For the PLC Direct D3-08TD1, PLC Direct D3-16NA, Koyo D3-08TD1 and Koyo D3-16NA

Page 76

Bases, Expansion Bases, and I/O Configuration

The following diagram shows the terminal connections located on the power supply of the DL305 bases. WARNING: Damage will occur to the base power supply if 230 VAC is connected to the 115 VAC terminal connections. Once the power wiring is connected, install the protective cover. When the cover is removed there is a risk of electrical shock if you accidentally touch the connection terminals. 24 VDC Terminal Strip

110/220 VAC Terminal Strip

Bases and Expansion Bases

Line Neutral

Expansion Base Power Supply Wiring Example

Bases and Expansion Bases

Connecting the Power Supply

4--9

The following diagram shows how to connect the power when you use both local CPU and Expansion bases. 220VAC

24VDC + --

Neutral

110VAC

220VAC

24VDC + --

Local CPU

Local CPU

Local CPU

110VAC

220VAC

24VDC + --

Expansion Base 1

Expansion Base 1

Expansion Base 1

110VAC

220VAC

24VDC + --

Expansion Base 2

Expansion Base 2

Expansion Base 2

DL305 User Manual, Rev. D

Bases, Expansion Bases and I/O Configuration

110VAC Line

Page 77

Bases, Expansion Bases and I/O Configuration

Bases and Expansion Bases

Bases and Expansion Bases

4--10

Bases, Expansion Bases, and I/O Configuration

Base Specifications D3--05B

D3--05BDC

D3--08B

D3--10B

Number of Slots

5

5

8

10

Local CPU Base

Yes

Yes

Yes

Yes

Expansion Base

Yes

Yes

No

Yes

Input Voltage Range

97--132 VAC 194--264 VAC 47--63Hz

20.5--30 VDC <10% ripple

97--132 VAC 194--264 VAC 47--63Hz

97--132 VAC 194--264 VAC 47--63Hz

Base Power

70 VA max (46W)

48 Watts

70 VA max (57W)

70 VA max (57W)

Inrush Current max.

30A

30A

30A

30A

Dielectric Strength

1500VAC for 1 minute between terminals of AC P/S, Run output, Common, 24VDC

1500VAC for 1 minute between 24VDC input terminals and Run output

1500VAC for 1 minute between terminals of AC P/S, Run output, Common, 24VDC

2000VAC for 1 minute between terminals of AC P/S, Run output, Common, 24VDC

Insulation Resistance

>10MΩ at 500VDC

>10MΩ at 500VDC

>10MΩ at 500VDC

>10MΩ at 500VDC

Power Supply Output (Voltage Ranges and Ripple)

(5VDC) 4.75--5.25V less than 0.1V p--p

(5VDC) 4.75--5.25V less than 0.1V p--p

(5VDC) 4.75--5.25V less than 0.1V p--p

(5VDC) 4.75--5.25V less than 0.1V p--p

(9VDC) 8.5--13.5V less than 0.2V p--p

(9VDC) 8.5--13.5V less than 0.2V p--p

(9VDC) 8.0--12.0V less than 0.2V p--p

(9VDC) 8.0--12.0V less than 0.2V p--p

(24VDC) 20--28V less than 1.2V p--p

(24VDC) 20--28V less than 1.2V p--p

(24VDC) 20--28V less than 1.2V p--p

(24VDC) 20--28V less than 1.2V p--p

5 VDC current available

1.4A *

1.4A

1.4A @ 122° F (50° C) 1.0A @ 140° F (60° C)

1.4A @ 122° F (50° C) 1.0A @ 140° F (60° C)

9 VDC current available

0.8A *

0.8A

1.7A @ 122° F (50° C) 1.4A @ 140° F (60° C)

1.7A @ 122° F (50° C) 1.4A @ 140° F (60° C)

24 VDC current available

0.5A *

0.5A

0.6A

0.6A

Auxiliary 24 VDC

100mA max

None

100mA max

100mA max

Run Relay

250 VAC, 4A (resistive load)

250 VAC, 4A (resistive load)

250 VAC, 4A (resistive load)

250 VAC, 4A (resistive load)

Fuses

2A (250V)

4A (250V)

2A (250V)

2A (250V)

User replaceable

User replaceable

User replaceable

User replaceable

WxHxD

11.42x4.85x4.41 in. (290x123x112 mm)

11.42x4.85x4.41 in (290x123x112 mm)

15.55x4.85x4.41 in (395x123x112 mm)

18.3x4.85x4.41 in. (465x123x112 mm)

Weight

34 oz. (964g)

34 oz. (964g)

44.2 oz. (1253g)

50.5 oz. (1432g)

Consumption

Output

Dimensions

* The total current for the D3--05B must not exceed 2.3A. Auxiliary 24VDC Output at Base Terminal

There is 24 VDC available from the 24 VDC output terminals on all bases except the 5 slot DC version (D3--05BDC). The 24 VDC supply can be used to power external devices or DL305 modules that require external 24 VDC. The power used from the this 24 VDC output reduces the internal system 24 VDC available to the modules by an equal amount. So if you use this power supply, make sure you consider this when you calculate the power budget. (The power budget is discussed in more detail later in this chapter.)

DL305 User Manual, Rev. D

Page 78

4--11

Bases, Expansion Bases, and I/O Configuration

The following diagram shows the details of how the DL305 base provides many of the specifications listed on the previous page.

Schematic for D3--05B, D3--08B, D3--10B 2A +

0V

--

+9V

+

+5V

+ --

115VAC

Switching Power Source Circuit

24V/9V Voltage Abnormality Detection

L

N

230VAC

Coil RUN Output

CPU Normal RUN

Bases and Expansion Bases

+24V

Bases and Expansion Bases

Power Supply Schematics

+ 24VDC Output --

Inside of CPU

G

0V

Schematic for D3--05BDC +

0V

--

+9V

+

+5V

+ --

24V/9V Voltage Abnormality Detection

Switching Power Source Circuit

+ --

Coil RUN Output

CPU Normal RUN Inside of CPU 0V

G

DL305 User Manual, Rev. D

24VDC

Bases, Expansion Bases and I/O Configuration

4A +24V

Page 79

Bases and Expansion Bases

Bases and Expansion Bases

4--12

Bases, Expansion Bases, and I/O Configuration

Using the Run Relay on the Base Power Supply

The RUN relay output, located on the DL305 base power supply, can be used to detect an undesired failure on the local CPU base or an expansion base. The following table shows the operating characteristics of the RUN relay for a local CPU base or an expansion base. Event

Local CPU Base RUN Relay Would:

Expansion Base RUN Relay Would:

PROGRAM to RUN mode Transition

Energize

Not change

The CPU detects a fatal error

De--energize

Not change

CPU Local Base is Removed Form the RUN Mode

De--energize

Not change

Power Source to the Power Supply is Turned OFF

De--energize

De--energize

9 VDC or 24 VDC Failure on the Power Supply

De--energize

De--energize

The following example demonstrates possible uses for the RUN relay on the DL305 bases. Relay Power Supply

Bases, Expansion Bases and I/O Configuration

Use of the RUN relay to shutdown critical field devices upon error detection

Relay Critical Field Device

Field Power Supply Panel Lamp Power

Use of the RUN relay to monitor system operation PLC OK Lamp

DL305 User Manual, Rev. D

Page 80

Bases, Expansion Bases, and I/O Configuration

The CPU must go into first slot (next to the power supply) on the far right side of the base. When inserting components into the base, align the PC board(s) of the module with the grooves on the top and bottom of the base. Push the module straight into the base until it is firmly seated in the backplane connector. To remove a module from the base squeeze the tabs on the top and bottom of the faceplate and pull the module straight out.

Bases and Expansion Bases

Align module to slots in base and slide in

Bases and Expansion Bases

Installing CPUs and I/O Modules

4--13

WARNING: Do not remove any system component when system power is on. This may cause damage to the system or unpredictable system operation that can result in a risk of personal injury.

Bases, Expansion Bases and I/O Configuration

DL305 User Manual, Rev. D

Page 81

Bases and Expansion Bases

Bases and Expansion Bases

4--14

Bases, Expansion Bases, and I/O Configuration

Using Bases for Local or Expansion I/O Systems Base Uses Table

Local/Expansion Connectivity

It is helpful to understand how you can use the various DL305 bases in your control system. The following table shows how the bases can be used. Base Part #

Number of Slots

Can Be Used As A Local CPU Base

Can Be Used As An Expansion Base

D3--05B

5

Yes

Yes

D3--05BDC

5

Yes

Yes

D3--08B

8

Yes

No

D3--10B

10

Yes

Yes

The configurations below show the valid combinations of local CPU bases and expansion bases.

NOTE: You should use one of the configurations listed below when designing an expansion system. If you use a configuration not listed below the system will not function properly.

10 slot local CPU base with a 5 slot expansion base

1.5 ft (0.5m)

8 slot local CPU base with a 5 slot expansion base

1.5 ft (0.5m)

10 slot local CPU base with a 10 slot expansion base 1.5 ft (0.5m)

1.5 ft (0.5m) 1.5 ft (0.5m)

Bases, Expansion Bases and I/O Configuration

5 slot local CPU base with a maximum of two 5 slot expansion bases

DL305 User Manual, Rev. D

Page 82

Bases, Expansion Bases, and I/O Configuration

The local CPU base is connected to the expansion base using a 1.5 ft. cable (D3--EXCBL). The base must be connected as shown in the diagram below. The top expansion connector on the base is the input from a previous base. The bottom expansion connector on the base is the output to an expansion base. The expansion cable is marked with “CPU Side” and “Expansion Side”. The“ CPU Side” of the cable is connected to the bottom port of the base and the “Expansion Side” of the cable is connected to the top port of the next base.

030 to 037

020 to 027

010 to 017

000 to 007

100 to 107

070 to 077

060 to 067

050 to 057

040 to 047

DL305

150 to 157

140 to 147

130 to 137

120 to 127

110 to 117

DL305

DL305

1.5 ft (0.5 m)

CPU Side

C P U

Bases and Expansion Bases

Expansion Cable

Bases and Expansion Bases

Connecting Expansion Bases

4--15

Expansion Side

Expansion Side

Note: Avoid placing the expansion cable in the same wiring tray as the I/O and power source wiring.

DL305 User Manual, Rev. D

Bases, Expansion Bases and I/O Configuration

1.5 ft (0.5 m)

CPU Side

Page 83

Bases, Expansion Bases, and I/O Configuration

Setting the Base Switches

5 Slot Bases

The 5 slot and 10 slot bases have jumper switches that need to be set depending on which system configuration is used. The 8 slot base does not have any switches. The 5 slot bases have a two position toggle switch which is used to set the base as the CPU local base, the first expansion base, or the second (last) expansion base. The switch is set to the “1,3” position if the base is the local CPU base or the third base in the system. The switch is set to the “2” position if the base is the 2nd base in the system. If the 5 slot base is used as an expansion base for a 10 slot local CPU base the switch is set in the “1,3” position.

Bases and Expansion Bases

Bases and Expansion Bases

4--16

BASE 1,3 2

The 10 slot base has a jumper switch between slot 3 and 4 used to set the base to local CPU base or expansion base. There is also a jumper switch between slot 9 and 10 that sets slot 10 to the 100--107 I/O address range or to the 700--707 I/O address range.

Bases, Expansion Bases and I/O Configuration

10 Slot Base

DL305 User Manual, Rev. D