 Analog Connection
11
PMnI2@
I2@
Input 2 Analog Connection
12
PMnI3@
I3@
Input 3 Analog Connection
13
PMnI4@
I4@
Input 4 Analog Connection
14
PMnI5@
I5@
Input 5 Logic Connection
15
PMnI6@
I6@
Input 6 Logic Connection
26
PMnK1
K1
Constant
27
PMnK2
C1
Constant
28
PMnK3
K2
Constant
29
PMnK4
C2
Constant
30
PMnK5
K3
Constant
31
PMnK6
C3
Constant
32
PMnK7
K4
Constant
33
PMnK8
C4
Constant
36
PMnK11
HIL
Upper Limit of the Calculated Output
37
PMnK12
LOL
Lower Limit of the Calculated Output
60
PMnOU1
NCM
Calculated Output
70
PMnHDC HLD
Hold Mode Control/Status 0 0 0 0 0 0 X1 = 1 Hold Control/Status
NML
Programmable Function Module Status 0 0 0 0 0 0 0 0 0 0 0 0 0 0 X2 X1 X1 = 1 Calculated Output at Low Limit
NMH
X2 = 1 Calculated Output at High Limit
72
262
PMnST
Configuration Guides - DX-9100 Configuration Guide
0
X1