Page 52

Chapter 2: Installation, Wiring and Specifications

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

Installing DL205 Bases Choosing the Base Type The DL205 system offers four different sizes of bases and three different power supply options. The following diagram shows an example of a 6-slot base.

Power Wiring Connections

CPU Slot

I/O Slots

Your choice of base depends on three things: • Number of I/O modules required • Input power requirement (AC or DC power) • Available power budget

Mounting the Base All I/O configurations of the DL205 may use any of the base configurations. The bases are secured to the equipment panel or mounting location using four M4 screws in the corner tabs of the base. The full mounting dimensions are given in the previous section on Mounting Guidelines.

Mounting Tabs

2–10

WARNING: To minimize the risk of electrical shock, personal injury, or equipment damage, always disconnect the system power before installing or removing any system component.

DL205 User Manual, 4th Edition, Rev. A

Page 53

Chapter 2: Installation, Wiring and Specifications

Using Mounting Rails The DL205 bases can also be secured to the cabinet by using mounting rails. You should use rails that conform to DIN EN standard 50 022. Refer to our catalog for a complete line of DIN rail, DINnectors and DIN rail mounted apparatus. These rails are approximately 35mm high, with a depth of 7.5mm. If you mount the base on a rail, you should also consider using end brackets on each end of the rail. The end brackets help keep the base from sliding horizontally along the rail. This helps minimize the possibility of accidentally pulling the wiring loose. If you examine the bottom of the base, you’ll notice small retaining clips. To secure the base to a DIN rail, place the base onto the rail and gently push up on the retaining clips. The clips lock the base onto the rail. To remove the base, pull down on the retaining clips, lift up on the base slightly, and pull it away from the rail.

DIN Rail Dimensions 7.5mm

35 mm

Retaining Clips

DL205 User Manual, 4th Edition, Rev. A

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

2–11

Page 54

Chapter 2: Installation, Wiring and Specifications

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

Installing Components in the Base

2–12

To insert components into the base: first slide the module retaining clips to the out position and align the PC board(s) of the module with the grooves on the top and bottom of the base. Push the module straight into the base until it is firmly seated in the backplane connector. Once the module is inserted into the base, push in the retaining clips to firmly secure the module to the base.

CPU must be positioned in the first slot of the base Align module PC board to slots in base and slide in Push the retaining clips in to secure the module to the DL205 base

WARNING: Minimize the risk of electrical shock, personal injury, or equipment damage. Always disconnect the system power before installing or removing any system component.

DL205 User Manual, 4th Edition, Rev. A

Page 55

Chapter 2: Installation, Wiring and Specifications

Base Wiring Guidelines

1 110/220 VAC Base T erminal Strip Base Wiring 2 The diagrams show the terminal connections located on the power supply of the DL205 bases. The base terminals 3 can accept up to 16 AWG. You may be able to use larger wiring depending on 4 the type of wire used, but 16 AWG is the recommended size. Do not overtighten the connector screws; the recommended 5 + torque value is 7.81 ld-in (0.882 N•m). 6 7 NOTE: You can connect either a 115 VAC or 220 VAC supply to the AC terminals. Special wiring or jumpers 8 are not required as with some of the other DirectLOGIC. products. 9 12/24 VDC Base Terminal Strip 125 VDC Base Terminal Strip 10 11 12 13 14 WARNING: Once the power wiring is connected, install the plastic protective cover. When the cover is A removed there is a risk of electrical shock if you accidentally touch the wiring or wiring terminals. B C D 85 – 264 VAC G

LG

24 VDC OUT, 0.3A

+ 12 – 24 VDC –

+

115 – 264 VDC –

G

G

LG

LG

+ 24 VDC OUT, 0.3A –

DL205 User Manual, 4th Edition

2–13

Page 56

Chapter 2: Installation, Wiring and Specifications

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

I/O Wiring Strategies

2–14

The DL205 PLC system is very flexible and will work in many different wiring configurations. By studying this section before actual installation, you can probably find the best wiring strategy for your application. This will help to lower system cost, wiring errors, and avoid safety problems.

PLC Isolation Boundaries PLC circuitry is divided into three main regions separated by isolation boundaries, shown in the drawing below. Electrical isolation provides safety, so that a fault in one area does not damage another. A powerline filter will provide isolation between the power source and the power supply. A transformer in the power supply provides magnetic isolation between the primary and secondary sides. Opto-couplers provide optical isolation in Input and Output circuits. This isolates logic circuitry from the field side, where factory machinery connects. Note the discrete inputs are isolated from the discrete outputs, because each is isolated from the logic side. Isolation boundaries protect the operator interface (and the operator) from power input faults or field wiring faults. When wiring a PLC, it is extremely important to avoid making external connections that connect logic side circuits to any other. Secondary, or Logic side

Primary Side

PLC

Power Input

Main Power Supply

Filter

Isolation Boundary

Field Side

(backplane)

Input Module

Inputs

(backplane)

Output Module

Outputs

CPU

Programming Device, Operator Interface, or Network

Isolation Boundary

In addition to the basic circuits covered above, AC-powered and 125VDC bases include an auxiliary +24VDC power supply with its own isolation boundary. Since the supply output is isolated from the other three circuits, it can power input and/or output circuits! DL205 PLC

Primary Side Power Input

Filter

+24VDC Out

Main Power Supply

Auxiliary +24VDC Supply

Secondary, or Logic side Internal

CPU

Backplane

Comm.

Input Module

Output Module

To Programming Device, Operator Interface, Network

Inputs Commons

Outputs Commons

Field Side

Supply for Output Circuit

DL205 User Manual, 4th Edition, Rev. A

Page 57

Chapter 2: Installation, Wiring and Specifications

Powering I/O Circuits with the Auxiliary Supply In some cases, using the built-in auxiliary +24VDC supply can result in a cost savings for your control system. It can power combined loads up to 300mA. Be careful not to exceed the current rating of the supply. If you are the system designer for your application, you may be able to select and design in field devices which can use the +24VDC auxiliary supply. All AC powered and 125VDC DL205 bases feature the internal auxiliary supply. If input devices AND output loads need +24VDC power, the auxiliary supply may be able to power both circuits as shown in the following diagram. AC Power or 125VDC Bases Power Input

Auxiliary +24VDC Supply

+

DL205 PLC Input Module

Output Module

Inputs

Outputs Com.

Com.

– Loads

The 12/24VDC powered DL205 bases are designed for application environments in which low-voltage DC power is more readily available than AC. These include a wide range of battery–powered applications, such as remotely-located control, in vehicles, portable machines, etc. For this application type, all input devices and output loads typically use the same DC power source. Typical wiring for DC-powered applications is shown in the following diagram. +

+

–

–

DC Power

DL205 PLC Power Input

Input Module

Output Module

Inputs

Outputs Com.

Com.

Loads

DL205 User Manual, 4th Edition, Rev. A

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

2–15

Page 58

Chapter 2: Installation, Wiring and Specifications

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 2–16

Powering I/O Circuits Using Separate Supplies In most applications it will be necessary to power the input devices from one power source, and to power output loads from another source. Loads often require high-energy AC power, while input sensors use low-energy DC. If a machine operator is likely to come in close contact with input wiring, then safety reasons also require isolation from high-energy output circuits. It is most convenient if the loads can use the same power source as the PLC, and the input sensors can use the auxiliary supply, as shown to the left in the figure below. If the loads cannot be powered from the PLC supply, then a separate supply must be used as shown to the right in the figure below. AC Power Power Input

Auxiliary +24VDC Supply

+

AC Power Power Input

DL205 PLC Input Module

Output Module

Inputs

Outputs Com.

Com.

–

Auxiliary +24VDC Supply

+

DL205 PLC Input Module

Output Module

Inputs

Outputs Com.

Com.

–

Loads

Loads

Load Supply

Some applications will use the PLC external power source to also power the input circuit. This typically occurs on DC-powered PLCs, as shown in the drawing below to the left. The inputs share the PLC power source supply, while the outputs have their own separate supply. A worst-case scenario, from a cost and complexity viewpoint, is an application which requires separate power sources for the PLC, input devices, and output loads. The example wiring diagram below on the right shows how this can work, but also the auxiliary supply output is an unused resource. You will want to avoid this situation if possible. +

+

–

–

DC Power AC Power Power Input

DL205 PLC Power Input

Input Module

Output Module

Inputs

Outputs Com.

Com.

Auxiliary +24VDC Supply

+ Loads

Load Supply

DL205 User Manual, 4th Edition, Rev. A

DL205 PLC Input Module

Output Module

Inputs

Com.

Outputs Com.

Input Supply

Loads

– Load Supply

Page 59

Chapter 2: Installation, Wiring and Specifications

Sinking / Sourcing Concepts Before going further in the study of wiring strategies, you must have a solid understanding of “sinking” and “sourcing” concepts. Use of these terms occurs frequently in input or output circuit discussions. It is the goal of this section to make these concepts easy to understand, further ensuring your success in installation. First the following short definitions are provided, followed by practical applications. Sinking = provides a path to supply ground (–) Sourcing = provides a path to supply source (+) First you will notice these are only associated with DC circuits and not AC, because of the reference to (+) and (–) polarities. Therefore, sinking and sourcing terminology only applies to DC input and output circuits. Input and output points that are sinking only or sourcing only can conduct current in only one direction. This means it is possible to connect the external supply and field device to the I/O point with current trying to flow in the wrong direction, and the circuit will not operate. However, you can successfully connect the supply and field device every time by understanding “sourcing” and “sinking”. For example, the figure to the right depicts a “sinking” PLC input. To properly connect the external supply, you Input will have to connect it so the input provides a path to (sinking) ground (–). Start at the PLC input terminal, follow + through the input sensing circuit, exit at the common Input Sensing terminal, and connect the supply (–) to the common – terminal. By adding the switch, between the supply (+) Common and the input, the circuit has been completed . Current flows in the direction of the arrow when the switch is closed. Apply the circuit principle above to the four possible combinations of input/output sinking/sourcing types as shown below. The I/O module specifications at the end of this chapter list the input or output type. Sinking Input

Sinking Output Input

+ –

PLC Input Sensing

Common +

Load + –

Common

Sourcing Output PLC Input Sensing

Input

Output

Output Switch

Common

Sourcing Input

–

PLC

PLC

Common +

Output Switch Output

–

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

Load

DL205 User Manual, 4th Edition, Rev. A

2–17

Page 60

Chapter 2: Installation, Wiring and Specifications

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

I/O “Common” Terminal Concepts In order for a PLC I/O circuit to operate, current must enter at one terminal and exit at another. Therefore, at least two terminals are associated with every I/O point. In the figure to the right, the Input or Output terminal is the main path for the current. One additional terminal must provide the return path to the power supply.

Main Path (I/O Point)

I/O Circuit

+ – Return Path

PLC

If there was unlimited space and budget for I/O terminals, every I/O point could have two dedicated terminals as the figure above shows. However, providing this level of flexibility is not practical or even necessary for most applications. So, most Input or Output points on PLCs are in groups which share the return path (called commons). The figure to the right shows a group (or bank) of four input points which share a common return path. In this way, the four inputs require only five terminals instead of eight.

Input 1

Input Sensing

Input 2 Input 3 Input 4 + –

Common

NOTE: In the circuit above, the current in the common path is 4 times any channel’s input current when all inputs are energized. This is especially important in output circuits, where heavier gauge wire is sometimes necessary on commons.

Most DL205 input and output modules group their I/O points into banks that share a common return path. The best indication of I/O common grouping is on the wiring label, such as the one shown to the right. There are two circuit banks with eight input points in each. The common terminal for each is labeled “CA” and “CB”, respectively. In the wiring label example, the positive terminal of a DC supply connects to the common terminals. Some symbols you will see on the wiring labels, and their meanings are: AC supply

DC supply –

Input Switch

AC or DC supply

+

Output Load L

2–18

PLC Field Device

DL205 User Manual, 4th Edition, Rev. A

IN 24 VDC A 0 4 5 1 6 2 7 B 3 D2–16ND3–2 20-28VDC 8mA CLASS 2

CA 0 4 1 5 2 6 3 7 NC CB 0 4 1 5 2 6 3 7 D2-16ND3-2