Page 120

Discrete Input Modules

Internal Power Sources

--

+V TTL

+

+VCC

Discrete Input Modules

Common

5VDC -- +

6--9

To other 12 or 4 circuits

15VDC 12-24 VDC

Source Sink 4.7k

Optical Coupler

Input Jumper selected for 12--24VDC, sinking load configuration

Common Internal Power Sources 12-24 VDC

5VDC -- + --

+V TTL

+

+VCC

To other 12 or 4 circuits

15VDC 12-24 VDC

Source Sink Optical Coupler

Input Jumper selected for sourcing load configuration. An external power supply must be used in this configuration.

The DC power to sense the state of the inputs when jumpers are installed for sinking type signals is provided by the rack power supply. Sinking type inputs are turned ON by switching the input circuit to common. Source type input signals assume the ON state until the input device provides the voltage to turn the input OFF. Selection of Operating Mode: The mode of operation, either 5VDC or 12--24VDC sink or source, for each group of circuits is determined by the position of jumper plugs on pins located on the edge of the circuit board. There are four sets of pins (3 pins in each set), with two sets for each group of inputs. The first two sets of pins are used to configure the first 12 inputs (eg. 0 to 7 and 100 to 103) and are labeled 12 CIRCUITS. Above the first set of pins are the labels 12/24V and 5V. Above the second set of pins are the labels SINK and SRC (source). To select an operating mode for the first 12 circuits, place a jumper on the two pins nearest the appropriate labels. For example, to select 24VDC Sink input operation for the first 12 inputs, place a jumper on the two pins labeled 12/24V and on the two pins labeled SINK. The last two sets of pins are used to configure the last 4 inputs (eg. 104 to 107) and are labeled 4 CIRCUITS. The operating mode selected for the last group of 4 inputs can be different than the mode chosen for the first group of 12 inputs. Correct module operation requires each set of three pins have a jumper installed (four jumpers total). NOTE: When a group of inputs are used with TTL logic, select the SINK operating mode for that group. “Standard” TTL can sink several milliamps but can source less than 1 mA.

DL305 User Manual, Rev. D

Discrete Input Modules

4.7k

Page 121

6--10

Discrete Input Modules

Discrete Input Modules

D3--08NA--1, 110 VAC Input Module Inputs per module Commons per module Input voltage range Input voltage supply Peak voltage AC frequency ON voltage level OFF voltage level Input impedance Input current

8 2 (isolated) 85--132VAC External 132VAC 47--63 Hz >80 VAC <20 VAC 10 K ohm 15 mA @ 50 Hz 18 mA @ 60 Hz

Minimum ON current Maximum OFF current Base power required

8 mA 2 mA 9V 10 mA Max 24V N/A

OFF to ON response ON to OFF response Terminal type Status indicators Weight

10--30 ms 10--60 ms Non--removable Field side 5 oz. (140 g)

Derating Chart for D3--08NA--1

Discrete Input Modules

Points 8

110VAC INPUT D3--08NA--1

0

4

1

5

2

6

C1

3

7

0

1

C 1

2

3

0 1

4

5

2 3

6

7

4 5

110VAC

6 4 2 0 0 32

110VAC Common Line

6 7 110VAC

DL305 User Manual, Rev. D

2.2k

0.33μF

Optical Coupler

9V

C2 C 2

10 20 30 40 50 60°C 50 68 86 104 122 140°F Ambient Temperature (°C/°F)

Input

Page 122

Discrete Input Modules

6--11

D3--08NA--2, 220 VAC Input Module 8 2 (isolated) 180--265VAC External 265 VAC 50--60Hz >180 VAC < 40 VAC 18 K ohm 13 mA @ 50 Hz 18 mA @ 60 Hz

Minimum ON current Maximum OFF current Base power required

10 mA 2 mA 9V 10 mA max 24V N/A

OFF to ON response ON to OFF response Terminal type Status indicators Weight

5--50 ms 5--60 ms Non--removable Field side 5 oz. (140 g)

Discrete Input Modules

Inputs per module Commons per module Input voltage range Input voltage supply Peak voltage AC frequency ON voltage level OFF voltage level Input impedance Input current

Derating Chart for D3--08NA--2 Points 220VAC INPUT

180--265VAC Line Neut

C1

0

4

1

5

2

6

3

7

Discrete Input Modules

8

D3--08NA--2

6 4 2

0

1

C 1

2

3

0 1

4

5

2 3

6

7

4 5

0 0 32

10 20 30 40 50 60°C 50 68 86 104 122 140°F Ambient Temperature (°C/°F) 270

185--265 VAC Line

Common

Optical Coupler

6 7 Line Neut 180--265VAC

9V

C2 C 2

470K Input

1K .15μF

DL305 User Manual, Rev. D

Page 123

6--12

Discrete Input Modules

Discrete Input Modules

D3--16NA, 110 VAC Input Module Inputs per module Commons per module Input voltage range Input voltage supply Peak voltage AC frequency ON voltage level OFF voltage level Input impedance Input current

16 2 (isolated) 80--132VAC External 132VAC 50--60 Hz >80 VAC <15 VAC 8 K ohm 16 mA @ 50 Hz 25 mA @ 60 Hz

Minimum ON current Maximum OFF current Base power required*

8 mA 1.5 mA 9V 6.25 mA Max/ON pt. 100mA max

OFF to ON response ON to OFF response Terminal type Status indicators Weight

5--50 ms 5--60 ms Removable Logic side 6.4 oz. (180 g)

* 9V typical values are 4 mA/ON pt., 64 mA total

Derating Chart for D3--16NA Discrete Input Modules

Points 16

110VAC INPUT D3--16NA

I 80--132VAC Common

CI 0

Line

2 4

80--132VAC Common Line

6 CII 1 3 5 7

I 1 3 5 7 0 2 4 6

DL305 User Manual, Rev. D

0 2 4 6 C 1 3 5 7

0 1 2 3

4 5 6 7

0 1 2 3

4 5 6 7

12 II 8 4

C 0

1

0 32

3

10 20 30 40 50 60°C 50 68 86 104 122 140°F Ambient Temperature (°C/°F)

5 7 0 2 4

110VAC Line

Common

9V

Other 7 Circuits

0.33μF

6 II

Input 150k

Optical Coupler

Page 124

Discrete Input Modules

6--13

D3--08NE3, 24 VAC/DC Input Module 8 (sink/source) 2 (isolated) 20--28 VAC/VDC External 28 VAC/VDC 47--63 Hz >20 V <6V 1.5 K ohm 19 mA Max 10 mA 2 mA

Base power required

9V 10 mA max 24V N/A

OFF to ON response

AC: 5--50 ms DC: 6--30 ms

ON to OFF response Terminal type Status indicators Weight

AC/DC: 5--60 ms Non--removable Field side 4.2 oz. (120 g)

Discrete Input Modules

Inputs per module Commons per module Input voltage range Input voltage Peak voltage AC frequency ON voltage level OFF voltage level Input impedance Input current Minimum ON current Maximum OFF current

Derating Chart for D3--08NE3 Points 8

24VAC/DC INPUT 0

4

1

5

2

6

C1

3

7

0

1

C 1

2

3

0 1

4

5

2 3

Common 24VAC/DC

6

6 4 2 0 0 32 24VAC

4 5

+

10 20 30 40 50 60°C 50 68 86 104 122 140°F Ambient Temperature (°C/°F) 270 LED

+24VDC

7

Discrete Input Modules

D3--08NE3

--

Common

Optical Coupler

9V

6 7

+ --

-+

24VAC/DC

C2 Common

C 2 Input

1.5k Sinking Module Configuration

NOTE: This module can be wired in a sourcing configuration and it will be operational except there will be no module LED indication for each input.

DL305 User Manual, Rev. D

Page 125

6--14

Discrete Input Modules

Discrete Input Modules

D3--16NE3, 24 VAC/DC Input Module Inputs per module Commons per module Input voltage range Input voltage supplied Peak voltage AC frequency ON voltage level OFF voltage level Input impedance Input current Minimum ON current Maximum OFF current

16 (sink/source) 2 (isolated) 14--30VAC/VDC External 30 VAC/VDC 47--63 Hz >14 V <3 V 1.8 K ohm 16 mA Max 7 mA 2 mA

Base power required

9V 2.5 mA.+4.5mA/ ON pt.(130 mA max) 24V N/A

OFF to ON response

AC 5--30 ms DC 5--25 ms

ON to OFF response

AC 5--30 ms DC 5--25 ms

Terminal type Status indicators Weight

Removable Logic side 6 oz. (170 g)

Derating Chart for D3--16NE3 Points 16

Discrete Input Modules

24VAC/DC INPUT D3--16NE3

I 24VAC Common

CI 0

Line

2 4

24VDC Common

6 CII 1

24VDC

3 5 7

I 1 3 5 7 0 2 4 6

0 2 4 6 C 1 3 5 7

0 1 2 3

4 5 6 7

0 1 2 3

4 5 6 7

12 II

16 circuits ON Vin=18V Vin=30V

8

10 circuits ON

Vin=24V

4 0

C

0 10 20 30 40 50 60°C 32 50 68 86 104 122 140°F Ambient Temperature (°C/°F)

1 3 5

9V

7

Common

0 2

24VAC 24VDC

4 6 II

1.8k Input

Sinking Module Configuration

DL305 User Manual, Rev. D

7 circuits ON 5 circuits ON

Optical Coupler

Page 126

Discrete Input Modules

6--15

D3--08SIM, Input Simulator 8 10mA @ 9VDC 112mA max @ 24VDC

OFF to ON response

4--15 ms

ON to OFF response

4--15 ms

Terminal type

None

Status indicators

Switch side

Weight

3.0 oz. (85 g)

Discrete Input Modules

Inputs per module Base Power required

INPUT SIMULATOR D3--08SIM

4

1

5

2

6

3

7

Discrete Input Modules

0

0 1 2 3 4 5 6 7

DL305 User Manual, Rev. D

Page 127

This page is a scan with no text; see it in the PDF.