DL305 User Manual: Chapter 7: Discrete Output Modules, pages 128 to 135

Pages 128 to 135 of 357, from DL305 User Manual

The original document is the PDF (3.4 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the PLC Direct D3-08TD1, PLC Direct D3-16NA, Koyo D3-08TD1 and Koyo D3-16NA

Page 128

Discrete Output Modules

17

In This Chapter. . . ., Discrete Output Module Identification and Terminology, Relay Arc Suppression -- DC and AC Applications, D3--08TD1, 24 VDC Output Module, D3--08TD2, 24 VDC Output Module, D3--16TD1--1, 24 VDC Output Module, D3--16TD1--2, 24 VDC Output Module, D3--16TD2, 24 VDC Output Module, D3--04TAS, 110--220 VAC Output Module, F3--08TAS, 250 VAC Isolated Output Module, F3--08TAS--1, 125 VAC Isolated Output Module, D3--08TA--1, 110--220 VAC Output Module, D3--08TA--2, 110--220 VAC Output Module, F3--16TA--2, 20--125 VAC Output Module, D3--16TA--2, 110--220 VAC Output Module, D3--08TR, Relay Output Module, F3--08TRS--1, Relay Output Module, F3--08TRS--2, Relay Output Module, D3--16TR, Relay Output Module

Page 129

7--2

Discrete Output Modules

Discrete Output Module Identification and Terminology Discrete Output Module Status Indicators

This chapter contains I/O specification sheets for the DL305/FL305 discrete output modules. The following diagram shows the status indicator location for some of the most common discrete output modules.

Discrete Output Modules

Squeeze Tab

Squeeze Tab Removable Cover

Color Coding of I/O The DL305 family of I/O modules has a color coding scheme to help you identify whether the module is an input module, an output module or a special module. This Modules is done through a color bar indicator located on the front of each module below the part number. The following color scheme is used. Color Bar

´

110VAC INPUT D3--16NA I

Discrete Output Modules

I 0 2 4 6 C 1 3 5 7

Output Modules Selection

0 4 1 5 2 6 3 7 C 1 3 5 7 0

0 4 1 5 2 6 3 7

II

Color Code Module Type Discrete/Analog Output Red Discrete/Analog Input Blue White Other

2 4 6 II

Your output module selection depends on the field devices used and system performance requirements. The output module specifications in this chapter list the information which is needed for choosing the correct module for a field device and to assure it meets the system requirements. The following list defines the specifications listed in this chapter.

DL305 User Manual, Rev. D

Page 130

Discrete Output Modules

7--3

Outputs Per Module

Indicates number of output points per module and designates current sinking, current sourcing, or either.

Commons Per Module Operating Voltage

Number of commons per module and their electrical characteristics.

Output Type

The output circuit can be a transistor, a triac, or a relay. The NPN or PNP transistor outputs are normally used in low voltage or high speed DC applications. Triac outputs are used in AC voltage applications. The Form A or C relay outputs are normally used where a wide voltage range is needed. Relay output modules are capable of carrying more current than a transistor or a triac output and can pass AC or DC voltages. The disadvantage of a relay module is the internal power consumption and the relay life expectancy.

Peak Voltage

Maximum voltage the output circuit can control.

AC Frequency

AC modules are designed to operating within a specific frequency range. 60 Hz is the standard AC frequency in the U.S., 50 Hz is common in other countries.

ON Voltage Drop

The voltage between the output point and common during an active ON with a load.

Maximum Current (Resistive) Maximum Leakage Current Maximum Inrush Current

The maximum current for an output with a resistive load.

Minimum Load

The minimum load across the output’s circuit for the circuit to operate properly.

Base Power Required

Power from the base power supply is used by the DL305 output modules and varies between different modules. The guidelines for using module power is explained in the power budget configuration section in chapter 4.

OFF to ON Response Time ON to OFF Response Time Terminal Type

The processing time the module requires to transition from an OFF to ON state.

Status Indicators

LEDs indicate the ON/OFF status of an input point. These LEDs are electrically located on either the logic side or the field device side of the output circuit.

Fuses

Indicates the current rating of the replaceable or non-replaceable fuse(s).

Relay Life

Amount of closures typical for a relay point before failure.

Weight

Indicates the weight of the module.

The operating voltage range of the output circuit.

Discrete Output Modules

The maximum current of the output circuit during an OFF state. The maximum current over a short period of time during the OFF to ON transition of a output point. It is greater than the normal ON state current and depends on the field device electrical characteristics.

Indicates whether the terminal type is a removable or non-removable connector or terminal.

DL305 User Manual, Rev. D

Discrete Output Modules

The processing time the module requires to transition from an ON to OFF state.

Page 131

7--4

Discrete Output Modules

Discrete Output Modules

Relay Arc Suppression -- DC and AC Applications FL305 High Current This application note describes the addition of external contact protection to high current isolated relay output modules. It supplements the wiring information for the Relay Output F3--08TRS--1 and F3--08TRS--2 relay output modules. Module Arc Suppression Adding external contact protection may extend a relays life beyond the number of operations listed. High current inductive loads such as clutches, brakes, motors, direct acting solenoid valves, and motor starters will benefit the most from external contact protection. Resistor and C (μF) = I2 / 10 Capacitor where x = (1 + 50 / E) R (Ω) = V / 10 Ix Selection Use peak AC values for I and V, see ”Peak Voltage and Current” below. Where I = Amperes of load current immediately prior to opening of contacts. Where E = Source voltage immediately prior to closing of contacts. R minimum = 0.5 Ω, 1/2 W C minimum = 0.001 μF, the voltage rating of C must be ≥ E Resistor Tolerance For E < 70V, R may be 3 times indicated value. For 70V < E < 100V, R may be 50% indicated value. For 100V < E < 150V,R may be 10% indicated value. For E > 150V, R may be 5% indicated value.

Discrete Output Modules

Peak Voltage and Current

The following equations can be used to determine Ipeak and V peak: Ipeak = Irms / .707

Alternating Current

Vpeak = Vrms / .707 Ipeak = Iave / .636 Adding Contact Protection

DC Rectified Alternating Current

If the contact is switching a DC inductive load, add a diode across the load as near to load coil as possible. Add the RC network across the relay contacts as close to the relay as possible.

DL305 User Manual, Rev. D

Page 132

Discrete Output Modules Resistor and Capacitor Nomogram

7--5

The nomogram shown below affords a convenient method of selecting the proper contact protection for P & B relays used in F3-08TRS-1 and F3-08TRS-2 modules. Example: Use a current (1) of 1.0 ampere and a voltage (E) of 50 volts. Capacitance (C ) in microfarads is found directly on the left side scale, opposite 1.0 amperes as 0.1. Resistance (R) in ohms is obtained using a straight edge. Locate 1.0 amperes (I) on the left side scale and 50 volts (E) on the center scale. Place the straightedge on these points. The junction of the straight edge and the right side determines R. In this example R is equal to 5.0 ohms.

R

I

10,000 10

8,000

8

6,000 4,000 3,000

C

CURRENT AMPERES

3

.8 .6 .4

2

.3 .2

.1

1

.08

600 400 300

.6

200

5 6

.02

E 8

.4 .01 .008

800

.3

LOAD VOLTAGE

10

.004

300 200

20 30

.006

500 400

50

100

.2

.003 .002

.001

100 80 60

40 30 20

.1 .08

10

.06

8 6

.04 4 .03 3 .02

2

1 .01

(1) C = 12 / 10 microfarads (2) R = E / 10 Ix ohms

For DC. For AC, use peak values Where x = (1 + 50/E)

DL305 User Manual, Rev. D

Discrete Output Modules

CAPACITOR MICROFARADS

.03

1,000

.8

.06 .04

2,000

RESISTANCE OHMS

1.0

4

Discrete Output Modules

6

Page 133

7--6

Discrete Output Modules

D3--08TD1, 24 VDC Output Module

Discrete Output Modules

Outputs per module Commons per module Operating voltage Output type

8 (current sinking) 2(internally connected) 5--24VDC NPN (open collector)

Peak voltage AC frequency ON voltage drop Max current

45VDC N/A 0.8V @ 0.5A 0.5A / point 1.8 / common

Max leakage current Max inrush current

0.1 mA @ 40VDC 3A / 20ms 1A / 100ms

Minimum load Base power required

1 mA 9V 20 mA Max 24V 3mA/pt. (24mA Max)

OFF to ON response ON to OFF response Terminal type Status indicators Weight Fuses

0.1 ms 0.1 ms Non-removable Logic Side 4.2 oz. (120 g) (2) One 3A per common Non--replaceable

Derating Chart for D3--08TD1 Points

8

24VDC OUTPUT D3--08TD1

0

4

1

5

2

6

C1

3

7

Internally Connected

5--24VDC + --

6 4 2

L L

0

1

C 1

L

2

3

0 1

4

5

2 3

6

7

4 5

0 0 32

Discrete Output Modules

L

L

L

10 20 30 40 50 60°C 50 68 86 104 122 140°F Ambient Temperature (°C/°F)

Output

L L

Optical Coupler

L

6 7

C2 C 2

3A Common + -5--24VDC

DL305 User Manual, Rev. D

24VDC -- + Internal Power Supply

9V

Page 134

7--7

Discrete Output Modules

D3--08TD2, 24 VDC Output Module 8 (current sourcing) 2 (internally connected) 5--24VDC NPN Transistor (emitter follower)

Peak voltage AC frequency ON voltage drop Max current

40VDC N/A 1V @ 0.5A 0.5A / point 1.8A/ common

Max leakage current Max inrush current

0.1 mA @ 24VDC 3A / 20ms 1A / 100ms

Minimum load Base power required

1 mA 9V 30 mA Max 24V N/A

OFF to ON response ON to OFF response Terminal type Status indicators Weight Fuses

0.1 ms 0.1 ms Non-removable Logic Side 4.2 oz. (120 g) (2) One 3A per common Non--replaceable

Derating Chart for D3--08TD2

24VDC OUTPUT D3--08TD2

5--24VDC -- +

0

4

1

5

2

6

Internally Connected

3

7

C1

C 1

Points 8 6 4 2 0

L

0

1

0 1

L

2

3

2 3

L

4

5

6

7

L L L

4 5

5--24VDC -- +

3A Common

Optical Coupler

6 7 C 2

L

Output

C2

DL305 User Manual, Rev. D

9V

Discrete Output Modules

0 10 20 30 40 50 60°C 32 50 68 86 104 122 140°F Ambient Temperature (°C/°F)

L

L

Discrete Output Modules

Outputs per module Commons per module Operating voltage Output type

Page 135

7--8

Discrete Output Modules

D3--16TD1--1, 24 VDC Output Module

Discrete Output Modules

Outputs per module Commons per module Operating voltage Output type

16 (current sinking) 2 (internally connected) 5--24VDC NPN transistor (open collector) 45VDC N/A 2V @ 0.5A 0.5A/ point 2A/ common

Peak voltage AC frequency ON voltage drop Max current Max leakage current Max inrush current

0.1mA @ 40VDC 3A / 20 ms 1A / 100 ms

Minimum load Base power required

1 mA 9V (40 mA Max) 3mA+2.3mA/ON pt. 24V 6 mA/ON pt. (96 mA Max)

OFF to ON response ON to OFF response Terminal type Status indicators Weight Fuses

0.1 ms 0.1 ms Removable Logic Side 5.6 oz. (160 g) (2) One 3A per common Non-replaceable

Derating Chart for D3--16TD1--1 Points 16

24VDC OUTPUT D3--16TD1--1

Internally Connected 5--24VDC + --

CI 0

L L

2

L L

4

Discrete Output Modules

L L

5--24VDC + --

6

L L

CII

L L

1

L L

3

L

5

L

7

L

L

I

I 1 3 5 7 0 2 4 6

DL305 User Manual, Rev. D

0 2 4 6 C 1 3 5 7

0 1 2 3

4 5 6 7

0 1 2 3

4 5 6 7

II

12

0.25A 0.35A

8 0.5A

4

C

0

1

0 10 20 30 40 50 60°C 32 50 68 86 104 122 140°F Ambient Temperature (°C/°F)

3 5 7

24VDC 9V

0 2 4

L

3A

6 II

Output

+ -5--24VDC

Common