Page 88
Chapter 2: Installation, Wiring and Specifications
F2–08TR, Relay Output
1 F2-08TR Relay Output Outputs per Module Points Consumed 2 Outputs Commons per Module Type 3 Output Operating Voltage Voltage 4 Peak ON Voltage Drop AC Frequency 5 Minimum Load Current Max Load Current (resistive) 6 Max Leakage Current Max Inrush Current Power Required 5VDC 7 Base OFF to ON Response to OFF Response 8 ON Terminal Type (included) Status Indicator 9 Weight Fuses 10 11 12 13 14 A B C D
8 8 2 (isolated), 4-pts. per common 8, Form A (SPST normally open) 7A @ 12-28 VDC, 12-250VAC; 0.5A @ 120 VDC 150 VDC, 265 VAC N/A 47 to 63Hz 10 mA @ 12 VDC 10A/point 3 (subject to derating) Max of 10A/common N/A 12A 670 mA 15 ms (typical) 5 ms (typical) Removable; D2-8IOCON Logic side 5.5 oz. (156g) None
Typical Relay Life1 (Operations) at Room Temperature Voltage & Type of Load 2
50 mA
24 VDC Resistive 10M 600k 300k 24 VDC Solenoid 150k 75k 110 VDC Resistive – 600k 300k 110 VDC Solenoid – 500k 200k 220 VAC Resistive – 300k 150k 220 VAC Solenoid – 250k 100k 1) Contact life may be extended beyond those values shown with the use of arc suppression techniques described in the DL205 User Manual. Since these modules have no leakage current, they do not have built-in snubber. For example, if you place a diode across a 24 VDC inductive load, you can significantly increase the life of the relay. 2) At 120 VDC 0.5A resistive load, contact life cycle is 200k cycles. 3) Normally closed contacts have 1/2 the current handling capability of the normally open contacts.
Derating Chart
2.5 A/pt.
8 6
3 A/pt.
Number Points On 4 (100% duty 2 cycle)
5A/pt. 10 A/pt.
0 0 32 OUT
10 20 30 40 50 55 °C 50 68 86 104 122 131 °F Ambient Temperature (°C/°F )
RELAY
0 1 2 3 F 2--08TR
4 5 6 7
12- 250VAC 10A50/60Hz 12- 28VDC 10ma-10A
Typical Circuit 12--28VDC 12--250VAC
Internal Circuitry
Common
L
L
L L
NO 0 NO 1 C0-3 NO 2 NO 3
L
NO 4
L
NO 5
L
C4-7 NO 6 NO 7
L
2–46
Load Current 5A 7A
DL205 User Manual, 4th Edition, Rev. A
NO L
Page 89
Chapter 2: Installation, Wiring and Specifications
F2–08TRS, Relay Output F2-08TRS Relay Output Outputs per Module Outputs Points Consumed Commons per Module
8 8 8 (isolated) 3, Form C (SPDT) 5, Form A (SPST normally open) 7A @ 12-28 VDC, 12-250 VAC 0.5A @ 120VDC 150 VDC, 265 VAC N/A 47 to 63Hz 10 mA @ 12 VDC
Output Type Operating Voltage
Peak Voltage ON Voltage Drop AC Frequency Minimum Load Current Max Load Current (resistive) 7A/point 3 (subject to derating) N/A Max Leakage Current 12A Max Inrush Current Base Power Required 5VDC 670 mA 15 ms (typical) OFF to ON Response 5 ms (typical) ON to OFF Response Removable; D2-16IOCON Terminal Type (included) Logic side Status Indicator 5.5oz. (156g) Weight None Fuses
Typical Relay Life1 (Operations) at Room Temperature Voltage & Type of Load 2
Load Current 50mA 5A
7A
24 VDC Resistive 10M 600k 300k 24 VDC Solenoid 150k 75k 110 VDC Resistive – 600k 300k 110 VDC Solenoid – 500k 200k 220 VAC Resistive – 300k 150k 220 VAC Solenoid – 250k 100k 1) Contact life may be extended beyond those values shown with the use of arc suppression techniques described in the DL205 User Manual. Since these modules have no leakage current, they do not have built-in snubber. For example, if you place a diode across a 24 VDC inductive load, you can significantly increase the life of the relay. 2) At 120 VDC 0.5A resistive load, contact life cycle is 200k cycles. 3) Normally closed contacts have 1/2 the current handling capability of the normally open contacts. Derating Chart
8
4A/ pt.
6
5A/pt.
Number Points On 4 (100% duty 2 cycle)
6A/ pt. 7A/pt.
0 0 32
OUT NO 0
12--28VDC 12--250VAC
L
C1 C0
12--28VDC 12--250VAC
NO 1 L
12--28VDC 12--250VAC
NC 0 normally clos ed L C2 C3
12--28VDC 12--250VAC
NO 2 NO 3
12--28VDC 12--250VAC
L
C4 C5
12--28VDC 12--250VAC
NO 4
NO 1
Typical Circuit (points 1,2,3,4,5) 12--28VDC 12--250VAC
NO L
C0 NC 0
NO 2
NC 6
Typical Circuit (P oints 0, 6, & 7 only)
C3 NO 3
NO 5
12--28VDC 12--250VAC
NC 7 C6
NC 7 normally clos ed L C7
12--28VDC 12--250VAC
NO 6 NO 7
Internal Circuitry
Common
C6 NO 6
C7 NO7 L L
L
Internal Circuitry
Common
C2
NO 4 L
NC 6
4 5 6 7
NO 0
C5 NO 5
12--28VDC 12--250VAC
12- 250VAC 7A50/60Hz 12- 28VDC 10ma- 7A
C4
L normally clos ed L
RELAY
0 1 2 3 F 2--08TR S
C1
L
10 20 30 40 50 55 ˚C 50 68 86 104 122131 ˚ F Ambient Temperature (˚C/˚F )
NO
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
NC
L
DL205 User Manual, 4th Edition, Rev. A
2–47
Page 90
Chapter 2: Installation, Wiring and Specifications
D2–12TR, Relay Output
1 D2-12TR Relay Output Outputs per Module 2 Outputs Points Consumed Commons per Module Type 3 Output Operating Voltage Peak Voltage 4 ON Voltage Drop AC Frequency Load Current 5 Minimum Max Load Current (resistive) Max Leakage Current 6 Max Inrush Current Power Required 5VDC 7 Base OFF to ON Response ON to OFF Response Type (included) 8 Terminal Status Indicator 9 Weight Fuses 10 11 12 13 14 A B C D
Typical Relay Life (Operations)
12 16 (four unused, see chart below) 2 (6-pts. per common) Relay, form A (SPST) 5-30 VDC; 5-240 VAC 30 VDC; 264 VAC N/A 47 to 60 Hz 5 mA @ 5VDC 1.5 A/point; Max of 3A/common 0.1 mA @ 265 VAC Output: 3A for 10 ms Common: 10A for 10 ms 450 mA 10 ms 10 ms Removable; D2-16IOCON Logic side 4.6 oz. (130g) (2) 4A slow blow, replaceable Order D2-FUSE-4 (5 per pack)
5--30 VDC 5--240 VAC
4
L L
5
2
NC
3
L
5--30 VDC 5--240 VAC L
L L
500k 100k 500k 200k 350k 100k
Addresses Used Points
Used?
Yn+0 Yn+1 Yn+2 Yn+3 Yn+4 Yn+5 Yn+6 Yn+7
Yes Yes Yes Yes Yes Yes No No
NC
Used? Yes Yes Yes Yes Yes Yes No No
Derating Chart
0.5A / Pt. OUT A 0 1 2 B 3 D2--12TR
RELAY
8
4 5
4
0.75A / Pt.
0 1 2
1.25A / Pt. 1.5A / Pt.
0 0 32
10 20 30 40 50 55 ˚C 50 68 86 104 122131 ˚ F Ambient Temperature (˚C/˚F )
5- 240VAC 1.5A50/60Hz 5- 30VDC 5mA- 1.5A
CA Internal module circuitry
4 5
OUTP UT L
3
CB
0
4
1
5
2
0 1 2
CB
NC
To LE D
4 5
3
NC
2–48
Yn+10 Yn+11 Yn+12 Yn+13 Yn+14 Yn+15 Yn+16 Yn+17 n is the starting address
12
3
L
Points
NC
L L
Closures
1A 1A 1A 1A 1A 1A
Points
1
L
Current
24 VDC Resistive 24 VDC Solenoid 110 VDC Resistive 110 VDC Solenoid 220 VAC Resistive 220 VAC Solenoid
CA
0
L
L
Voltage/Load
D2--12TR
DL205 User Manual, 4th Edition, Rev. A
COM 5--30 VDC 5--240 VAC
4A
Page 91
Chapter 2: Installation, Wiring and Specifications
D2–08CDR, 4 pt. DC Input / 4pt. Relay Output D2-08CDR 4-pt. DC In / 4pt. Relay Out General Specifications Base Power Required 5VDC 200 mA Terminal Type (included) Removable; D2-8IOCON Logic side Status Indicator 3.5 oz. (100 g) Weight Input Specifications 4 (sink/source) Inputs per Module 8 (only first 4-pts. are used) Input Points Consumed 1 Commons per Module 20-28 VDC Input Voltage Range 30 VDC Peak Voltage 19 VDC minimum ON Voltage Level 7 VDC maximum OFF Voltage Level N/A AC Frequency 4.7 Input Impedance 5 mA @ 24 VDC Input Current 8 mA @ 30 VDC Maximum Current 4.5 mA Minimum ON Current 1.5 mA Maximum OFF Current 1 to 10 ms OFF to ON Response 1 to 10 ms ON to OFF Response None Fuses (input circuits)
Output Specifications 4 Outputs per Module Outputs Points Consumed 8 (only first 4-pts. are used) 1 Commons per Module Relay, form A (SPST) Output Type 5-30 VDC; 5-240 VAC Operating Voltage 30 VDC; 264 VAC Peak Voltage N/A ON Voltage Drop 47 to 63 Hz AC Frequency 5 mA @ 5 VDC Minimum Load Current Max Load Current (resistive) 1A/point ; 4A/module 0.1 mA @ 264 VAC Max Leakage Current 3A for < 100 ms 10 A for < 10 ms (common) 12 ms 10 ms 1 (6.3A slow blow, replaceable); Order D2-FUSE-3 (5 per pack)
Max Inrush Current OFF to ON Response ON to OFF Response Fuses (output circuits)
Current
Closures
24 VDC Resistive 24 VDC Solenoid 110 VAC Resistive 110 VAC Solenoid 220 VAC Resistive 220 VAC Solenoid
1A 1A 1A 1A 1A 1A
500k 100k 500k 200k 350k 100k
Outputs 1A / Pt. Inputs 5mA / Pt.
3 2
Typical Relay Life (Operations) Voltage/Load
Derating Chart
Points 4
1 0 IN/ OUT A 0 1 2 3 D2--08CDR
24VDC RELAY 0 B 1 2 3
0 32
10 20 30 40 50 55°C 50 68 86 104 122131°F Ambient Temperature (°C/°F )
Internal module circuitry V+
D2- 08CDR 20- 28VDC 8mA
INP UT CA
0
Source
1
L
Sink
+
To LE D
0
L
24VD C
CA
--
O L
2
1
Source 24VDC Internal module circuitry
3
1
Optical Is olator
COM
+
3
L
OUTP UT
CB
2 L
2
L
0 L
Sink
1
L 5- 240VAC 1A50/60Hz 5- 30VDC 5mA- 1A
2 3
To LE D
L
3 COM
CB 5--30 VDC 5--240 VAC
5--30 VDC 5--240 VAC
6.3A
DL205 User Manual, 4th Edition, Rev. A
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
2–49
Page 92
Chapter 2: Installation, Wiring and Specifications
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
Glossary of Specification Terms
2–50
Inputs or Outputs Per Module Indicates number of input or output points per module and designates current sinking, current sourcing, or either.
Commons Per Module Number of commons per module and their electrical characteristics.
Input Voltage Range The operating voltage range of the input circuit.
Output Voltage Range The operating voltage range of the output circuit.
Peak Voltage Maximum voltage allowed for the input circuit.
AC Frequency AC modules are designed to operate within a specific frequency range.
ON Voltage Level The voltage level at which the input point will turn ON.
OFF Voltage Level The voltage level at which the input point will turn OFF.
Input impedance Input impedance can be used to calculate input current for a particular operating voltage.
Input Current Typical operating current for an active (ON) input.
Minimum ON Current The minimum current for the input circuit to operate reliably in the ON state.
Maximum OFF Current The maximum current for the input circuit to operate reliably in the OFF state.
Minimum Load The minimum load current for the output circuit to operate properly.
External DC Required Some output modules require external power for the output circuitry.
ON Voltage Drop Sometimes called “saturation voltage”, it is the voltage measured from an output point to its common terminal when the output is ON at max. load.
DL205 User Manual, 4th Edition, Rev. A
Page 93
Chapter 2: Installation, Wiring and Specifications
Maximum Leakage Current
1 Maximum Inrush Current 2 The maximum current used by a load for a short duration upon an OFF to ON transition of a output point. It is greater than the normal ON state current and is characteristic of 3 inductive loads in AC circuits. Base Power Required 4 Power from the base power supply is used by the DL205 input modules and varies between different modules. The guidelines for using module power is explained in the power budget 5 configuration section in Chapter 4–7. OFF to ON Response 6 The time the module requires to process an OFF to ON state transition. ON to OFF Response 7 The time the module requires to process an ON to OFF state transition. Terminal Type 8 Indicates whether the terminal type is a removable or non-removable connector or a terminal. Status Indicators 9 The LEDs that indicate the ON/OFF status of an input point. These LEDs are electrically located on either the logic side or the field device side of the input circuit. 10 Weight Indicates the weight of the module. See Appendix F for a list of the weights for the various 11 DL205 components. Fuses 12 Protective devices for an output circuit, which stop current flow when current exceeds the fuse rating. They may be replaceable or non–replaceable, or located externally or internally. 13 14 A B C D The maximum current a connected maximum load will receive when the output point is OFF.
DL205 User Manual, 4th Edition, Rev. A
2–51
Page 94
Chapter 2: Installation, Wiring and Specifications
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 2–52
Notes
DL205 User Manual, 4th Edition, Rev. A