Chapter 5: Standard RLL Instructions - Logical

Exclusive Or Formatted (XORF) The Exclusive Or Formatted instruction performs an exclusive OR

230 of the binary value in the accumulator and a specified range of 240 discrete memory bits (1 to 32). 250-1 The instruction requires a starting location (Aaaa) and the number 260 of bits (Kbbb) to be exclusive ORed. Discrete status flags indicate if DS Used HPP Used

XORF

A aaa

K bbb the result of the Exclusive Or Formatted is zero or negative (the most significant bit is on). Operand Data Type Inputs Outputs Control Relays Stage bits Timer bits Counter bits Special Relays Global I/O Constant

DL250-1 Range

DL260 Range

A aaa bbb aaa bbb

X Y C S T CT SP GX/GY K

0–777 0–777 0–1777 0–1777 0–377 0–177 0-777 -

– – – – – – – – 1–32

0–1777 0–1777 0–3777 0–1777 0–377 0–377 0–777 0-3777 -

– – – – – – – – 1–32

Discrete Bit Flags

Description

SP63 SP70

Will be on if the result in the accumulator is zero Will be on if the result in the accumulator is negative

NOTE: Status flags are valid only until another instruction uses the same flag.

In the following example, when X1 is on, the binary pattern of C10–C13 (4 bits) will be loaded into the accumulator using the Load Formatted instruction. The value in the accumulator will be logically Exclusive Ored with the bit pattern from Y20–Y23 using the Exclusive Or Formatted instruction. The value in the lower 4 bits of the accumulator are output to C20–C23 using the Out Formatted instruction. DirectSOFT X1

LDF

C10

Location

Constant

C13 C12 C11 C10

C10

K4

OFF ON

ON OFF

K4 Load the status of 4 consecutive bits (C10-C13) into the accumulator X0RF

The unused accumulator bits are set to zero

Y20 K4

31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 15 14 13 12 11 10 9

8

7 6 5

4 3

2

1

0

0

0

0 0

0

0

1 1

0

0

0

0 0

0

0

0

0

0 0

0 0

0

0

0

0

0

0 0

0 0

0

0

0

0

0

0

Acc.

0

0

0 0

0

0

0 0

0

0

0

0 0

0

0

0

0 0

1

1

0

1

0

0

0

0 0

0

0

0

0 0

0

0

0

0 1

1

1

0

Accumulator

Exclusive OR the binary bit pattern (Y20-Y23) with the value in the accumulator

Acc.

0

0 0

0

0

0

0

Y23 Y22 Y21 Y20 XORF (Y20-Y23) ON OFF OFF OFF

OUTF

0

C20 K4

Copy the specified number of bits from the accumulator to C20-C23

Handheld Programmer Keystrokes $

B 1

STR SHFT

L ANDST

D

SHFT

X SET

Q

GX OUT

SHFT

F

OR 5

Constant

C23 C22 C21 C20

K4

ON ON ON OFF

ENT F

3

Location C20

NEXT

5 SHFT

F 5 PREV

PREV

NEXT

NEXT

NEXT

NEXT

C

A

C

A 2

2

B

A E

0

4 E

0

E 0

1

4

4

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

ENT

ENT

ENT

DL205 User Manual, 4th Edition, Rev. A

5–81

Page 304

Chapter 5: Standard RLL Instructions - Logical

1 2

3 4 5 6 7 8 9 10 11 12 13 14 A B C D

Exclusive Or with Stack (XORS) The Exclusive Or with Stack instruction is a 32-bit instruction that performs an Exclusive Or of the value in the accumulator with the first level of the accumulator stack. The result resides in the accumulator. The value in the first level of the accumulator stack is removed from the stack and all values are moved up one level. Discrete status flags indicate if the result of the Exclusive Or with Stack is zero or a negative number (the most significant bit is on).

230 240 250-1 260

DS Used HPP Used

Discrete Bit Flags

XO R S

Description

SP63 SP70

Will be on if the result in the accumulator is zero Will be on if the result in the accumulator is negative

NOTE: Status flags are valid only until another instruction uses the same flag.

In the following example when X1 is on, the binary value in the accumulator will be Exclusive ORed with the binary value in the first level of the accumulator stack. The result will reside in the accumulator.

DirectSOFT V1401

LDD

X1

5

V1400

4

7

V1400 E

2

8

7

A

Load the value in V1400 and V1401 into the accumulator 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 15 14 13 12 11 10 9

8 7

6 5

4 3

Acc.

0

1

0 1

0

1

0

0 0

1

1

1

1 1

1

0

0 0

1

1

Acc.

0

0

1 0

1

0

0

1

2

1

0

1 0

1

0

XORS

Exclusive OR the value in the accumulator with the value in the first level of the accumulator stack OUTD

0

1

0 1

0

1

0

0 0

1

1

1

1 1

1

0

0

0

1 0

1

0

0

0 0

1

1

1

1 0

1

0

36476A38 XOR (1st level of Stack) 0

0

1 1

0

1

1

0 0

1

0

0

0 1

1

1

0

1

1 0

1

0

1

0 0

0

1

1

1 0

0

0

0

1 0

1 0 0

0

0 1

1 0

0 0

0

1 0

1 0

1 0 0

0

1 0

0

1

0 0

0

0

1

0 0

1

0

0

0 0

1

0

2

9

2

2

Acc.

V1500 6

Copy the value in the accumulator to V1500 and V1501

Handheld Programmer Keystrokes $

B 1

STR

SHFT

L ANDST

D

SHFT

X SET

Q

GX OUT

SHFT

D

5–82

ENT D

3 OR 3

B 3

SHFT

E

ENT

B

F 1

A 4

1 S RST

A 5

3

V1501

A 0

A 0

0

0

ENT

ENT

DL205 User Manual, 4th Edition, Rev. A

4

4

V1500

Page 305

Chapter 5: Standard RLL Instructions - Logical

Compare (CMP)

1 2 3 Operand Data Type DL230 Range DL240 Range DL250-1 Range DL260 Range A aaa aaa aaa aaa 4 5 Discrete Bit Flags Description 6 7 NOTE: The status flags are only valid until another instruction that uses the same flags is executed. 8 In the following example when X1 is on, the constant 4526 will be loaded into the lower 16 bits of the accumulator using the Load instruction. The value in the accumulator is compared 9 with the value in V2000 using the Compare instruction. The corresponding discrete status flag will be turned on indicating the result of the comparison. In this example, if the value in 10 the accumulator is less than the value specified in the Compare instruction, SP60 will turn on, energizing contact C30. 11 12 13 14 A B C D The compare instruction is a 16-bit instruction that

230 compares the value in the lower 16 bits of the 240 accumulator with the value in a specified V-memory 250-1 location (Aaaa). The corresponding status flag will be 260 turned on indicating the result of the comparison. DS Used HPP Used

V-memory

All V See memory map

Pointer

P

SP60 SP61 SP62

-

CMP

A aaa

All See memory map All V-memory. See memory map

All See memory map All V-memory. See memory map

All See memory map All V-memory. See memory map

On when the value in the accumulator is less than the instruction value. On when the value in the accumulator is equal to the instruction value. On when the value in the accumulator is greater than the instruction value.

DirectSOFT X1

CONSTANT

LD

4

K4526

Load the constant value 4526 into the lower 16 bits of the accumulator

5

? 2

6

The unused accumulator bits are set to zero Acc. 0

0

0

0

44 55 2? 2 66

Compared with

CMP

V2000

8

Compare the value in the accumulator with the value in V2000

SP60

9

4

5

V2000

C30

OUT

Handheld Programmer Keystrokes $

B

STR

1

SHFT

L ANDST

SHFT

C

$

STR GX OUT

2

ENT

D

SHFT

3

SHFT

M ORST

P

SHFT

SP STRN

G

SHFT

C

D 2

K JMP

E

F

4

C

CV

2

A

6

0 A

3

0

C

5

A

G

2

A

0

6

A

0

0

ENT ENT

ENT ENT

DL205 User Manual, 4th Edition, Rev. A

5–83

Page 306

Chapter 5: Standard RLL Instructions - Logical

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

Compare Double (CMPD) Compare Double instruction is a 32–bit instruction that 230 The compares the value in the accumulator with the value (Aaaa), 240 which is either two consecutive V-memory locations or an 8–digit 250-1 (max.) constant. The corresponding status flag will be turned on 260 indicating the result of the comparison. DS Used HPP Used

Operand Data Type

DL240 Range DL250-1 Range DL260 Range aaa

All V See memory map

V-memory Pointer

P

-

Constant

K

0-FFFFFFFF aaa aaa aaa

All See memory map All V-memory. See memory map 0-FFFFFFFF

All See memory map All V-memory. See memory map 0-FFFFFFFF

All See memory map All V-memory. See memory map 0-FFFFFFFF

Discrete Bit Flags

Description

SP60 SP61 SP62

On when the value in the accumulator is less than the instruction value. On when the value in the accumulator is equal to the instruction value. On when the value in the accumulator is greater than the instruction value.

NOTE: The status flags are only valid until another instruction that uses the same flags is executed.

In the following example when X1 is on, the value in V2000 and V2001 will be loaded into the accumulator using the Load Double instruction. The value in the accumulator is compared with the value in V2010 and V2011 using the CMPD instruction. The corresponding discrete status flag will be turned on indicating the result of the comparison. In this example, if the value in the accumulator is less than the value specified in the Compare instruction, SP60 will turn on, energizing contact C30. DirectSOFT X1

V2000

V2001

LDD

4

5

2

6

7

2

9

9

Acc. 4

5

? 2

6

77 72

9

9

2

6

V2000 Load the value in V2000 and V2001 into the accumulator

Compared with

CMPD V2010 6

Compare the value in the accumulator with the value in V2010 and V2011 SP60

7

3

9

5

V2011

0

V2010

C30

OUT

Handheld Programmer Keystrokes $

B STR

1

ENT

SHFT

L ANDST

D 3

3

SHFT

C

SHFT

M ORST

P

SHFT

SP STRN

G

SHFT

C

D

$ STR GX OUT

5–84

DL230 Range A

CMPD A aaa

2

D

C

2

A 2

A 0

D CV

C

0 A

3

0

0 A

2

3 A

6

A 0

ENT ENT

DL205 User Manual, 4th Edition, Rev. A

ENT B

0

A 1

0

ENT

Page 307

Chapter 5: Standard RLL Instructions - Logical

Compare Formatted (CMPF)

1 2 result of the comparison. 3 Operand Data Type DL250-1 Range DL260 Range A aaa bbb aaa bbb 4 5 6 7 8 Discrete Bit Flags Description 9 10 NOTE: Status flags are valid only until another instruction uses the same flag. 11 In the following example, when X1 is on the Load Formatted instruction loads the binary value (6) from C10–C13 into the accumulator. The CMPF instruction compares the value in the accumulator to the value in Y20–Y23 (E hex). The corresponding discrete status flag will 12 be turned on indicating the result of the comparison. In this example, if the value in the accumulator is less than the value specified in the Compare instruction, SP60 will turn on, 13 energizing C30. 14 A B C D

Compare Formatted compares the value in the 230 The accumulator with a specified number of discrete locations 240 (1–32). The instruction requires a starting location (Aaaa) 250-1 and the number of bits (Kbbb) to be compared. The 260 corresponding status flag will be turned on indicating the DS Used HPP Used

Inputs Outputs Control Relays Stage bits Timer bits Counter bits Special Relays Global I/O Constant

X Y C S T CT SP GX/GY K

SP60 SP61 SP62

DirectSOFT X1

A aaa

K bbb

– – – – – – – – 1–32

0–1777 0–1777 0–3777 0–1777 0–377 0–377 0–777 0-3777 -

– – – – – – – – 1–32

On when the value in the accumulator is less than the instruction value. On when the value in the accumulator is equal to the instruction value. On when the value in the accumulator is greater than the instruction value.

LDF

C10

K4

CMPF

Y20

K4

SP60

0–777 0–777 0–1777 0–1777 0–377 0–177 0-777 -

CMPF

Load the value of the specified discrete locations (C10- C13) into the accumulator Compare the value in the accumulator with the value of the specified discrete location (Y20- Y23)

Constant K4

C13 C12 C11 C10

OFF ON ON OFF

The unused accumulator bits are set to zero

Acc.

C30

Y23 Y22 Y21 Y20

OUT

Location

C10

0

0

0

0

0

0

0

6

Compared with

ON ON ON OFF

E

DL205 User Manual, 4th Edition, Rev. A

5–85

Page 308

Chapter 5: Standard RLL Instructions - Logical

1

2

3 4 5 6 7 8 9 10 11 12 13 14 A B C D

Compare with Stack (CMPS) The Compare with Stack instruction is a 32-bit instruction that compares the value in the accumulator with the value in the first level of the accumulator stack. The corresponding status flag will be turned on indicating the result of the comparison. This does not affect the value in the accumulator.

230 240 250-1 260

DS Used HPP Used

Discrete Bit Flags

Description

SP60 SP61 SP62

On when the value in the accumulator is less than the instruction value. On when the value in the accumulator is equal to the instruction value. On when the value in the accumulator is greater than the instruction value.

NOTE: Status flags are valid only until another instruction uses the same flag.

In the following example when X1 is on, the value in V1400 and V1401 is loaded into the accumulator using the Load Double instruction. The value in V1410 and V1411 is loaded into the accumulator using the Load Double instruction. The value that was loaded into the accumulator from V1400 and V1401 is placed on top of the stack when the second Load instruction is executed. The value in the accumulator is compared with the value in the first level of the accumulator stack using the CMPS instruction. The corresponding discrete status flag will be turned on indicating the result of the comparison. In this example, if the value in the accumulator is less than the value in the stack, SP60 will turn on, energizing C30. DirectSOFT

V1400

V1401

X1

Load the value in V1400 and V1401 into the accumulator

LDD

6

5

0

0

3

5

4

4

6

5

0

0

3

5

4

4

V1400 Load the value in V1410 and V1411 into the accumulator

LDD

Acc.

V1410 Compare the value in the accumulator with the value in the first level of the accumulator stack

CMPS

SP60

C30

B STR

1

SHFT

L ANDST

D

SHFT

L ANDST

D

SHFT

C

$ GX OUT

2

ENT D

3

B 3

E

D

B 3

SHFT

M ORST

P

SHFT

SP STRN

G

C

D 2

CV

E 4

S RST

ENT

A

ENT

0 A 0

A 0

B

1

6 3

A 4

1

3

SHFT

5

5

0

0

3

5

4

4

Acc. 5

5

0

0

3

5

4

4

Compared with Top of Stack

Handheld Programmer Keystrokes $

V1410

V1411

OUT

STR

5–86

C MP S

ENT

DL205 User Manual, 4th Edition, Rev. A

0 A

1

0

ENT ENT

Page 309

Chapter 5: Standard RLL Instructions - Logical

Compare Real Number (CMPR) Compare Real Number instruction 230 The compares a real number value in the 240 accumulator with two consecutive V-memory 250-1 locations containing a real number. The 260 corresponding status flag will be turned on DS Used HPP N/A

CMPR A aaa indicating the result of the comparison. Both numbers being compared are 32 bits long. Operand Data Type

DL250-1 Range

DL260 Range

A aaa aaa

V-memory

V

Pointer

P

Constant

R

All. See memory map All V-memory. See memory map -3.402823E+038 to + 3.402823E+038

All. See memory map All V-memory. See memory map -3.402823E+038 to + 3.402823E+038

Discrete Bit Flags SP60 SP61 SP62 SP71 SP75

Description On when the value in the accumulator is less than the instruction value. On when the value in the accumulator is equal to the instruction value. On when the value in the accumulator is greater than the instruction value. On anytime the V-memory specified by a pointer (P) is not valid On when a real number instruction is executed and a non-real number encountered.

NOTE: Status flags are valid only until another instruction uses the same flag.

In the following example when X1 is on, the LDR instruction loads the real number representation for 7 decimal into the accumulator. The CMPR instruction compares the accumulator contents with the real representation for decimal 6. Since 7 > 6, the corresponding discrete status flag is turned on (special relay SP62). DirectSOFT X1

LDR R7.0

CMPR R6.0

SP62

Load the real number representation for decimal 7 into the accumulator Compare the value with the real number representation for decimal 6

Acc.

4

0

E

0

0

0

0

0

CMPR

4

0

D

0

0

0

0

0

C1

OUT

DL205 User Manual, 4th Edition, Rev. A

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

5–87

Page 310

Chapter 5: Standard RLL Instructions - Math

Math Instructions

1 Add (ADD) is a 16-bit instruction that adds a BCD value in the 2 Add accumulator with a BCD value in a V-memory location (Aaaa). (You cannot use a constant (K) as the BCD value in 3 the box.) The result resides in the accumulator.

Operand Data Type DL230 Range DL240 Range DL250-1 Range DL260 Range 4 A aaa aaa aaa aaa 5 6 Discrete Bit Flags Description 7 8 9 NOTE: The status flags are only valid until another instruction that uses the same flags is executed. In the following example, when X1 is on, the value in V2000 will be loaded into the 10 accumulator using the Load instruction. The value in the lower 16 bits of the accumulator are added to the value in V2006 using the Add instruction. The value in the accumulator is 11 copied to V2010 using the Out instruction. 12 13 14 A B C D ADD

230

A aaa

240

250-1 260

DS Used HPP Used

V-memory

All V See memory map

Pointer

P

SP63 SP66 SP67 SP70 SP75

All See memory map All V-memory. See memory map

-

All See memory map All V-memory. See memory map

On when the result of the instruction causes the value in the accumulator to be zero On when the 16 bit addition instruction results in a carry On when the 32 bit addition instruction results in a carry On anytime the value in the accumulator is negative On when a BCD instruction is executed and a NON-BCD number is encountered

DirectSOFT

V2000

X1

4

LD

9

3

5

V2000

Load the value in V2000 into the lower 16 bits of the accumulator

The unused accumulator bits are set to zero 0 0 0 0 4

ADD

+

V2006

Acc.

Add the value in the lower 16 bits of the accumulator with the value in V2006

9

3

5

(Accumulator)

2

5

0

0

(V2006)

7

4

3

5

7

4

3

5

OUT

V2010

Copy the value in the lower 16 bits of the accumulator to V2010 Handheld Programmer Keystrokes $

B

STR

1

SHFT

L ANDST

D

SHFT

A

D

GX OUT

5–88

All See memory map All V-memory. See memory map

0

V2010

ENT

C

A

2

3

D

A

0

C

3

3

SHFT

V AND

2

C

A 2

A

0

A

0

B 0

DL205 User Manual, 4th Edition, Rev. A

0

A

0

A 1

ENT

G

0

6

ENT

ENT

Page 311

Chapter 5: Standard RLL Instructions - Math

Add Double (ADDD)

230 240 250-1 260 DS Used HPP Used

Add Double is a 32-bit instruction that adds the BCD value in the accumulator with a BCD value (Aaaa), which is either two consecutive V-memory locations or an 8–digit (max.) BCD constant. The result resides in the accumulator. Operand Data Type

ADDD A aaa

DL230 Range DL240 Range DL250-1 Range DL260 Range A aaa aaa aaa aaa

V-memory

V

All See memory map

Pointer

P

-

All See memory map All V-memory. See memory map

All See memory map All V-memory. See memory map

All See memory map All V-memory. See memory map

Constant

K

0-99999999

0-99999999

0-99999999

0-99999999

Discrete Bit Flags SP63 SP66 SP67 SP70 SP75

Description On when the result of the instruction causes the value in the accumulator to be zero On when the 16 bit addition instruction results in a carry On when the 32 bit addition instruction results in a carry On anytime the value in the accumulator is negative On when a BCD instruction is executed and a NON-BCD number is encountered

NOTE: The status flags are only valid until another instruction that uses the same flags is executed.

In the following example, when X1 is on, the value in V2000 and V2001 will be loaded into the accumulator using the Load Double instruction. The value in the accumulator is added with the value in V2006 and V2007 using the Add Double instruction. The value in the accumulator is copied to V2010 and V2011 using the Out Double instruction. DirectSOFT X1

V2001 LDD

V2000

6

7

3

9

5

0

2

6

V2000 Load the value in V2000 and V2001 into the accumulator ADDD V2006

6

7

3

9

5

0

2

6

(Accumulator)

+ 2

0

0

0

4

0

4

6

(V2006 and V2007)

Acc. 8

7

3

9

9

0

7

2

8

7

3

9

9

0

7

2

Add the value in the accumulator with the value in V2006 and V2007 OUTD V2010

V2011

Copy the value in the accumulator to V2010 and V2011

V2010

Handheld Programmer Keystrokes $

B 1

STR SHFT

L ANDST

D

SHFT

A

D

GX OUT

C 3

3

0 SHFT

ENT D D

3 D 3

A 2

D 3

A 0

C

SHFT

A 2

3 V AND

A 0

C

0 A

2

0 A

6

0 B

0

ENT G A

1

0

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

ENT ENT

DL205 User Manual, 4th Edition, Rev. A

5–89

Page 312

Chapter 5: Standard RLL Instructions - Math

Add Real (ADDR)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

230 240 250-1 260

Add Real is a 32-bit instruction that adds a real number, which is either two consecutive V-memory locations or a 32-bit constant, to a real number in the accumulator. Both numbers must conform to the IEEE floating point format. The result is a 32-bit real number that resides in the accumulator. Operand Data Type

DS Used HPP N/A

5–90

ADDR A aaa

DL250-1 Range

DL260 Range

A aaa aaa

V-memory

V

Pointer

P

Constant

R

All. See memory map All V-memory. See memory map -3.402823E+038 to + 3.402823E+038

All. See memory map All V-memory. See memory map -3.402823E+038 to + 3.402823E+038

Discrete Bit Flags Description SP63 SP70 SP71 SP72 SP73 SP74 SP75

On when the result of the instruction causes the value in the accumulator to be zero. On anytime the value in the accumulator is negative. On anytime the V-memory specified by a pointer (P) is not valid. On anytime the value in the accumulator is an invalid floating point number. On when a signed addition or subtraction results in a incorrect sign bit. On anytime a floating point math operation results in an underflow error. On when a real number instruction is executed and a non-real number was encountered.

NOTE: Status flags are valid only until another instruction uses the same flag. DirectSOFT X1

LDR

4

0

E

0

0

0

0

0

R7.0 Load the real number 7.0 into the accumulator 4

0

E

0

0

0

0

0

(Accumulator)

1

5

+ 4

1

7

0

0

0

0

0

(ADDR)

2

2

Acc. 4

1

B

0

0

0

0

0

0

0

7 +

(decimal)

ADDR R15.0

V1401

Add the real number 15.0 to the accumulator contents, which is in real number format.

4

1

B

V1400 0

0

0

(Hex number)

Real Value

OUTD

Acc.

8 4

2

1

8

4 2

1

8

4

2 1

8

4

2

1

8 4

2

1

8

4 2

1

8

4

2 1

8

4

2

1

0 1

0

0

0

0 0

1

1

0

1 1

0

0

0

0

0 0

0

0

0

0 0

0

0

0

0 0

0

0

0

0

V1400 Copy the result in the accumulator to V1400 and V1401.

Exponent (8 bits)

Sign Bit

128 + 2 + 1 = 131 131 - 127 = 4 Implies 2 (exp 4)

Mantissa (23 bits)

1.011 x 2 (exp 4) = 10110. binary= 22 decimal

NOTE1: The current HPP does not support real number entry with automatic conversion to the 32-bit IEEE format. You must use DirectSOFT for this feature. NOTE2: If the value being added to a real number is 16,777,216 times smaller than the real number, the calculation will not work.