DL205 PLC User Manual, Volume 1 of 2: Chapter 2: Installation, Wiring and Specifications, pages 61 to 69

Pages 61 to 69 of 592, from DL205 PLC User Manual, Volume 1 of 2

The original document is the PDF (13 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the PLC Direct D2-08ND3 and Koyo D2-08ND3

Page 61

Chapter 2: Installation, Wiring and Specifications

Connecting DC I/O to “Solid State” Field Devices

1 2 3 Solid State Input Sensors Several DL205 DC input modules are flexible because they detect current flow in either direction, so they can be wired as either sourcing or sinking. In the following circuit, a field 4 device has an open-collector NPN transistor output. It sinks current from the PLC input point, which sources current. The power supply can be the +24 auxiliary supply or another 5 supply (+12 VDC or +24VDC), as long as the input specifications are met. 6 7 8 In the next circuit, a field device has an open-collector PNP transistor output. It sources 9 current to the PLC input point, which sinks the current back to ground. Since the field device is sourcing current, no additional power supply is required. 10 11 12 Solid State Output Loads Sometimes an application requires connecting a PLC output point to a solid state input on a 13 device. This type of connection is usually made to carry a low-level control signal, not to send DC power to an actuator. 14 Several of the DL205 DC output modules are the sinking type. This means that each DC output provides a path to ground when it is energized. In the following circuit, the PLC A output point sinks current to the output common when energized. It is connected to a sourcing input of a field device input. B C D In the previous section on Sourcing and Sinking concepts, the DC I/O circuits were explained to sometimes only allow current to flow one way. This is also true for many of the field devices which have solid-state (transistor) interfaces. In other words, field devices can also be sourcing or sinking. When connecting two devices in a series DC circuit, one must be wired as sourcing and the other as sinking.

Field Device

PLC DC Input

Input (sourcing)

Output (sinking)

Supply

Ground

–

+

Common

Field Device +V

PLC DC Input

Input

Output (sourcing) Ground

(sinking)

Common

PLC DC Sinking Output Power +DC pwr

Field Device +V

Output

(sinking)

+

Common

–

Input (sourcing) 10–30 VDC Ground

DL205 User Manual, 4th Edition, Rev. A

2–19

Page 62

Chapter 2: Installation, Wiring and Specifications

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 2–20

In the next example a PLC sinking DC output point is connected to the sinking input of a field device. This is a little tricky, because both the PLC output and field device input are sinking type. Since the circuit must have one sourcing and one sinking device, a sourcing capability needs to be added to the PLC output by using a pull-up resistor. In the circuit below, a Rpull-up is connected from the output to the DC output circuit power input. PLC DC Output Power

+DC pwr

Field Device

R pull-up (sourcing) (sinking)

Output +

Input (sinking)

–

Ground

R input

Supply Common

NOTE 1: DO NOT attempt to drive a heavy load (>25 mA) with this pull-up method NOTE 2: Using the pull-up resistor to implement a sourcing output has the effect of inverting the output point logic. In other words, the field device input is energized when the PLC output is OFF, from a ladder logic point of view. Your ladder program must comprehend this and generate an inverted output. Or, you may choose to cancel the effect of the inversion elsewhere, such as in the field device.

It is important to choose the correct value of Rpull-up. In order to do so, you need to know the nominal input current to the field device (Iinput) when the input is energized. If this value is not known, it can be calculated as shown (a typical value is 15 mA). Then use Iinput and the voltage of the external supply to compute Rpull-up. Then calculate the power Ppull-up (in watts), in order to size Rpull-up properly. I input

=

R pull-up =

V input (turn–on) R input V supply – 0.7 I input

– R input

P pull-up =

V supply2 R pullup

Of course, the easiest way to drive a sinking input field device as shown below is to use a DC sourcing output module. The Darlington NPN stage will have about 1.5 V ON-state saturation, but this is not a problem with low-current solid-state loads. PLC DC Sourcing Output +DC pwr

Common Field Device Output (sourcing) +

Input (sinking)

–

Ground

Supply

DL205 User Manual, 4th Edition, Rev. A

R input

Page 63

Chapter 2: Installation, Wiring and Specifications

Relay Output Guidelines Several output modules in the DL205 I/O family feature relay outputs: D2–04TRS, D2–08TR, D2–12TR, D2–08CDR, F2–08TR and F2–08TRS. Relays are best for the following applications:

1 • Loads that require higher currents than the solid-state outputs can deliver 2 • Cost-sensitive applications • Some output channels need isolation from other outputs (such as when some loads require different 3 voltages than other loads) Some applications in which NOT to use relays: 4 • Loads that require currents under 10 mA • Loads which must be switched at high speed or heavy duty cycle 5 Relay outputs in the DL205 output modules are available in 6 two contact arrangements, shown to the right. The Form A type, or SPST (single pole, single throw) type is normally open 7 and is the simplest to use. The Form C type, or SPDT (single pole, double throw) type has a center contact which moves and a stationary contact on either side. This provides a normally 8 closed contact and a normally open contact. Some relay output module’s relays share common terminals, 9 which connect to the wiper contact in each relay of the bank. Other relay modules have relays which are completely isolated 10 from each other. In all cases, the module drives the relay coil when the corresponding output point is on. 11 Surge Suppression For Inductive Loads 12 Inductive load devices (devices with a coil) generate transient voltages when de-energized with a relay contact. When a relay contact is closed it “bounces”, which energizes and de-energizes 13 the coil until the “bouncing” stops. The transient voltages generated are much larger in amplitude than the supply voltage, especially with a DC supply voltage. When switching a DC-supplied inductive load the full supply voltage is always present when 14 the relay contact opens (or “bounces”). When switching an AC-supplied inductive load there are two (2) points when the voltage is zero (0) in one complete cycle of a sine wave; therefore, A there are two (2) chances in 60 (60 Hz) or 50 (50 Hz) to stop the current flow at a zero crossover point. If current flow isn’t stopped, the relay contact will open (or “bounce”). If the B voltage is not zero when the relay contact opens there is energy stored in the inductor that is released when the voltage to the inductor is suddenly removed. This release of energy is the cause of the transient voltages. C When inductive load devices (motors, motor starters, interposing relays, solenoids, valves, etc.) are controlled with relay contacts, it is recommended that a surge suppression device be D connected directly across the coil of the field device. If the inductive device has plug-type Relay with Form A contacts

Relay with Form C contacts connectors, the suppression device can be installed on the terminal block of the relay output.

DL205 User Manual, 4th Edition, Rev. A

2–21

Page 64

Chapter 2: Installation, Wiring and Specifications

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

Transient Voltage Suppressors (TVS or transorb) provide the best surge and transient suppression of AC and DC powered coils, providing the fastest response with the smallest overshoot. Metal Oxide Varistors (MOV) provide the next best surge and transient suppression of AC and DC powered coils. For example, the waveform in the figure below shows the energy released when opening a contact switching a 24 VDC solenoid. Notice the large voltage spike. +24 VDC

–24 VDC

+24 VDC

Module Relay Contact –324 VDC

This figure shows the same circuit with a transorb (TVS) across the coil. Notice that the voltage spike is significantly reduced. +24 VDC –24 VDC

+24 VDC –42 VDC

Module Relay Contact

Use the following table to help select a TVS or MOV suppressor for your application based on the inductive load voltage. Vendor / Catalog

Suppressor Types

Inductive Load Voltage

Part Number

AutomationDirect Transient Voltage Suppressors www.automationdirect.com

8–channel TVS

24 VDC

ZL–TD8–24

8–channel TVS

110 VAC

ZL–TD8–120

General Instrument Transient Voltage Suppressors and LiteOn Diodes; from Digi-Key Catalog; www.digikey.com; Phone: 1-800-344-4539

TVS, MOV TVS, MOV TVS Diode

110/120 VAC 220/240 VAC 12/24 VDC or VAC 12/24 VDC or VAC

Check Digi-Key Corp. catalog or website

2–22

DL205 User Manual, 4th Edition, Rev. A

Page 65

Chapter 2: Installation, Wiring and Specifications

Relay contacts wear according to the amount of relay switching, amount of spark created at the time of open or closure, and presence of airborne contaminants. However, there are some steps you can take to help prolong the life of relay contacts:

1 • Switch the relay on or off only when the application requires it. 2 • If you have the option, switch the load on or off at a time when it will draw the least current. 3 • Take measures to suppress inductive voltage spikes from inductive DC loads such as contactors and solenoids (circuit given below). 4 PLC Relay Output Inductive Field Device Input Output 5 R 6 Supply C + – Common Common 7 8 Adding external contact protection may extend relay life beyond the number of contact cycles listed in the specification tables for relay modules. High current inductive loads such as 9 clutches, brakes, motors, direct-acting solenoid valves, and motor starters will benefit the most from external contact protection. 10 The RC network must be located close to the relay module output connector. To find the values for the RC snubber network, first determine the voltage across the contacts when open, and the current through them when closed. If the load supply is AC, then convert the current 11 and voltage values to peak values: Now you are ready to calculate values for R and C, according to the formulas: 12 2 50 I V 13 , where x = 1 + C (µF) = R ( = x V 10 10 x I 14 C minimum = 0.001 µ F, the voltage rating of C must be V, non-polarized R minimum = 0.5 1/2 W, tolerance is ± 5% A B C D DL205 User Manual, 4th Edition, Rev. A

2–23

Page 66

Chapter 2: Installation, Wiring and Specifications

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 2–24

For example, suppose a relay contact drives a load at 120VAC, 1/2 A. Since this example has an AC power source, first calculate the peak values:

Ipeak = Irms x 1.414, = 0.5 x 1.414 = 0.707 Amperes Vpeak = Vrms x 1.414 = 120 x 1.414 = 169.7 Volts Now, find the values of R and C,: I

C (µ F) =

2

=

10 R = x= 1 +

10

V 10 x I 50

0.707 x

2

= 0.05 µF, voltage rating 170 Volts

, where x= 1 +

= 1.29

50 V

R =

169.7

169.7 10 x 0.707 1.29

= 26 1/2 W, ± 5%

If the contact is switching a DC inductive load, add a diode across the load as near to load coil as possible. When the load is energized the diode is reverse-biased (high impedance). When the load is turned off, energy stored in its coil is released in the form of a negativegoing voltage spike. At this moment the diode is forward-biased (low impedance) and shunts the energy to ground. This protects the relay contacts from the high voltage arc that would occur as the contacts are opening. For best results, follow these guidelines in using a noise suppression diode: • DO NOT use this circuit with an AC power supply. • Place the diode as close to the inductive field device as possible. • Use a diode with a peak inverse voltage rating (PIV) at least 100 PIV, 3A forward current or larger. Use a fast-recovery type (such as Schottky type). DO NOT use a small-signal diode such as 1N914, 1N941, etc. • Be sure the diode is in the circuit correctly before operation. If installed backwards, it shortcircuits the supply when the relay energizes.

DL205 User Manual, 4th Edition, Rev. A

Page 67

Chapter 2: Installation, Wiring and Specifications

I/O Modules Position, Wiring, and Specification

1 The DL205 bases each provide different numbers of slots for use with the I/O modules. You 2 may notice the bases refer to 3-slot, 4-slot, etc. One of the slots is dedicated to the CPU, so you always have one less I/O slot. For example, you have five I/O slots with a 6-slot base. The I/O slots are numbered 0 – 4. The CPU slot always contains a PLC CPU or other CPU–slot 3 controller and is not numbered. Module Placement Restrictions 4 The following table lists the valid locations for all types of modules in a 5 DL205 system: Module/Unit Local CPU Base Local Expansion Base Remote I/O Base 6 CPUs DC Input Modules . 7 AC Input Modules DC Output Modules 8 AC Output Modules Relay Output Modules Analog Input and Output Modules 9 Local Expansion Base Expansion Module 10 Base Controller Module Serial Remote I/O 11 Remote Master Remote Slave Unit 12 Ethernet Remote Master CPU Interface 13 Ethernet Base Controller WinPLC 14 DeviceNet Profibus SDS A Specialty Modules Counter Interface B * Counter I/O Data Communications C Ethernet Communications BASIC CoProcessor D Simulator Slot Numbering

Slot 0 Slot 1 Slot 2 Slot 3 Slot 4

CPU Slot

I/O Slots

CPU Slot Only

CPU Slot Only

CPU Slot Only

Slot 0 Only

Slot 0 Only*

Slot 0 Only Slot 0 Only

Slot 0 Only

Slot 0 Only Slot 0 Only

Filler

* When used with H2-ERM Ethernet Remote I/O system

DL205 User Manual, 4th Edition, Rev. A

2–25

Page 68

Chapter 2: Installation, Wiring and Specifications

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 2–26

Special Placement Considerations for Analog Modules In most cases, the analog modules can be placed in any slot. However, the placement can also depend on the type of CPU you are using and the other types of modules installed to the left of the analog modules. If you’re using a DL230 CPU (or a DL240 CPU with firmware earlier than V1.4) you should check the DL205 Analog I/O Manual for any possible placement restrictions related to your particular module. You can order the DL205 Analog I/O Manual by ordering part number D2–ANLG–M.

Discrete Input Module Status Indicators The discrete modules provide LED status indicators to show the status of the input points. Status indicators

Terminal

Terminal Cover (installed)

Wire tray area behind terminal cover

Color Coding of I/O Modules The DL205 family of I/O modules have a color coding scheme to help you quickly identify if a module is either an input module, output module, or a specialty module. This is done through a color bar indicator located on the front of each module. The color scheme is listed below:

Color Bar

Module Type Discrete/Analog Output Discrete/Analog Input Other

DL205 User Manual, 4th Edition, Rev. A

Color Code Red Blue White

Page 69

Chapter 2: Installation, Wiring and Specifications

Wiring the Different Module Connectors There are two types of module connectors for the DL205 I/O. Some modules have normal screw terminal connectors. Other modules have connectors with recessed screws. The recessed screws help minimize the risk of someone accidentally touching active wiring. Both types of connectors can be easily removed. If you examine the connectors closely, you’ll notice there are squeeze tabs on the top and bottom. To remove the terminal block, press the squeeze tabs and pull the terminal block away from the module. We also have DIN rail mounted terminal blocks, DINnectors (refer to our catalog for a complete listing of all available products). ZIPLinks come with special pre–assembled cables with the I/O connectors installed and wired. WARNING: For some modules, field device power may still be present on the terminal block even though the PLC system is turned off. To minimize the risk of electrical shock, check all field device power before you remove the connector.

DL205 User Manual, 4th Edition, Rev. A

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

2–27