Chapter 5: Standard RLL Instructions - Table
AND Move (ANDMOV)
1 2 ORMOV 3 Vaaa OR Move (ORMOV) The Or Move instruction copies data from a table to the 4 specified memory location, ORing each word with the XORMOV accumulator contents as it is written. 5 Vaaa Exclusive OR Move (XORMOV) The Exclusive OR Move instruction copies data from a table to 6 the specified memory location, XORing each word with the accululator value as it is written.
The following description applies to the AND Move, OR Move, and Exclusive OR Move
7 instructions. A table is just a range of V-memory locations. These instructions copy the data of a table to another specified location, preforming a logical operation on each word with the accumulator contents as the new table is written. 8 Step 1: Load the length of the table (number of V-memory locations) into the first level of the accumulator stack. This parameter must be a HEX value, 0 to FF. 9 Step 2: Load the starting V-memory location for the table into the accumulator. This parameter must be a HEX value. You can use the LDA instruction to convert an octal address to hex. 10 Step 3: Load the BCD/hex bit pattern into the accumulator which will be logically combined with the table contents as they are copied. 11 Step 4: Insert the AND Move, OR Move, or XOR Move instruction. This specifies the starting location of the copy of the original table. This new table will automatically be the same length as the original table. 12 Operand Data Type DL260 Range 13 aaa 14 The example table to the right contains BCD data as shown (for demonstration purposes). Suppose we want to A move a table of two words at V3000 and AND it with K6666. The copy of the table at V3100 shows the result B of the AND operation for each word. The program on the next page performs the ANDMOV operation example above. It assumes that the data in the table at V3000 – V3001 already exists. First we load the table length (two C words) into the accumulator. Next we load the starting addrss of the source table, using the LDA instruction. Then we load the data into the accumulator to be ANDed with the table. D In the ANDMOV command, we specify the table destination, V3100. 230 240 250-1 260
ANDMOV Vaaa
The AND Move instruction copies data from a table to the specified memory location, ANDing each word with the accumulator data as it is written.
230 240
250-1 260
DS Used HPP Used
V-memory
V
All (See page 3 - 56) V 3000
3 3 3 3
ANDMOV K 6666
F F F F
DL205 User Manual, 4th Edition, Rev. A
V 3100
2 2 2 2 6 6 6 6
5–171
Page 394
Chapter 5: Standard RLL Instructions - Table DirectSOFT
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 5–172
Handheld Programmer Keystrokes $ STR
A 0
SHFT
L D ANDST 3
SHFT
L D 3 ANDST
SHFT
L D 3 ANDST
V AND
SHFT
M ORST
X0
LD
ENT
K2 PREV
A
C 2 D
0 PREV O INST#
A
A 0
3 G
G
A G 6
6 D
0
0 G
6
V AND
Load the constant value 2 (Hex.) into the lower 16 bits of the accumulator.
ENT
B 3
6 A
1
ENT
LDA ENT A
0
0
0 3000 Convert otal 3000 to HEX and load the value into the accumulator. This is the table beginning.
ENT
The example to the right shows a table of two words at V3000 and logically ORs it with K8888. The copy of the table at V3100 shows the result of the OR operation for each word. The program to the right performs the ORMOV example above. It assumes that the data in the table at V3000 – V3001 already exists. First we load the table length (two words) into the accumulator. Next we load the starting address of the source table, using the LDA instruction. Then we load the data into the accumulator to be ORed with the table. V 3000 In the ORMOV command, we specify the table 1 1 1 1 destination, V3100.
LD K6666 Load the constant value 6666 (Hex.) into the lower 16 bits of the accumulator. ANDMOV 0 3100 Copy the table to V3100, ANDing its contents with the accumulator as it is written.
V 3100
OR MOV K 8888
9 9 9 9
1 1 1 1 DirectSOFT 32
Handheld Programmer Keystrokes
X0
A
$ STR
0
SHFT
L D ANDST 3
SHFT
L D ANDST 3
SHFT
L D ANDST 3
Q
SHFT
OR
M ORST
9 9 9 9
ENT
LD K2
PREV A
C D
0
A 3
PREV O INST#
ENT
2
V AND
I
A 0
I 8
A 0
I 8
D
8 B
3
0 I 8 A
1
ENT
LDA
ENT
0 3000 A
0
Load the constant value 2 (Hex) into the lower 16 bits of the accumulator.
0
ENT
Convert octal 3000 to HEX and load the value into the accumulator. This is the table beginning.
The example to the right shows a table of two words at V3000 and logicall XORs it with K3333. The copy of the table at V3100 shows the result of the XOR operation for each word. The ladder program example for the XORMOV is similar to the one above for the ORMOV. Just use the XORMOV instruction. On the handheld programmer, you must use the SHFT key and spell “XORMOV” explicitly. V 3000 1 1 1 1 1 1 1 1
DL205 User Manual, 4th Edition, Rev. A
LD K8888 Load the constant value 8888 (Hex.) into the lower 16 bits of the accumulator. ORMOV 0 3100 Copy the table to V3100, ORing its contents with the accumulator as it is written.
X OR MOV K 3333
V 3100 2 2 2 2 2 2 2 2
Page 395
Chapter 5: Standard RLL Instructions - Table
Find Block (FINDB)
1 2 stored in the accumulator. If the block is not found, flag SP53 3 will be set. 4 Operand Data Type DL260 Range A aaa 5 6 Discrete Bit Flags Description 7 The below steps are necessary to program the Find Block function. 8 Step 1: Load the number of bytes in the block to be located. This parameter must be a decimal value from 1 to 256. Step 2: Load the length of a table (number of words) to be searched. The Find Block will search 9 multiple tables that are adjacent in V-memory. This parameter must be a decimal value from 1 to 128. 10 Step 3: Load the ending location for all the tables into the accumulator. This parameter must be a HEX value. You can use the LDA instruction to convert an octal address to hex. Step 4: Load the table starting location for all the tables into the accumulator. This parameter must be 11 a HEX value. You can use the LDA instruction to convert an octal address to hex. Step 5: Insert the Find Block instruction. This specifies the starting location of the block of data you 12 are trying to locate. 13 14 A B C D
Find Block instruction searches for an occurrence of a 230 The specified block of values in a V-memory table. The function 240 parameters are loaded into the first and second levels of the 250-1 accumulator stack and the accumulator by three additional 260 instructions. If the block is found, its starting address will be
FINDB Aaaa
DS Used HPP N/A
V-memory V-memory
SP53
V P
All (See page 3 - 56) All (See page 3 - 56)
On when the Find Block instruction was executed but did not find the block of data in table specified.
Start Addr. V2000 V2017 V2020 V2037 V2040 V2057
Sample Program of FINDB
X1
Table 1
16 words
Table 2
16 words
Start Addr.
Table 3
16 words
V3000
LD
LD
K16
Block
32 bytes
LDA O2777
V3017
V2760 V2777
Table 32
K32
LDA O2000
16 words
FINDB V3000
End Addr.
END
DL205 User Manual, 4th Edition, Rev. A
5–173
Page 396
Chapter 5: Standard RLL Instructions - Table
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
Swap (SWAP)
230 240 250-1 260 DS Used HPP Used
5–174
The Swap instruction exchanges the data in two tables of equal length.
SWAP V aaa
The following description applies to both the Set Bit and Reset Bit table instructions. Step 1: Load the length of the tables (number of V-memory locations) into the first level of the accumulator stack. This parameter must be a HEX value, 0 to FF. Remember that the tables must be of equal length. Step 2: Load the starting V-memory location for the first table into the accumulator. This parameter must be a HEX value. You can use the LDA instruction to convert an octal address to hex. Step 3: Insert the Swap instruction. This specifies the starting address of the second table.
Helpful hint:, The data swap occurs within a single scan. If the instruction executes on multiple consecutive scans, it will be difficult to know the actual contents of either table at any particular time. So, remember to swap just on a single scan. Operand Data Type
DL260 Range
V-memory
All (See page 3 - 56)
aaa V
The example to the right shows a table of two words at V3000. We will swap its contents with another table of two words at V3100 by using the Swap instruction.
V 3000
V 3100
1 2 3 4
A B C D
S WAP
5 6 7 8
0 0 0 0
The example program below uses a PD contact (triggers for one scan for off-to-on transition). First, we load the length of the tables (two words) into the accumulator. Then we load the address of the first table (V3000) into the accumulator using the LDA instruction, converting the octal address to hex. Note that it does not matter which table we declare “first”, because the swap results will be the same. DirectSOFT X0
Load the constant value 2 (Hex.) into the lower 16 bits of the accumulator.
LD K2
Convert octal 3000 to HEX and load the value into the accumulator. This is the table beginning.
LDA O 3000
Swap the contents of the table in the previous instruction with the one at V3100.
SWAP V 3100 Handheld Programmer Keystrokes $ STR
SHFT
P
D CV
SHFT
L ANDST
D
SHFT
L ANDST
D
SHFT
S RST
A 3
0 PREV
3 A
C 2 D
3
0
SHFT
W ANDN
P 0
ENT A
A 3
A
ENT
A 0
0 D
CV
DL205 User Manual, 4th Edition, Rev. A
0 B
3
ENT A
1
A 0
0
ENT
Page 397
Chapter 5: Standard RLL Instructions - Clock/Calendar
Clock/Calendar Instructions Date (DATE) The Date instruction can be used to set the date in the CPU.
DATE
230 The instruction requires two consecutive V-memory locations 240 (Vaaa) to set the date. If the values in the specified locations are 250-1 not valid, the date will not be set. The current date can be read 260 from 4 consecutive V-memory locations (V7771–V7774). DS Used HPP Used
V aaa
Date
Range
V-memory Location (BCD) (READ Only)
Year Month Day Day of Week
0-99 1-12 1-31 0-06
V7774 V7773 V7772 V7771
The values entered for the day of week are: 0=Sunday, 1=Monday, 2=Tuesday, 3=Wednesday, 4=Thursday, 5=Friday, 6=Saturday.
Operand Data Type V-memory
DL250-1 Range
V
DL260 Range aaa aaa
All (See page 3 - 55)
All (See page 3 - 56)
In the following example, when C0 is on, the constant value (K94010301) is loaded into the accumulator using the Load Double instruction (C0 should be a contact from a one shot (PD) instruction). The value in the accumulator is output to V2000 using the Out Double instruction. The Date instruction uses the value in V2000 to set the date in the CPU. DirectSOFT
Constant (K)
C0
9
4
0
1
0
3
0
1
Acc. 9
4
0
1
0
3
0
1
Acc. 9
4
0
1
0
3
0
1
9
4
0
1
0
3
0
1
LDD
In this example, the Date instruction uses the value set in V2000 and V2001 to set the date in the appropriate V memory locations (V7771-V7774).
K94010301 Load the constant value (K94010301) into the accumulator OUTD V2000 Copy the value in the accumulator to V2000 and V2001
V2000
V2001
Format DATE
V2001 V2000
9
Set the date in the CPU using the value in V2000 and 2001 Handheld Programmer Keystrokes $ STR
NEXT
NEXT D
SHFT
L ANDST
D
A
D
A
3
0
3
GX OUT
SHFT
D
SHFT
D
A 3
0
1
C
0
NEXT
A
PREV
J
A
A
0
V2000 1
Month
0
3
Day
0
1
Day of Week
ENT E
A 4
9
B 0
1
ENT
ENT
3
2 T MLR
0
Year NEXT
3 B
4
E
A 0
0 C
4
0 A
2
ENT A
0
A 0
0
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
ENT
DL205 User Manual, 4th Edition, Rev. A
5–175
Page 398
Chapter 5: Standard RLL Instructions - Clock/Calendar
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
Time (TIME) Time instruction can be used to set the time (24-hour TIME 230 The clock) in the CPU. The instruction requires two consecutive V aaa 240 V-memory locations (Vaaa) which are used to set the time. If 250-1 the values in the specified locations are not valid, the time will 260 not be set. The current time can be read from memory locations V7747 and V7766–V7770. DS Used HPP Used
5–176
Date
Range
V-memory Location (BCD) (READ Only)
1/100 seconds (10ms) Seconds Minutes Hour
0-99 0-59 0-59 0-23
V7747 V7766 V7767 V7770
Operand Data Type
DL250-1 Range
DL260 Range aaa aaa
V-memory
All (See page 3 - 55)
All (See page 3 - 56)
V
In the following example, when C0 is on, the constant value (K73000) is loaded into the accumulator using the Load Double instruction (C0 should be a contact from a one shot (PD) instruction). The value in the accumulator is output to V2000 using the Out Double instruction. The Time instruction uses the value in V2000 to set the time in the CPU. DirectSOFT
Constant (K)
C0
0
0
0
7
3
0
0
0
Acc. 0
0
0
7
3
0
0
0
Acc. 0
0
0
7
3
0
0
0
0
0
0
7
3
0
0
0
The Time instruction uses the value set in V2000 and V2001 to set the time in the appropriate Vmemory locations (V7766–V7770)
LDD K73000 Load the constant value (K73000) into the accumulator
OUTD V2000 Copy the value in the accumulator to V2000 and V2001
V2001
V2000
Format V2001
TIME
0
V2000
0
0
V2000 7
3
0
0
0
Set the time in the CPU using the value in V2000 and V2001
Not Used
Handheld Programmer Keystrokes $
NEXT
NEXT
SHFT
L ANDST
D
D
GX OUT
SHFT
D
SHFT
T MLR
SHFT
STR
3
NEXT
3 C
3
NEXT
A
PREV
H
A
A 0
2 I 8
M ORST
E
0
ENT D
7
A 3
A 0
0 C
4
Hour Minutes
A 0
DL205 User Manual, 4th Edition, Rev. A
0
ENT
ENT A
2
A 0
A 0
A 0
0
ENT
Seconds
Page 399
Chapter 5: Standard RLL Instructions - CPU Control
CPU Control Instructions No Operation (NOP)
230 240 250-1 260
The No Operation is an empty (not programmed) memory location.
DirectSOFT
Handheld Programmer Keystrokes SHFT
DS Used HPP Used
NOP
NOP
N TMR
O INST#
P
ENT
CV
End (END) The End instruction marks the termination point of the normal
230 program scan. An End instruction is required at the end of the main 240 program body. If the End instruction is omitted an error will occur and 250-1 the CPU will not enter the Run Mode. Data labels, subroutines and routines are placed after the End instruction. The End 260 interrupt instruction is not conditional; therefore, no input contact is allowed. DS Used HPP Used
DirectSOFT
END
Handheld Programmer Keystrokes SHFT
E 4
END
N TMR
D
ENT
3
Stop (STOP) The Stop instruction changes the operational mode of the CPU from
STOP 230 Run to Program (Stop) mode. This instruction is typically used to stop 240 PLC operation in a shutdown condition such as a I/O module failure.
250-1 260 In the following example, when SP45 comes on indicating a I/O module failure, the CPU will stop operation and switch to the program mode. DS Used HPP Used
DirectSOFT
Handheld Programmer Keystrokes $
SP45
STR STOP SHFT
SP45 will turn on if there is an I/O module failure.
S RST
F
SHFT
SP STRN
E
SHFT
T MLR
O INST#
5
4 P
CV
ENT ENT
DL205 User Manual, 4th Edition, Rev. A
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
5–177
Page 400
Chapter 5: Standard RLL Instructions - CPU Control
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
Reset Watch Dog Timer (RSTWT) The Reset Watch Dog Timer instruction resets the CPU scan
230 timer. The default setting for the watch dog timer is 200ms. 240 Scan times very seldom exceed 200ms, but it is possible. 250-1 For/next loops, subroutines, interrupt routines, and table can be programmed such that the scan becomes 260 instructions longer than 200ms. When instructions are used in a manner DS Used HPP Used
5–178
RSTWT that could exceed the watch dog timer setting, this instruction can be used to reset the timer. A software timeout error (E003) will occur and the CPU will enter the program mode if the scan time exceeds the watch dog timer setting. Placement of the RSTWT instruction in the program is very important. The instruction has to be executed before the scan time exceeds the watch dog timer’s setting. If the scan time is consistently longer than the watch dog timer’s setting, the timeout value may be permanently increased from the default value of 200ms by AUX 55 on the HPP or the appropriate auxiliary function in your programming package. This eliminates the need for the RSTWT instruction. In the following example the CPU scan timer will be reset to 0 when the RSTWT instruction is executed. See the For/Next instruction for a detailed example.
DirectSOFT
Handheld Programmer Keystrokes SHFT RSTWT
DL205 User Manual, 4th Edition, Rev. A
R ORN
S RST
T MLR
W ANDN
T MLR
ENT
Page 401
Chapter 5: Standard RLL Instructions - Program Control
Program Control Instructions Goto Label (GOTO) (LBL) The Goto / Label skips all instructions between the Goto
K aaa
230 and the corresponding LBL instruction. The operand 240 value for the Goto and the corresponding LBL are the same. The logic between Goto and 250-1 instruction LBL instruction is not executed when the Goto 260 instruction is enabled. Up to 128 Goto instructions and
GOTO
LBL
K aaa
64 LBL instructions can be used in the program. DS Used HPP Used
Operand Data Type Constant
K
DL240 Range
DL250-1 Range aaa aaa
DL260 Range aaa
1-FFFF
1-FFFF
1-FFFF
In the following example, when C7 is on, all the program logic between the GOTO and the corresponding LBL instruction (designated with the same constant Kaaa value) will be skipped. The instructions being skipped will not be executed by the CPU. DirectSOFT C7
Handheld Programmer Keystrokes K5 GOTO
$
SHFT
STR SHFT
G 6
O INST# B
$
1
STR X1
C2 OUT
GX OUT
SHFT LBL
$
K5
SHFT
L B ANDST 1 F
STR GX OUT X5
5 C 2
C
H 2
7
MLR
O INST#
T
ENT F 5
ENT C
C 2
L ANDST
2
ENT
F 5
ENT
ENT ENT
Y2 OUT
DL205 User Manual, 4th Edition, Rev. A
ENT
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
5–179
Page 402
Chapter 5: Standard RLL Instructions - Program Control
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
For/Next (FOR) (NEXT) For and Next instructions are used to execute a 230 The section of ladder logic between the For and Next 240 instruction a specified numbers of times. When the For 250-1 instruction is enabled, the program will loop the specified 260 number of times. If the For instruction is not energized DS Used HPP Used
5–180 the section of ladder logic between the For and Next instructions is not executed. For/Next instructions cannot be nested. Up to 64 For/Next loops may be used in a program. If the maximum number of For / Next loops is exceeded, error E413 will occur. The normal I/O update and CPU housekeeping is suspended while executing the For/Next loop. The program scan can increase significantly, depending on the amount of times the logic between the For and Next instruction is executed. With the exception of immediate I/O instructions, I/O will not be updated until the program execution is completed for that scan. Depending on the length of time required to complete the program execution, it may be necessary to reset the watch dog timer inside of the For/Next loop using the RSTWT instruction. Operand Data Type V-memory Constant
A aaa FOR
NEXT
DL240 Range
DL250-1 Range
A aaa aaa aaa
V K
All (See page 3 - 54) 1-9999
All (See page 3 - 55) 1-9999
All (See page 3 - 56) 1-9999
DL205 User Manual, 4th Edition, Rev. A
DL260 Range