Page 79
Chapter 2: Installation, Wiring and Specifications
D2–16TD1–2, DC Output D2-16TD1-2 DC Output
D2-16TD2-2 DC Output
Outputs per Module Commons per Module Output Type External DC required Operating Voltage Peak Voltage ON Voltage Drop AC Frequency Minimum Load Current
16 (current sinking) 1 (2 I/O terminal points) NPN open collector 24 VDC ±4V @ 80 mA max 10.2-26.4 VDC 30 VDC 0.5 VDC maximum N/A 0.2 mA 0.1A/point Max Load Current 1.6A/common 0.1 mA @ 30 VDC Max Leakage Current 150 mA for 10 ms Max Inrush Current Base Power Required 5VDC 200 mA 0.5 ms OFF to ON Response 0.5 ms ON to OFF Response Terminal Type (included) Removable; D2-16IOCON Logic side Status Indicator
Weight Fuses
D2–16TD2–2, DC Output
2.3 oz. (65g)
Outputs per Module Commons per Module Output Type Operating Voltage Peak Voltage ON Voltage Drop AC Frequency Minimum Load Current
16 (current sourcing) 2 NPN open collector 10.2-26.4 VDC 30 VDC 1.0 VDC maximum N/A 0.2 mA 0.1A/point Max Load Current 1.6A/module 0.1 mA @ 30 VDC Max Leakage Current 150 mA for 10 ms Max Inrush Current Base Power Required 5VDC 200 mA 0.5 ms OFF to ON Response 0.5 ms ON to OFF Response Terminal Type (included) Removable; D2-16IOCON Logic side Status Indicator 2.8 oz. (80g) Weight None Fuses
None
Derating Chart
Points 16 12 8 4
OUT
0 0 32
10 20 30 40 50 55 ˚C 50 68 86 104 122131 ˚ F Ambient Temperature (˚C/˚F ) C 0
L
4
L
1
L
12--24 VDC 4 5 6 7
5
L
10.2- 26.4 VDC 0.1A CLASS2
2
L
6
L
A
3
L L 12--24VDC +
A 0 1 2 B 3 D2--16TD1--2
24VDC
+
7
0
C
1
+V 0
L
4
L
Internally connected
1
L
5
L
2
L
6
L
3
L
7
L
2 3 +V 0 1 2 3
+V Internal module circuitry
B
C 4 5 6 7 C 4 5 6 7
+ 24VDC L
+
OUTP UT
Optical Is olator
12--24 VDC COM
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
COM
* Can also be used with 5VDC supply
DL205 User Manual, 4th Edition, Rev. A
2–37
Page 80
Chapter 2: Installation, Wiring and Specifications
F2–16TD1(2)P, DC Output With Fault Protection
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
Not supported in D2-230, D2-240 and D2-250 CPUs.
These modules detect the following fault status and turn the related X bit(s) on. 1. Missing external 24VDC for the module 2. Open load1 3. Over temperature (the output is shut down) 4. Over load current (the output is shut down) Fault Status Missing external 24VDC Open load1 Over temperature
X bit Fault Status Indication All 16 X bits are on. Only the X bit assigned to the faulted output is on
Over load current
When these module are installed, 16 X bits are automatically assigned as the fault status indicator. Each X bit indicates the fault status of each output. In this example, X10-X27 are assigned as the fault status indicator. X10: Fault status indicator for Y0 X11: Fault status indicator for Y1
D2-250-1 or D2-260
X26: Fault status indicator for Y16 X27: Fault status indicator for Y17
Fault Status Missing external 24VDC Open load1 Over temperature Over load current
D2-08ND3
X0 - X7
Operation Apply external 24VDC Connect the load. Turn the output (Y bit) off or power cycle the PLC
NOTE 1: Open load detection can be disabled by removing the jumper switch J6 on the module PC board.
DL205 User Manual, 4th Edition, Rev. A
F2-16TD1P or F2-16TD2P
Slot 0 Slot 1 Slot 2 Slot 3 Slot 4
The fault status indicators (X bits) can be reset by performing the indicated operations in the following table:
Continued on next two pages.
2–38
Example
Jumper Switch J6 PC Board
X10 - X27 Y0 - Y17
Page 81
Chapter 2: Installation, Wiring and Specifications
F2–16TD1P, DC Output With Fault Protection Not supported in D2-230, D2-240 and D2-250 CPUs.
Supporting Firmware: D2-250-1 must be V4.80 or later D2-260 must be V2.60 or later
This module does not currently support Think & Do 8.0. It does not support Think & Do Live! or Studio.
Points 16
Derating Chart
12 8 4
OUT
0 10 20 30 40 50 55°C 50 68 86 104 122 131°F Ambient Temperature (°C/°F)
0 32
0V 0
L
4
L
A 0 1 2 B 3 F2–16TD1P
F2-16TD1P DC Output with Fault Protection Inputs per module Outputs per module Commons per module Output type Operating voltage Peak voltage AC frequency ON voltage drop Overcurrent trip
16 (status indication) 16 (current sinking) 1 (2 I/O terminal points) NMOS FET (open drain) 10.2 -26.4 VDC, external 40 VDC N/A 0.7 V (output current 0.5 A) 0.6 A min., 1.2 A max. A continuous, 0.5 A Maximum load current 0.25 peak J6 installed: 200 -A; Maximum OFF current Jumper J6 removed: 30 -A Base power required 5V 70 mA 0.5 ms OFF to ON response 0.5 ms ON to OFF response Removable (D2-16IOCON) Terminal type Logic Side Status indicators 2.0 oz. (25g) Weight None Fuses 24 VDC @ 50 mA External DC required External DC overvoltage 27 V, outputs are restored when voltage is within limits shutdown
12-24 VDC 4 5 6 7
1
L
5
L
10.2-26.4 VDC 0.25A CLASS2
2
L
6
L
A
3
L
7
L 24VDC
+
0V
12–24VDC +
0
L
4
L
1
L
5
L
2
L
6
L
3
L
0 1
24V
7
L
Internally connected
2 3 24V 0 1 2 3
24V Internal module circuitry
B
0V 4 5 6 7 0V 4 5 6 7
+ 24VDC OUTPUT
Optical Isolator
L
+ 12–24 VDC 0V 0V
When the A/B switch is in the A position, the LEDs display the output status of the module’s first 8 output points. Positon B displays the output status of the module’s second group of 8 output points.
DL205 User Manual, 4th Edition, Rev. A
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
2–39
Page 82
Chapter 2: Installation, Wiring and Specifications
F2–16TD2P, DC Output with Fault Protection Not supported in D2-230, D2-240 and D2-250 CPUs.
Supporting Firmware: D2-250-1 must be V4.80 or later D2-260 must be V2.60 or later
This module does not currently support Think & Do 8.0. It does not support Think & Do Live! or Studio.
Points 16
Derating Chart
12 8 4
OUT
0 10 20 30 40 50 55°C 50 68 86 104 122 131°F Ambient Temperature (°C/°F)
0 32
12–24VDC
V1
+
0
L
4
L
A 0 1 2 B 3 F2–16TD2P
5
L
2
L
6
L
7
L
24VDC
+
24V 0V
4
L
1
L
5
L
2
L
6
L
3
L
7
L
0 1 2
0
L
10.2-26.4 VDC 0.25A CLASS2
A
3
L
3 24V 0 1 2 3
24VDC
– +
12-24 VDC 4 5 6 7
1
L
B
24V
V1 4 5 6 7 0V 4 5 6 7
Reg
0V 12–24VDC +
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
L
2–40
Optical Isolator
V1
OUTPUT
When the A/B switch is in the A position, the LEDs display the output status of the module’s first 8 output points. Positon B displays the output status of the module’s second group of 8 output points.
DL205 User Manual, 4th Edition, Rev. A
F2-16TD2P DC Output with Fault Protection Inputs per module Outputs per module Commons per module Output type Operating voltage Peak voltage AC frequency ON voltage drop Overcurrent trip
16 (status indication) 16 (current sourcing) 1 NMOS FET (open source) 10.2 -26.4 VDC, external 40 VDC N/A 0.7 V (output current 0.5 A) 0.6 A min., 1.2A max. A continuous, 0.5 A Maximum load current 0.25 peak J6 installed: 200 -A; Maximum OFF current Jumper J6 removed: 30 -A Base power required 5V 70 mA 0.5 ms OFF to ON response 0.5 ms ON to OFF response Removable (D2-16IOCON) Terminal type Logic Side Status indicators 2.0 oz. (25g) Weight None Fuses 24 VDC @ 50 mA External DC required External DC overvoltage 27 V, outputs are restored when voltage is within limits shutdown
Page 83
Chapter 2: Installation, Wiring and Specifications
D2–32TD1, DC Output
D2–32TD2, DC Output
D2-32TD1 DC Output
D2-32TD2 DC Output
32 (current sinking) Outputs per Module 4 (8 I/O terminal points) Commons per Module NPN open collector Output Type 12-24 VDC Operating Voltage 30 VDC Peak Voltage 0.5 VDC maximum ON Voltage Drop 0.2 mA Minimum Load Current 0.1A/point; 3.2A per module Max Load Current 0.1 mA @ 30 VDC Max Leakage Current 150 mA for 10 ms Max Inrush Current Base Power Required 5VDC 350 mA 0.5 ms OFF to ON Response 0.5 ms ON to OFF Response Terminal Type (not included) removable 40-pin connector1
32 (current sourcing) Outputs per Module 4 (8 I/O terminal points) Commons per Module Transistor Output Type 12 to 24 VDC Operating Voltage 30 VDC Peak Voltage 0.5 VDC @ 0.1 A ON Voltage Drop 0.2 mA Minimum Load Current 0.1A/point; 0.8A/common Max Load Current 0.1 mA @ 30 VDC Max Leakage Current 150 mA @ 10 ms Max Inrush Current Base Power Required 5VDC 350 mA 0.5 ms OFF to ON Response 0.5 ms ON to OFF Response Terminal Type (not included) Removable 40-pin connector1
Module activity (no I/O status indicators) 2.1 oz. (60g) Weight None Fuses VDC max. 120 mA (all External DC Power Required 20-28 points on) 1 Connector sold separately. See Terminal Blocks and Wiring for wiring options.
Status Indicator
Status Indicator
Weight Fuses 1
Module activity (no I/O status indicators) 2.1 oz (60g) None
Connector sold separately. See Terminal Blocks and Wiring for wiring options.
DL205 User Manual, 4th Edition, Rev. A
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
2–41
Page 84
Chapter 2: Installation, Wiring and Specifications
F2–08TA, AC Output
D2–08TA, AC Output
F2-08TA AC Output 1 Outputs per Module per Module 2 Commons Output Type Operating Voltage 3 Peak Voltage ON Voltage Drop Frequency 4 ACMinimum Load Current 5 Max Load Current Leakage Current 6 Max Peak One Cycle Surge Current Base Power Required 5VDC 7 OFF to ON Response ON to OFF Response 8 Terminal Type (included) Status Indicator 9 Weight Fuses 10 11 12 13 14 A B C D
8 2 (Isolated) SSR (Triac with zero crossover) 24-140 VAC 140 VAC 1.6 V(rms) @ 1.5A 47 to 63 Hz 50 mA 1.5A / pt @ 30ºC 1.0A / pt @ 60ºC 4.0A / common; 8.0A / module @ 60ºC 0.7 mA(rms) 15A
250 mA 0.5 ms - 1/2 cycle 0.5 ms - 1/2 cycle Removable; D2-8IOCON Logic side 3.5 oz. None
2–42
DL205 User Manual, 4th Edition, Rev. A
D2-08TA AC Output Outputs per Module Commons per Module Output Type Operating Voltage Peak Voltage
8 1 (2 I/O terminal points) SSR (Triac) 15-264 VAC 264 VAC < 1.5 VAC (>0.1A) ON Voltage Drop < 3.0 VAC (<0.1A) 47 to 63 Hz AC Frequency 10 mA Minimum Load Current 0.5A/point; 4A/common Max Load Current 4 mA (264 VAC, 60 Hz) 1.2 mA (100 VAC, 60 Hz) Max Leakage Current 0.9 mA (100 VAC, 50 Hz) 10A for 10 ms Max Inrush Current Base Power Required 5VDC 250 mA 1 ms OFF to ON Response 1 ms + 1/2 cycle ON to OFF Response Terminal Type (included) Removable; D2-8IOCON Logic side Status Indicator 2.8 oz. (80g) Weight 1 per common, 6.3A slow blow, Fuses non-replaceable
Page 85
Chapter 2: Installation, Wiring and Specifications
D2–12TA, AC Output 2mA (132 VAC, 60 Hz) Max Leakage Current 10A for 10 ms Max Inrush Current Base Power Required 5VDC 350 mA 1 ms OFF to ON Response 1 ms + 1/2 cycle ON to OFF Response Terminal Type (included) Removable; D2-16IOCON Logic side Status Indicator 2.8 oz. (80g) Weight
D2-12TA AC Output Outputs per Module Outputs Points Consumed Commons per Module Output Type Operating Voltage Peak Voltage
12 16 (four unused, see chart below) 2 (isolated) SSR (Triac) 15-132 VAC 132 VAC < 1.5VAC (>50mA) < 4.0VAC (<50mA) 47 to 63 Hz 10 mA 0.3A/point; 1.8A/common
ON Voltage Drop AC Frequency Minimum Load Current Max Load Current
Points
Derating Chart
(2) 1 per common 3.15A slow blow, replaceable Order D2-FUSE-1 (5 per pack)
Fuses
P oints
Addres s es Us ed P oints Us ed?
Yn+0 Yn+1 Yn+2 Yn+3 Yn+4 Yn+5 Yn+6 Yn+7
Yes Yes Yes Yes Yes Yes No No
250mA / Pt.
12
300mA / Pt.
9
OUT
6 3 0 0 32
10 20 30 40 50 55 ˚C 50 68 86 104 122131 ˚ F Ambient Temperature (˚C/˚F )
15--132 VAC L L L L L L
15--132 VAC L
CA
L L
15- 132VAC 10mA- 0.3A 50/60 Hz
0 4 1
0
5
1
NC
2
2
CB
4 5 Internal module circuitry OUTP UT
0 4 1 5
0 1 2
CB 4 5
COM
NC 3
L
Optical Is olator
L
3
2
NC
Yes Yes Yes Yes Yes Yes No No
CA
NC NC
Us ed?
n is the starting address
3
3
L L
A 0 1 2 B 3 D2--12TA
18--110 VAC 4 5
Yn+10 Yn+11 Yn+12 Yn+13 Yn+14 Yn+15 Yn+16 Yn+17
D2--12TA
15--132 VAC
3.15A
DL205 User Manual, 4th Edition, Rev. A
To LE D
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
2–43
Page 86
Chapter 2: Installation, Wiring and Specifications
D2–04TRS, Relay Output
1 D2-04TRS Relay Output Outputs per Module 2 Outputs Points Consumed per Module 3 Commons Output Type Operating Voltage Voltage 4 Peak ON Voltage Drop Frequency 5 ACMinimum Load Current Max Load Current (resistive) 6 Relay Life (Operations) 7 Voltage &Typical Load Current Type of Load 1A 2A 3A 4A 8 9 10 11 12 13 14 A B C D
0.1 mA @ 264 VAC Max Leakage Current 5A for < 10 ms Max Inrush Current Base Power Required 5VDC 250 mA 10 ms OFF to ON Response 10 ms ON to OFF Response Removable; D2-8IOCON Terminal Type (included) Logic side Status Indicator 2.8 oz. (80 g) Weight
4 8 (only 1st 4pts. are used) 4 (isolated) Relay, form A (SPST) 5-30 VDC / 5-240 VAC 30 VDC, 264 VAC 0.72 VDC maximum 47 to 63 Hz 10 mA 4A/point; 8A/module (resistive)
24 VDC Resistive 24 VDC Solenoid 110 VAC Resistive 110 VAC Solenoid 220 VAC Resistive 220 VAC Solenoid
500k 100k 500k 200k 350k 100k
200k 40k 250k 100k 150k 50k
100k –– 150k 50k 100k ––
1 per point 6.3A slow blow, replaceable Order D2-FUSE-3 (5 per pack)
Fuses
50k – 100k – 50k ––
Derating Chart
Points 4
2A / Pt.
3
3A / Pt. 4A / Pt.
At 24 VDC, solenoid (inductive) loads over 2A cannot be used.
2
At 100 VAC, solenoid (inductive) loads over 3A cannot be used.
1
At 220 VAC, solenoid (inductive) loads over 2A cannot be used.
0
OUT
RELAY
10 50
0 32
20 30 40 68 86 104 Ambient Temperature (˚C/˚F )
50 55 ˚ C 122 131 ˚ F
0 1 2 3 D2--04TR S 5-240VAC 4A50/60Hz 5- 30VDC 10mA- 4A
NC
5--30 VDC 5--240 VAC
NC
C0
0
L
C1
1
L
C2
2
L
C3
3
L
2–44
Internal module circuitry
NC NC C0 L C1 L C2 L C3 L
0
OUTP UT L
1 To LE D 2
3
D2--04TR S
DL205 User Manual, 4th Edition, Rev. A
COM 5--30 VDC 5--240 VAC
6.3A
Page 87
Chapter 2: Installation, Wiring and Specifications
D2–08TR, Relay Output Max Leakage Current
D2-08TR Relay Output 8 Outputs per Module Outputs Points Consumed 8 1 (2 I/O terminals) Commons per Module Relay, form A (SPST) Output Type 5-30 VDC; 5-240 VAC Operating Voltage 30 VDC, 264 VAC Peak Voltage N/A ON Voltage Drop 47 to 60 Hz AC Frequency 5mA @ 5VDC Minimum Load Current Max Load Current (resistive) 1A/point; 4A/common
Max Inrush Current Base Power Required 5VDC OFF to ON Response ON to OFF Response Terminal Type (included) Status Indicator Weight Fuses
0.1 mA @265 VAC Output: 3A for 10 ms Common: 10A for 10 ms 250 mA 12 ms 10 ms Removable; D2-8IOCON Logic side 3.9 oz. (110g) One 6.3A slow blow, replaceable Order D2-FUSE-3 (5 per pack)
Typical Relay Life (Operations) Voltage/Load
Current
Closures
24 VDC Resistive 24 VDC Solenoid 110 VDC Resistive 110 VDC Solenoid 220 VAC Resistive 220 VAC Solenoid
1A 1A 1A 1A 1A 1A
500k 100k 500k 200k 350k 100k
Derating Chart
Points 8
0.5A / Pt. OUT 0 1 2 3 D2--08TR
RELAY
6
4 5 6 7
4 1A / Pt. 2 0
5--30 VDC 5--240 VAC
Internally connected
C
5-240VAC 1A50/60Hz 5- 30VDC 5mA- 1A
C 0 L L
1
L
0 L 1
Internal module circuitry
2
2
6
L
6 L
L
4 5
5
L
L
10 20 30 40 50 55 ˚C 50 68 86 104 122131 ˚ F Ambient Temperature (˚C/˚F )
C L
4
0 32
C
3
OUTP UT L
3 7
7
To LE D D2--08TR
COM 5--30 VDC 5--240 VAC
6.3A
DL205 User Manual, 4th Edition, Rev. A
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
2–45