The text of a manual · part 13 of 41
DL305 User Manual: Chapter 4: Bases, Expansion Bases, and I/O Configuration, pages 92 to 99
Pages 92 to 99 of 357, from DL305 User Manual
The original document is the PDF (3.4 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the PLC Direct D3-08TD1, PLC Direct D3-16NA, Koyo D3-08TD1 and Koyo D3-16NA
Page 92
4--25
Bases, Expansion Bases, and I/O Configuration
10 Slot Base and 10 Slot Expansion Base with 8 Point I/O
Total I/O: 152 Jumper SW2
Jumper SW1
100 EXP
EXP 100 to 107
SW2 700
060 to 067
050 to 057
040 to 047
030 to 037
020 to 027
010 to 017
000 to 007
DL305
C P U
SW1
100 EXP
EXP 760 to 767
10 Slot Base and 10 Slot Expansion Base with 16 Point I/O
070 to 077
CPU
750 to 757
740 to 747
730 to 737
720 to 727
710 to 717
700 to 707
130 to 137
120 110 to to 127 117
CPU
Bases and Expansion Bases
700
Bases and Expansion Bases
I/O addresses change depending on the point configuration in the local CPU base. Expansion Addresses Depend Notice, when the local CPU base contains only 8 point I/O modules, addresses on Local CPU Base 110--117, 120--127 and 130--137 are available for use in the expansion base. When the local CPU base has 16 point I/O modules, which use the I/O addresses 110--117, Configuration. 120--127 and 130--137, these addresses are taken up and are not available for use in the expansion base.
DL305
Total I/O: 184 Jumper SW2
SW2 700
100 EXP
8 7
6 5
4
3 2
1 0
070 to 077
060 to 067
050 to 057
040 to 047
030 to 037
020 to 027
010 to 017
000 to 007
170 to 177
160 to 167
150 to 157
140 to 147
130 to 137
120 to 127
110 to 117
100 to 107
EXP
C P U
DL305
SW1
DL340 only
100 EXP 760 to 767
750 to 757
740 to 747
730 to 737
720 to 727
710 to 717
700 to 707
CPU
EXP
CPU
DL305
NOTE: If a 16pt module is used in Slot 6 for the DL330 or DL330P CPU, 160 through 167 will not be available for control relay assignments. If a 16pt module is used in Slot 6 and/or Slot 7 for a DL340 CPU, 160--167 and/or 170--177 are not available for control relay assignments. Also, even though you are using these points as I/O, you still enter them as C160--C167/C170--C177 in DirectSOFT.
DL305 User Manual, Rev. D
Bases, Expansion Bases and I/O Configuration
700
Jumper SW1
Page 93
Bases, Expansion Bases, and I/O Configuration
Calculating the Power Budget Managing your Power Resource
Bases and Expansion Bases
Bases and Expansion Bases
4--26
WARNING: It is extremely important to calculate the power budget. If you exceed the power budget, the system may operate in an unpredictable manner which may result in a risk of personal injury or equipment damage. Auxiliary Base Power Source
Base Power Specifications Bases, Expansion Bases and I/O Configuration
When you determine the types and quantity of I/O modules you will be using in the DL305 system it is important to remember there is a limited amount of power available from the power supply. We have provided a chart to help you easily see the amount of power available with each base. The following chart will help you calculate the amount of power you need with your I/O selections. At the end of this section you will also find an example of power budgeting and a worksheet for your own calculations. If the I/O you choose exceeds the maximum power available from the power supply you can resolve the problem in one of two ways: S Shift some of the modules to an expansion base which contains another power supply. S If a 5 slot base is being used, replace it with an 8 or 10 slot base. This will provide more power on the 9V and 24V power supplies.
There is 24 VDC available from the 24 VDC output terminals on the bases (except D3--05BDC). The 24 VDC can be used to power external devices or DL305 modules that require external 24 VDC. The power used from this supply reduces the internal system 24 VDC available to the modules by an equal amount. When using the 24 VDC output at the base terminal it is not recommended to exceed 100mA. This chart shows the amount of current available for the three voltages supplied on DL305 bases. Use these currents when calculating the power budget for your system.
Bases
5V Power Supplied in mA
9V Power Supplied in mA
24V Power Supplied in mA
Auxiliary 24 VDC Output at Base Terminal
D3--05B
1400
800
500
Yes
D3--05BDC
1400
800
500
None
D3--08B
1400
1700
600
Yes
D3--10B
1400
1700
600
Yes
NOTE: The total current for the D3--05B and D3--05BDC should not exceed 2.3 Amps. The base currents listed for the D3--08B and the D3--10B are for operating ambient temperatures between 0° C and 50° C.
DL305 User Manual, Rev. D
Page 94
Bases, Expansion Bases, and I/O Configuration
The next three pages show the amount of maximum current required for each of the DL305 modules. The column labeled “External Power Source Required” is for module operation and is not for field wiring. Use these currents when calculating the power budget for your system. If 24 VDC is needed for external devices, the 24 VDC (100mA maximum) output at the base terminal strip may be used as long as the power budget is not exceeded. 5V Power Required in mA
9V Power Required in mA
24V Power Required in mA
External Power Source Required
D3--330
300
50
0
None
D3--330P
300
50
0
None
D3--340
300
20
0
None
F3--OMUX--1
300
0
0
None
F3--OMUX--2
300
0
150
None
F3--PMUX
500
0
0
None
F3--RTU
300
0
0
0
D3--08ND2
0
10
112
None
D3--16ND2--1
0
25
224
None
D3--16ND2--2
0
24
209
None
D3--16ND2F
0
25
224
None
F3--16ND3F
0
148
68
None
D3--08NA--1
0
10
0
None
D3--08NA--2
0
10
0
None
D3--16NA
0
100
0
None
D3--08NE3
0
10
0
None
D3--16NE3
0
130
0
None
Bases and Expansion Bases
Module Power Requirements
4--27
CPUs
Bases and Expansion Bases
Specialty CPUs
DC Input Modules
AC/DC Input Modules
DL305 User Manual, Rev. D
Bases, Expansion Bases and I/O Configuration
AC Input Modules
Page 95
Bases and Expansion Bases
Bases and Expansion Bases
4--28
Bases, Expansion Bases, and I/O Configuration
Module Power Requirements (continued)
5V Power Required in mA
9V Power Required in mA
24V Power Required in mA
External Power Source Required
D3--08TD1
0
20
24
None
D3--08TD2
0
30
0
None
D3--16TD1--1
0
40
96
None
D3--16TD1--2
0
40
96
None
D3--16TD2
0
180
0
None
D3--04TAS
0
12
0
None
F3--08TAS
0
80
0
None
F3--08TAS--1
0
25
0
None
D3--08TA--1
0
96
0
None
D3--08TA--2
0
160
0
None
F3--16TA--2
0
250
0
None
D3--16TA--2
0
400
0
None
D3--08TR
0
360
0
None
F3--08TRS--1
0
296
0
None
F3--08TRS--2
0
296
0
None
D3--16TR
0
480
0
None
D3--04AD
0
55
0
24VDC @ 65mA max
F3--04ADS
0
183
50
None
F3--08AD
0
25
37
None
F3--08TEMP
0
25
37
None
F3--08THM--n
0
50
34
None
F3--16AD
0
33
47
None
D3--02DA
0
80
0
24VDC @ 170mA max
F3--04DA--1
0
144
108
None
F3--04DA--2
0
144
108
None
F3--04DAS
0
154
145
None
DC Output Modules
AC Output Modules
Bases, Expansion Bases and I/O Configuration
Relay Output Modules
Analog
DL305 User Manual, Rev. D
Page 96
Bases, Expansion Bases, and I/O Configuration
4--29
24V Power Required in mA
External Power Source Required
D3--232--DCU
500
0
0
Optional 5VDC @ 500mA
D3--422--DCU
500
0
0
Optional 5VDC @ 500mA
F3--UNICON
0
0
0
(24 VDC or 5 VDC) @ 100mA
F3--AB128--R
0
205
0
None
F3--AB128--T
0
205
0
None
F3--AB128
0
90
0
None
F3--AB64
0
90
0
None
D3--08SIM
0
10
112
None
D3--HSC
0
70
0
None
D3--PWU
800
0
0
Optional 5VDC @ 800mA
D3--HP
50
50
0
Optional
D3--HPP
50
50
0
Optional
Communications and Networking
ASCII BASIC Modules
Bases and Expansion Bases
9V Power Required in mA
Bases and Expansion Bases
5V Power Required in mA
Specialty Modules
Programming
Bases, Expansion Bases and I/O Configuration
DL305 User Manual, Rev. D
Page 97
Bases and Expansion Bases
Bases and Expansion Bases
4--30
Bases, Expansion Bases, and I/O Configuration
Power Budget Calculation Example
The following example shows how to calculate the power budget for the DL305 system.
Base # 1
Module Type
5 VDC (mA)
24 VDC (mA) and/or Auxiliary Base Power Source 24 VDC Output (mA)
9 VDC (mA)
Base Used
D3--05B
1400
800
Slot 1
D3--330
+ 300
+ 50
+
0
Slot 2
D3--16NE3
+
0
+ 130
+
0
Slot 3
D3--16NE3
+
0
+ 130
+
0
Slot 4
F3--16TA--2
+
0
+ 250
+
0
Slot 5
F3--16TA--2
+
0
+ 250
+
0
D3--232--DCU
+ 500
+
+
0
500
Slot 6 Slot 7 Slot 8 Slot 9 Slot 10
Bases, Expansion Bases and I/O Configuration
Other
Maximum power required Remaining Power Available
800 1400 -- 800 = 600 800 -- 630
0
630 = 170 500 -- 0
0 = 500
1. Using the tables at the beginning of the Power Budgeting section of this chapter fill in the information for the Base, CPU, I/O modules, and any other devices that will use system power including devices that use the 24 VDC output. Pay special attention to the current supplied by the base which you have selected since they do differ. Devices which fall into the “Other” category are devices such as the Data Communications Unit and the Handheld programmer which plug onto the CPU. 2. Add the current columns starting with slot 1 and put the total in the row labeled “Maximum power required”. 3. Subtract the row labeled “Maximum power required” from the row labeled “Base Used”. Place the difference in the row labeled “Remaining Power Available”. 4. If “Maximum Power Required” is greater than “Base Used” in any of the three columns, the power budget will be exceeded. It will be unsafe to use this configuration and you will need to restructure your base/module configuration. DL305 User Manual, Rev. D
Page 98
Bases, Expansion Bases, and I/O Configuration
This blank chart is provided for you to copy and use in your power budget calculations.
Base # Module Type
5 VDC (mA)
9 VDC (mA)
24 VDC (mA) and/or Auxiliary Base Power Source 24 VDC Output (mA)
Bases and Expansion Bases
Power Budget Calculation Worksheet
4--31
Base Used Bases and Expansion Bases
Slot 1 Slot 2 Slot 3 Slot 4 Slot 5 Slot 6 Slot 7 Slot 8 Slot 9 Slot 10 Other
Remaining Power Available 1. Using the tables at the beginning of the Power Budgeting section of this chapter fill in the information for the Base, CPU, I/O modules, and any other devices that will use system power including devices that use the 24 VDC output. Pay special attention to the current supplied by the base which you have selected since they do differ. Devices which fall into the “Other” category are devices such as the Data Communications Unit and the Handheld programmer which plug onto the CPU. 2. Add the current columns starting with slot 1 and put the total in the row labeled “Maximum power required”. 3. Subtract the row labeled “Maximum power required” from the row labeled “Base Used”. Place the difference in the row labeled “Remaining Power Available”. 4. If “Maximum Power Required” is greater than “Base Used” in any of the three columns, the power budget will be exceeded. It will be unsafe to use this configuration and you will need to restructure your base/module configuration. DL305 User Manual, Rev. D
Bases, Expansion Bases and I/O Configuration
Maximum power required