Page 313

Chapter 5: Standard RLL Instructions - Math

Subtract (SUB) Subtract is a 16-bit instruction that subtracts the BCD

1 2 3 Operand Data Type DL230 Range DL240 Range DL250-1 Range DL260 Range A aaa aaa aaa aaa 4 5 Discrete Bit Flags Description 6 7 8 NOTE: A constant (K) cannot be used for the BCD value. 9 Status flags are only valid until another instruction that uses the same flags is executed. In the following example, when X1 is on, the value in V2000 will be loaded into the 10 accumulator using the Load instruction. The value in V2006 is subtracted from the value in the accumulator using the Subtract instruction. The value in the accumulator is copied to V2010 using the Out instruction. 11 12 13 14 A B C D

230 value (Aaaa) in a V-memory location from the BCD value 240 in the lower 16 bits of the accumulator. The result resides 250-1 in the accumulator. 260 DS Used HPP Used

V-memory

V

All See memory map

Pointer

P

-

SP63 SP66 SP67 SP70 SP75

SUB

A aaa

All See memory map All V-memory. See memory map

All See memory map All V-memory. See memory map

All See memory map All V-memory. See memory map

On when the result of the instruction causes the value in the accumulator to be zero On when the 16 bit addition instruction results in a carry On when the 32 bit addition instruction results in a carry On anytime the value in the accumulator is negative On when a BCD instruction is executed and a NON-BCD number is encountered

Direct SOFT

V2000

X1

2

4

7

5

LD

V2000

Load the value in V2000 into the lower 16 bits of the accumulator

The unused accumulator bits are set to zero 0 0 0 0

_

SUB

2

4

7

5

(Accumulator)

1

5

9

2

(V2006)

0

8

8

3

0

8

8

3

V2006

Acc.

Subtract the value in V2006 from the value in the lower 16 bits of the accumulator OUT

V2010

V2010

Copy the value in the lower 16 bits of the accumulator to V2010

Handheld Programmer Keystrokes $

B

STR

1

SHFT

L ANDST

D

SHFT

S RST

U

GX OUT

ENT

C

3

A

ISG

1

SHFT

V AND

C

2

A

A

0

0

SHFT

V AND

C

A

B

A

2

B

0

1

0

ENT

A

2 0

A

0

G

0

6

ENT

ENT

DL205 User Manual, 4th Edition, Rev. A

5–91

Page 314

Chapter 5: Standard RLL Instructions - Math

Subtract Double (SUBD)

Subtract Double is a 32-bit instruction that subtracts the 1 SUBD BCD value (Aaaa), which is either two consecutive V-memory A aaa locations or an 8-digit (max.) constant, from the BCD value 2 in the accumulator. The result resides in the accumulator.

3 Operand Data Type DL230 Range DL240 Range DL250-1 Range DL260 Range A aaa aaa aaa aaa 4 5 6 Discrete Bit Flags Description 7 8 NOTE: The status flags are only valid until another instruction that uses the same flags is executed. 9 In the following example, when X1 is on, the value in V2000 and V2001 will be loaded into the accumulator using the Load Double instruction. The value in V2006 and V2007 is 10 subtracted from the value in the accumulator. The value in the accumulator is copied to V2010 and V2011 using the Out Double instruction. 11 12 13 14 A B C D 230 240

250-1 260

V-memory

V

All (See page 3 - 53)

Pointer

P

-

Constant

K

0-99999999

SP63 SP64 SP65 SP70 SP75

DS Used HPP Used

All (See page 3 - 54) All V-memory (See page 3 - 54) 0-99999999

All (See page 3 - 55) All V-memory (See page 3 - 55) 0-99999999

All (See page 3 - 56) All V-memory (See page 3 - 56) 0-99999999

On when the result of the instruction causes the value in the accumulator to be zero. On when the 16 bit subtraction instruction results in a borrow. On when the 32 bit subtraction instruction results in a borrow. On anytime the value in the accumulator is negative. On when a BCD instruction is executed and a NON-BCD number was encountered.

DirectSOFT

V2001

0

X1

1

0

V2000

6

3

2

7

4

LDD

V2000

Load the value in V2000 and V2001 into the accumulator

0 1

0

6

3

2

7

4

6

7

2

3

7

5

0

3

9

0

8

9

9

0

3

9

0

8

9

9

_

SUBD

V2006

0

ACC.

The value in V2006 and V2007 is subtracted from the value in the accumulator OUTD

0

V2010

V2011

V2010

Copy the value in the accumulator to V2010 and V2011

Handheld Programmer Keystrokes $

B

STR

L ANDST

SHFT

S RST

SHFT

SHFT

D

GX OUT

5–92

1

SHFT

D

ENT

D

3

C

B

ISG

A

0

D

1

C 3

A

2

3

U

B 0

DL205 User Manual, 4th Edition, Rev. A

A 1

0

A

2

3

A 2

A

0

C

0

ENT

A

0

ENT

G

0

6

ENT

Page 315

Chapter 5: Standard RLL Instructions - Math

Subtract Real (SUBR) Subtract Real is a 32-bit instruction that subtracts a real 230 The number, which is either two consecutive V-memory locations or 240 a 32-bit constant, from a real number in the accumulator. The 250-1 result is a 32-bit real number that resides in the accumulator. 260 Both numbers must be Real data type (IEEE floating point

SUBR A aaa format).

Operand Data Type

DS Used HPP N/A

DL250-1 Range

DL260 Range aaa aaa

A V-memory Pointer

V All. (See page 3-55) All. (See page 3-56) P All V-memory (See page 3-55) All V-memory (See page 3-56) -3.402823E+038 to -3.402823E+038 to R + 3.402823E+038 + 3.402823E+038

Constant

Discrete Bit Flags SP63 SP70 SP71 SP72 SP73 SP74 SP75

Description On when the result of the instruction causes the value in the accumulator to be zero. On anytime the value in the accumulator is negative. On anytime the V-memory specified by a pointer (P) is not valid. On anytime the value in the accumulator is an invalid floating point number. On when a signed addition or subtraction results in an incorrect sign bit. On anytime a floating point math operation results in an underflow error. On when a real number instruction is executed and a non-real number was encountered.

NOTE: Status flags are valid only until another instruction uses the same flag.

DirectSOFT X1

LDR

4

1

B

0

0

0

0

0

R22.0 Load the real number 22.0 into the accumulator. _

2

2

B

0

0

0

0

0

(Accumulator)

5

4 _ 4

1

1

1

7

0

0

0

0

0

(SUBR)

7

Acc. 4

0

E

0

0

0

0

0

0

0

(decimal)

SUBR R15.0

V1401

Subtract the real number 15.0 from the accumulator contents, which is in real number format.

OUTD

4

0

E

V1400 0

0

0

(Hex number)

Real Value

Acc.

8 4

2

1

8

4 2

1

8

4

2 1

8

4

2

1

8 4

2

1

8

4 2

1

8

4

2 1

8

4

2

1

0 1

0

0

0

0 0

0

1

1

1 0

0

0

0

0

0 0

0

0

0

0 0

0

0

0

0 0

0

0

0

0

V1400 Copy the result in the accumulator to V1400 and V1401.

Sign Bit

Exponent (8 bits)

128 + 1 = 129 129 - 127 = 2 Implies 2 (exp 2)

Mantissa (23 bits)

1.11 x 2 (exp 2) = 111. binary= 7 decimal

NOTE: The current HPP does not support real number entry with automatic conversion to the 32-bit IEEE format. You must use DirectSOFT for this feature.

DL205 User Manual, 4th Edition, Rev. A

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

5–93

Page 316

Chapter 5: Standard RLL Instructions - Math

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

Multiply (MUL) is a 16-bit instruction that multiplies the BCD 230 Multiply value (Aaaa), which is either a V-memory location or a 240 4–digit (max.) constant, by the BCD value in the lower 16 250-1 bits of the accumulator The result can be up to 8 digits and 260 resides in the accumulator. Operand Data Type

MUL A aaa

DL230 Range

DL240 Range

DL250-1 Range

A aaa aaa aaa aaa

V-memory

V

All (See page 3 - 53)

Pointer

P

-

Constant

K

0-9999

All (See page 3 - 54) All V-memory (See page 3 - 54) 0-9999

All (See page 3 - 55) All V-memory (See page 3 - 55) 0-9999

All (See page 3 - 56) All V-memory (See page 3 - 56) 0-9999

Discrete Bit Flags

DL260 Range

Description

SP63 SP70 SP75

On when the result of the instruction causes the value in the accumulator to be zero. On anytime the value in the accumulator is negative. On when a BCD instruction is executed and a NON-BCD number was encountered.

NOTE: The status flags are only valid until another instruction that uses the same flags is executed.

In the following example, when X1 is on, the value in V2000 will be loaded into the accumulator using the Load instruction. The value in V2006 is multiplied by the value in the accumulator. The value in the accumulator is copied to V2010 and V2011 using the Out Double instruction. DS Used HPP Used

5–94

V2000

DirectSOFT X1

1

LD

0

0

0

V2000 The unused accumulator bits are set to zero

Load the value in V2000 into the lower 16 bits of the accumulator

0

0

0

0

1 0 0 0 2

X

MUL

Acc.

V2006

0

0

0

2

5

0

0

2

5

5

0

0

0

0

0

0

The value in V2006 is multiplied by the value in the accumulator 0 OUTD

V2011

V2010

V2010

Copy the value in the accumulator to V2010 and V2011

Handheld Programmer Keystrokes $

B STR

1

SHFT

L ANDST

D

SHFT

M ORST

U

GX OUT

SHFT

D

ENT C

ISG

A 2

3 L ANDST

C

A

A 2

A 0

B 0

DL205 User Manual, 4th Edition, Rev. A

0 A

0

2 C

3

A 0

0 A

1

ENT G

0

6 ENT

ENT

(Accumulator) (V2006)

Page 317

Chapter 5: Standard RLL Instructions - Math

Multiply Double (MULD) Multiply Double is a 32-bit instruction that multiplies the 8-

230 digit BCD value in the accumulator by the 8-digit BCD value 240 in the two consecutive V-memory locations specified in the 250-1 instruction. The lower 8 digits of the results reside in the 260 accumulator. Upper digits of the result reside in the

MULD A aaa accumulator stack.

Operand Data Type

DL250-1 Range

V-memory Pointer

DL260 Range

A aaa aaa

V P

All V-mem (See page 3 - 55) All V-mem (See page 3 - 55)

All V-mem (See page 3 - 56) All V-mem (See page 3 - 56)

Discrete Bit Flags

Description

SP63 SP70 SP75

On when the result of the instruction causes the value in the accumulator to be zero. On anytime the value in the accumulator is negative. On when a BCD instruction is executed and a NON-BCD number was encountered.

NOTE: Status flags are valid only until another instruction uses the same flag.

In the following example, when X1 is on, the constant Kbc614e hex will be loaded into the accumulator. When converted to BCD the number is ”12345678”. That number is stored in V1400 and V1401. After loading the constant K2 into the accumulator, we multiply it times 12345678, which is 24691356. DS Used HPP Used

DirectSOFT

1

X1

2

3

4

5

6

7

8

(Accumulator)

Load the hex equivalent of 12345678 decimal into the accumulator.

LDD Kbc614e

Convert the value to BCD format. It will occupy eight BCD digits (32 bits).

BCD

Output the number to V1400 and V1401 using the OUTD instruction.

OUTD V1400

V1400

V1401 1

2

3

4

5

6

7

8

2

4

6

9

1

3

5

6

2

4

6

9

1

3

5

6

2

X Acc.

(Accumulator)

Load the constant K2 into the accumulator.

LD K2

Multiply the accumulator contents (2) by the 8-digit number in V1400 and V1401.

MULD V1400

V1403

V1402

Move the result in the accumulator to V1402 and V1403 using the OUTD instruction.

OUTD V1402 Handheld Programmer Keystrokes $

B STR

1

SHFT

L ANDST

D

SHFT

B

C

ENT D

3 2

1

GX OUT

SHFT

D

SHFT

L ANDST

D

SHFT

M ORST

U

GX OUT

SHFT

D

3 D 3

B

B

E

A

A

4

1 PREV

3 L ANDST

C 2

D

C 2

1

0

SHFT

G

B

A

ENT

6

E 1

4

SHFT

E 4

ENT

B

E 1

E 1

0

A 4

ENT

ENT

3 B

3

SHFT

ENT

3

ISG

PREV

A 4

C 0

2

0

0

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

ENT

DL205 User Manual, 4th Edition, Rev. A

5–95

Page 318

Chapter 5: Standard RLL Instructions - Math

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

Multiply Real (MULR) Multiply Real instruction multiplies a real number in 230 The the accumulator with either a real constant or a real number 240 occupying two consecutive V-memory locations. The result 250-1 resides in the accumulator. Both numbers must be Real 260 data type (IEEE floating point format). Operand Data Type

DS Used HPP N/A

5–96

DL250-1 Range

DL260 Range aaa aaa

A V-memory Pointer

V All. (See page 3-55) All. (See page 3-56) P All V-memory (See page 3-55) All V-memory (See page 3-56) -3.402823E+038 to -3.402823E+038 to R + 3.402823E+038 + 3.402823E+038

Constant

Discrete Bit Flags SP63 SP70 SP71 SP72 SP73 SP74 SP75

MULR A aaa

Description On when the result of the instruction causes the value in the accumulator to be zero. On anytime the value in the accumulator is negative. On anytime the V-memory specified by a pointer (P) is not valid. On anytime the value in the accumulator is an invalid floating point number. On when a signed addition or subtraction results in an incorrect sign bit. On anytime a floating point math operation results in an underflow error. On when a real number instruction is executed and a non-real number was encountered.

NOTE: Status flags are valid only until another instruction uses the same flag.

DirectSOFT X1

LDR

4

0

E

0

0

0

0

0

R 7.0 Load the real number 7.0 into the accumulator. 4

0

E

0

0

0

0

0

(Accumulator)

x

1

5

X 4

1

7

0

0

0

0

0

(MULR)

1

0

5

Acc. 4

2

D

2

0

0

0

0

2

0

7

(decimal)

MULR R 15.0

V1401

Multiply the accumulator contents by the real number 15.0

4

2

D

V1400 0

0

0

(Hex number)

Real Value

OUTD

Acc.

8 4

2

1

8

4 2

1

8

4

2 1

8

4

2

1

8 4

2

1

8

4 2

1

8

4

2 1

8

4

2

1

0 1

0

0

0

0 1

0

1

1

0 1

0

0

1

0

0 0

0

0

0

0 0

0

0

0

0 0

0

0

0

0

V1400 Copy the result in the accumulator to V1400 and V1401.

Exponent (8 bits)

Sign Bit 128 + 4 + 1 = 133 133 - 127 = 6 Implies 2 (exp 6)

Mantissa (23 bits)

1.101001 x 2 (exp 6) = 1101001. binary= 105 decimal

NOTE: The current HPP does not support real number entry with automatic conversion to the 32-bit IEEE format. You must use DirectSOFT for this feature.

DL205 User Manual, 4th Edition, Rev. A

Page 319

Chapter 5: Standard RLL Instructions - Math

Divide (DIV) is a 16-bit instruction that divides the BCD value in 230 Divide the accumulator by a BCD value (Aaaa), which is either a 240 V-memory location or a 4-digit (max.) constant. The first 250-1 part of the quotient resides in the accumulator and the 260 remainder resides in the first stack location. Operand Data Type

DIV A aaa

DL230 Range

DL240 Range

DL250-1 Range

A aaa aaa aaa aaa

V-memory

V

All (See page 3 - 53)

Pointer

P

-

Constant

K

1-9999

All (See page 3 - 54) All V-memory (See page 3 - 54) 1-9999

All (See page 3 - 55) All V-memory (See page 3 - 55) 1-9999

All (See page 3 - 56) All V-memory (See page 3 - 56) 1-9999

Discrete Bit Flags

DL260 Range

Description

SP53 SP63 SP70 SP75

On when the value of the operand is larger than the accumulator can work with. On when the result of the instruction causes the value in the accumulator to be zero. On anytime the value in the accumulator is negative. On when a BCD instruction is executed and a NON-BCD number was encountered.

NOTE: The status flags are only valid until another instruction that uses the same flags is executed.

In the following example, when X1 is on, the value in V2000 will be loaded into the accumulator using the Load instruction. The value in the accumulator will be divided by the value in V2006 using the Divide instruction. The value in the accumulator is copied to V2010 using the Out instruction. DS Used HPP Used

DirectSOFT

V2000

X1

5

0

0

0

The unused accumulator bits are set to zero 0 0 0 0 5

0

0

0

(Accumulator)

5

0

(V2006)

0

0

0

LD V2000 Load the value in V2000 into the lower 16 bits of the accumulator DIV

÷ V2006 1

Acc.

The value in the accumulator is divided by the value in V2006

0

0

0

0

0

0

0

First stack location contains the remainder

1

OUT V2010

0

0

V2010

Copy the value in the lower 16 bits of the accumulator to V2010 Handheld Programmer Keystrokes $

B 1

STR SHFT

L ANDST

D

SHFT

D

I

GX OUT

3

ENT C

3 8 SHFT

A

V AND

A 0

2 V AND

C A 2

B 0

0 A

0

2 C

A 0

A

0 A

1

ENT G

0

6

ENT

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

ENT

DL205 User Manual, 4th Edition, Rev. A

5–97

Page 320

Chapter 5: Standard RLL Instructions - Math

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

Divide Double (DIVD) Divide Double is a 32-bit instruction that divides the BCD

230 value in the accumulator by a BCD value (Aaaa), which 240 must be obtained from two consecutive V-memory 250-1 locations. (You cannot use a constant as the parameter in 260 the box.) The first part of the quotient resides in the

DIVD A aaa accumulator and the remainder resides in the first stack location.

DS Used HPP Used

5–98

Operand Data Type V-memory Pointer

DL250-1 Range

DL260 Range

A aaa aaa

V P

All V-memory (See page 3 - 55) All V-memory (See page 3 - 55)

All V-memory (See page 3 - 56) All V-memory (See page 3 - 56)

Discrete Bit Flags

Description

SP53 SP63 SP70 SP75

On when the value of the operand is larger than the accumulator can work with. On when the result of the instruction causes the value in the accumulator to be zero. On anytime the value in the accumulator is negative. On when a BCD instruction is executed and a NON-BCD number was encountered.

NOTE: Status flags are valid only until another instruction uses the same flag.

In the following example, when X1 is on, the value in V1400 and V1401 will be loaded into the accumulator using the Load Double instruction. The value in the accumulator is divided by the value in V1420 and V1421 using the Divide Double instruction. The first part of the quotient resides in the accumulator and the remainder resides in the first stack location. The value in the accumulator is copied to V1500 and V1501 using the Out Double instruction. DirectSOFT V1401 X1

0

LDD

1

5

V1400 0

0

0

0

0

V1400 The unused accumulator bits are set to zero

Load the value in V1400 and V1401 into the accumulator

0

1

5

0

0

0

0

0

(Accumulator)

÷

0

0

0

0

0

0

5

0

(V1421 and V1420)

Acc.

0

0

0

3

0

0

0

0

DIVD V1420 The value in the accumulator is divided by the value in V1420 and V1421

0

V1500

0

0

3

0

V1501

Copy the value in the accumulator to V1500 and V1501

B 1

SHFT

L ANDST

D

SHFT

D

I

GX OUT

SHFT

3

ENT B

D 3

3

8

V AND

D

B

DL205 User Manual, 4th Edition, Rev. A

4 0

0 A

2 A

A 5

A 0

C

E

F 1

A 4

1 B

3

E 1

0

0 ENT

0

0

V1500

Handheld Programmer Keystrokes STR

0

0

0

0

0

0

0

First stack location contains the remainder

OUTD

$

0

ENT ENT

0

Page 321

Chapter 5: Standard RLL Instructions - Math

Divide Real (DIVR) Divide Real instruction divides a real number in the 230 The accumulator by either a real constant or a real number 240 occupying two consecutive V-memory locations. The result 250-1 resides in the accumulator. Both numbers must conform to 260 the IEEE floating point format. Operand Data Type

DS Used HPP N/A

DIVR A aaa

DL250-1 Range

DL260 Range

A aaa aaa

V-memory Pointer

V P

Constant

R

All (See page 3 - 55) All V mem (See page 3 - 55) -3.402823E + 038 to + 3.402823E+038

All (See page 3 - 56) All V mem (See page 3 - 56) -3.402823E + 038 to + 3.402823E+038

Discrete Bit Flags SP63 SP70 SP71 SP72 SP73 SP74 SP75

Description On when the result of the instruction causes the value in the accumulator to be zero. On anytime the value in the accumulator is negative. On anytime the V-memory specified by a pointer (P) is not valid. On anytime the value in the accumulator is a valid floating point number. On when a signed addition or subtraction results in a incorrect sign bit. On anytime a floating point math operation results in an underflow error. On when a real number instruction is executed and a non-real number was encountered.

NOTE: Status flags are valid only until another instruction uses the same flag. DirectSOFT LDR

4

1

7

0

0

0

0

0

R15.0 Load the real number 15.0 into the accumulator. 1

5

4

1

7

0

0

0

0

0

(Accumulator)

÷ 1

0

÷ 4

1

2

0

0

0

0

0

(DIVR )

1 . 5

Acc. 3

F

C

0

0

0

0

0

0

0

(decimal)

DIVR R10.0

V1401

Divide the accumulator contents by the real number 10.0.

3

F

C

V1400 0

0

0

(Hex number)

Real Value

OUTD

Acc.

8 4

2

1

8

4 2

1

8

4

2 1

8

4

2

1

8 4

2

1

8

4 2

1

8

4

2 1

8

4

2

1

0 0

1

1

1

1 1

1

1

1

0 0

0

0

0

0

0 0

0

0

0

0 0

0

0

0

0 0

0

0

0

0

V1400 Copy the result in the accumulator to V1400 and V1401.

Sign Bit

Exponent (8 bits)

64 + 32 + 16 + 8 + 4 + 2 + 1 = 127 127 - 127 = 0 Implies 2 (exp 0)

Mantissa (23 bits)

1.1 x 2 (exp 0) = 1.1 binary= 1.5 decimal ndard RLL

X1

NOTE: The current HPP does not support real number entry with automatic conversion to the 32-bit IEEE format. You must use DirectSOFT for this feature.

DL205 User Manual, 4th Edition, Rev. A

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

5–99

Page 322

Chapter 5: Standard RLL Instructions - Math

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

Increment (INC) Increment instruction increments a BCD value in a 230 The specified V-memory location by “1” each time the instruction 240 is executed. 250-1 260

INC A aaa

Decrement (DEC) DEC

Decrement instruction decrements a BCD value in a 230 The specified V-memory location by “1” each time the instruction 240 is executed. 250-1 260 Operand Data Type

DS Used HPP Used

5–100

A aaa

DL250-1 Range

V-memory Pointer

DL260 Range

A aaa aaa

V P

All V mem (See page 3 - 55) All V mem (See page 3 - 55)

All V mem (See page 3 - 56) All V mem (See page 3 - 56)

Discrete Bit Flags

Description

SP63 SP75

On when the result of the instruction causes the value in the accumulator to be zero. On when a BCD instruction is executed and a NON-BCD number was encountered.

NOTE: Status flags are valid only until another instruction uses the same flag.

In the following increment example, the value in V1400 increases by one each time that C5 is closed (true). DirectSOFT

V1400

C5

8

9

8

9

3

5

INC V1400 Increment the value in V1400 by “1”.

V1400 3

6

Handheld Programmer Keystrokes $ STR SHFT

SHFT

P CV

D

I

N TMR

C

8

3

NEXT

NEXT

NEXT

NEXT

F

B

E

A

A

ENT

2

1

4

0

0

5

ENT

In the following decrement example, the value in V1400 is decreased by one each time that C5 is closed (true). DirectSOFT

V1400

C5

DEC

8

9

8

9

3

5

V1400 Decrement the value in V1400 by “1”. V1400 3

4

Handheld Programmer Keystrokes $ STR SHFT

SHFT

P CV

D

D

E

C

3

4

3 2

NEXT

NEXT

NEXT

NEXT

F

B

E

A

A

ENT

1

4

0

0

5

ENT

NOTE: Use a pulsed contact closure to INC/DEC the value in V–memory once per closure.