Page 92

4--25

Bases, Expansion Bases, and I/O Configuration

10 Slot Base and 10 Slot Expansion Base with 8 Point I/O

Total I/O: 152 Jumper SW2

Jumper SW1

100 EXP

EXP 100 to 107

SW2 700

060 to 067

050 to 057

040 to 047

030 to 037

020 to 027

010 to 017

000 to 007

DL305

C P U

SW1

100 EXP

EXP 760 to 767

10 Slot Base and 10 Slot Expansion Base with 16 Point I/O

070 to 077

CPU

750 to 757

740 to 747

730 to 737

720 to 727

710 to 717

700 to 707

130 to 137

120 110 to to 127 117

CPU

Bases and Expansion Bases

700

Bases and Expansion Bases

I/O addresses change depending on the point configuration in the local CPU base. Expansion Addresses Depend Notice, when the local CPU base contains only 8 point I/O modules, addresses on Local CPU Base 110--117, 120--127 and 130--137 are available for use in the expansion base. When the local CPU base has 16 point I/O modules, which use the I/O addresses 110--117, Configuration. 120--127 and 130--137, these addresses are taken up and are not available for use in the expansion base.

DL305

Total I/O: 184 Jumper SW2

SW2 700

100 EXP

8 7

6 5

4

3 2

1 0

070 to 077

060 to 067

050 to 057

040 to 047

030 to 037

020 to 027

010 to 017

000 to 007

170 to 177

160 to 167

150 to 157

140 to 147

130 to 137

120 to 127

110 to 117

100 to 107

EXP

C P U

DL305

SW1

DL340 only

100 EXP 760 to 767

750 to 757

740 to 747

730 to 737

720 to 727

710 to 717

700 to 707

CPU

EXP

CPU

DL305

NOTE: If a 16pt module is used in Slot 6 for the DL330 or DL330P CPU, 160 through 167 will not be available for control relay assignments. If a 16pt module is used in Slot 6 and/or Slot 7 for a DL340 CPU, 160--167 and/or 170--177 are not available for control relay assignments. Also, even though you are using these points as I/O, you still enter them as C160--C167/C170--C177 in DirectSOFT.

DL305 User Manual, Rev. D

Bases, Expansion Bases and I/O Configuration

700

Jumper SW1

Page 93

Bases, Expansion Bases, and I/O Configuration

Calculating the Power Budget Managing your Power Resource

Bases and Expansion Bases

Bases and Expansion Bases

4--26

WARNING: It is extremely important to calculate the power budget. If you exceed the power budget, the system may operate in an unpredictable manner which may result in a risk of personal injury or equipment damage. Auxiliary Base Power Source

Base Power Specifications Bases, Expansion Bases and I/O Configuration

When you determine the types and quantity of I/O modules you will be using in the DL305 system it is important to remember there is a limited amount of power available from the power supply. We have provided a chart to help you easily see the amount of power available with each base. The following chart will help you calculate the amount of power you need with your I/O selections. At the end of this section you will also find an example of power budgeting and a worksheet for your own calculations. If the I/O you choose exceeds the maximum power available from the power supply you can resolve the problem in one of two ways: S Shift some of the modules to an expansion base which contains another power supply. S If a 5 slot base is being used, replace it with an 8 or 10 slot base. This will provide more power on the 9V and 24V power supplies.

There is 24 VDC available from the 24 VDC output terminals on the bases (except D3--05BDC). The 24 VDC can be used to power external devices or DL305 modules that require external 24 VDC. The power used from this supply reduces the internal system 24 VDC available to the modules by an equal amount. When using the 24 VDC output at the base terminal it is not recommended to exceed 100mA. This chart shows the amount of current available for the three voltages supplied on DL305 bases. Use these currents when calculating the power budget for your system.

Bases

5V Power Supplied in mA

9V Power Supplied in mA

24V Power Supplied in mA

Auxiliary 24 VDC Output at Base Terminal

D3--05B

1400

800

500

Yes

D3--05BDC

1400

800

500

None

D3--08B

1400

1700

600

Yes

D3--10B

1400

1700

600

Yes

NOTE: The total current for the D3--05B and D3--05BDC should not exceed 2.3 Amps. The base currents listed for the D3--08B and the D3--10B are for operating ambient temperatures between 0° C and 50° C.

DL305 User Manual, Rev. D

Page 94

Bases, Expansion Bases, and I/O Configuration

The next three pages show the amount of maximum current required for each of the DL305 modules. The column labeled “External Power Source Required” is for module operation and is not for field wiring. Use these currents when calculating the power budget for your system. If 24 VDC is needed for external devices, the 24 VDC (100mA maximum) output at the base terminal strip may be used as long as the power budget is not exceeded. 5V Power Required in mA

9V Power Required in mA

24V Power Required in mA

External Power Source Required

D3--330

300

50

0

None

D3--330P

300

50

0

None

D3--340

300

20

0

None

F3--OMUX--1

300

0

0

None

F3--OMUX--2

300

0

150

None

F3--PMUX

500

0

0

None

F3--RTU

300

0

0

0

D3--08ND2

0

10

112

None

D3--16ND2--1

0

25

224

None

D3--16ND2--2

0

24

209

None

D3--16ND2F

0

25

224

None

F3--16ND3F

0

148

68

None

D3--08NA--1

0

10

0

None

D3--08NA--2

0

10

0

None

D3--16NA

0

100

0

None

D3--08NE3

0

10

0

None

D3--16NE3

0

130

0

None

Bases and Expansion Bases

Module Power Requirements

4--27

CPUs

Bases and Expansion Bases

Specialty CPUs

DC Input Modules

AC/DC Input Modules

DL305 User Manual, Rev. D

Bases, Expansion Bases and I/O Configuration

AC Input Modules

Page 95

Bases and Expansion Bases

Bases and Expansion Bases

4--28

Bases, Expansion Bases, and I/O Configuration

Module Power Requirements (continued)

5V Power Required in mA

9V Power Required in mA

24V Power Required in mA

External Power Source Required

D3--08TD1

0

20

24

None

D3--08TD2

0

30

0

None

D3--16TD1--1

0

40

96

None

D3--16TD1--2

0

40

96

None

D3--16TD2

0

180

0

None

D3--04TAS

0

12

0

None

F3--08TAS

0

80

0

None

F3--08TAS--1

0

25

0

None

D3--08TA--1

0

96

0

None

D3--08TA--2

0

160

0

None

F3--16TA--2

0

250

0

None

D3--16TA--2

0

400

0

None

D3--08TR

0

360

0

None

F3--08TRS--1

0

296

0

None

F3--08TRS--2

0

296

0

None

D3--16TR

0

480

0

None

D3--04AD

0

55

0

24VDC @ 65mA max

F3--04ADS

0

183

50

None

F3--08AD

0

25

37

None

F3--08TEMP

0

25

37

None

F3--08THM--n

0

50

34

None

F3--16AD

0

33

47

None

D3--02DA

0

80

0

24VDC @ 170mA max

F3--04DA--1

0

144

108

None

F3--04DA--2

0

144

108

None

F3--04DAS

0

154

145

None

DC Output Modules

AC Output Modules

Bases, Expansion Bases and I/O Configuration

Relay Output Modules

Analog

DL305 User Manual, Rev. D

Page 96

Bases, Expansion Bases, and I/O Configuration

4--29

24V Power Required in mA

External Power Source Required

D3--232--DCU

500

0

0

Optional 5VDC @ 500mA

D3--422--DCU

500

0

0

Optional 5VDC @ 500mA

F3--UNICON

0

0

0

(24 VDC or 5 VDC) @ 100mA

F3--AB128--R

0

205

0

None

F3--AB128--T

0

205

0

None

F3--AB128

0

90

0

None

F3--AB64

0

90

0

None

D3--08SIM

0

10

112

None

D3--HSC

0

70

0

None

D3--PWU

800

0

0

Optional 5VDC @ 800mA

D3--HP

50

50

0

Optional

D3--HPP

50

50

0

Optional

Communications and Networking

ASCII BASIC Modules

Bases and Expansion Bases

9V Power Required in mA

Bases and Expansion Bases

5V Power Required in mA

Specialty Modules

Programming

Bases, Expansion Bases and I/O Configuration

DL305 User Manual, Rev. D

Page 97

Bases and Expansion Bases

Bases and Expansion Bases

4--30

Bases, Expansion Bases, and I/O Configuration

Power Budget Calculation Example

The following example shows how to calculate the power budget for the DL305 system.

Base # 1

Module Type

5 VDC (mA)

24 VDC (mA) and/or Auxiliary Base Power Source 24 VDC Output (mA)

9 VDC (mA)

Base Used

D3--05B

1400

800

Slot 1

D3--330

+ 300

+ 50

+

0

Slot 2

D3--16NE3

+

0

+ 130

+

0

Slot 3

D3--16NE3

+

0

+ 130

+

0

Slot 4

F3--16TA--2

+

0

+ 250

+

0

Slot 5

F3--16TA--2

+

0

+ 250

+

0

D3--232--DCU

+ 500

+

+

0

500

Slot 6 Slot 7 Slot 8 Slot 9 Slot 10

Bases, Expansion Bases and I/O Configuration

Other

Maximum power required Remaining Power Available

800 1400 -- 800 = 600 800 -- 630

0

630 = 170 500 -- 0

0 = 500

1. Using the tables at the beginning of the Power Budgeting section of this chapter fill in the information for the Base, CPU, I/O modules, and any other devices that will use system power including devices that use the 24 VDC output. Pay special attention to the current supplied by the base which you have selected since they do differ. Devices which fall into the “Other” category are devices such as the Data Communications Unit and the Handheld programmer which plug onto the CPU. 2. Add the current columns starting with slot 1 and put the total in the row labeled “Maximum power required”. 3. Subtract the row labeled “Maximum power required” from the row labeled “Base Used”. Place the difference in the row labeled “Remaining Power Available”. 4. If “Maximum Power Required” is greater than “Base Used” in any of the three columns, the power budget will be exceeded. It will be unsafe to use this configuration and you will need to restructure your base/module configuration. DL305 User Manual, Rev. D

Page 98

Bases, Expansion Bases, and I/O Configuration

This blank chart is provided for you to copy and use in your power budget calculations.

Base # Module Type

5 VDC (mA)

9 VDC (mA)

24 VDC (mA) and/or Auxiliary Base Power Source 24 VDC Output (mA)

Bases and Expansion Bases

Power Budget Calculation Worksheet

4--31

Base Used Bases and Expansion Bases

Slot 1 Slot 2 Slot 3 Slot 4 Slot 5 Slot 6 Slot 7 Slot 8 Slot 9 Slot 10 Other

Remaining Power Available 1. Using the tables at the beginning of the Power Budgeting section of this chapter fill in the information for the Base, CPU, I/O modules, and any other devices that will use system power including devices that use the 24 VDC output. Pay special attention to the current supplied by the base which you have selected since they do differ. Devices which fall into the “Other” category are devices such as the Data Communications Unit and the Handheld programmer which plug onto the CPU. 2. Add the current columns starting with slot 1 and put the total in the row labeled “Maximum power required”. 3. Subtract the row labeled “Maximum power required” from the row labeled “Base Used”. Place the difference in the row labeled “Remaining Power Available”. 4. If “Maximum Power Required” is greater than “Base Used” in any of the three columns, the power budget will be exceeded. It will be unsafe to use this configuration and you will need to restructure your base/module configuration. DL305 User Manual, Rev. D

Bases, Expansion Bases and I/O Configuration

Maximum power required

Page 99

This page is a scan with no text; see it in the PDF.