DL305 User Manual: Chapter 11: Instruction Set, pages 250 to 259

Pages 250 to 259 of 357, from DL305 User Manual

The original document is the PDF (3.4 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the PLC Direct D3-08TD1, PLC Direct D3-16NA, Koyo D3-08TD1 and Koyo D3-16NA

Page 250

11--11

Instruction Set Boolean Instructions

The And Timer instruction logically ands a normally open timer contact in series with another contact in a rung. The timer contact T aaa will be on when the timer current value ² the preset value of the associated timer.

And Not Timer (AND NOT TMR) DL330/340 Only

The And Not Timer instruction logically ands a normally closed timer contact in series with another contact in a rung. The timer contact T aaa will be on when the timer current value is < the preset value of the associated timer. Data Type

Timer

T

T aaa

Instruction Set

And Timer (AND TMR) DL330/340 Only

T aaa

D3--330 Range

D3--340 Range

D3--330P Range* aaa aaa aaa

600--677

600--677

----

* See Chapter 12 for similar RLL PLUS instructions In the following And Timer example, when input 000 is on and the current value in timer 604 is ² the preset value output 050 will energize. DirectSOFT Display 000

Handheld Programmer Keystrokes T604

050 OUT

STR AND OUT

SHF TMR SHF

0 SHF 5

ENT 6 0

0 ENT

4

ENT

In the following And Not Timer example, when input 000 is on and the current value in timer 604 is < the preset value output 050 will energize. DirectSOFT Display 000

Handheld Programmer Keystrokes T 604

050 OUT

STR AND OUT

SHF NOT SHF

0 TMR 5

ENT SHF 0

6 ENT

0

DL305 User Manual, Rev. D

4

ENT

Page 251

Instruction Set

11--12

Instruction Set Boolean Instructions

And Counter (AND CNT) DL330/340 Only

The And Counter instruction logically ands a normally open counter contact in series with another contact in a rung. The counter contact C aaa will be on when the counter current value is ² the preset value of the associated counter.

And Not Counter (AND NOT CNT) DL330/340 Only

The And Not Counter instruction logically ands a normally closed counter contact in series with another contact in a rung. The counter contact C aaa will be on when the counter current value is < the preset value of the associated counter. Data Type

Counter

C

C aaa

C aaa

D3--330 Range

D3--340 Range

D3--330P Range aaa aaa aaa

600--677

600--677

----

* See Chapter 12 for similar RLL PLUS instructions In the following And Counter example, when input 002 is on and the current value in counter 602 is ² the preset value output 050 will energize. DirectSOFT Display 002

Handheld Programmer Keystrokes C 602

050 OUT

STR AND OUT

SHF CNT SHF

2 SHF 5

ENT 6 0

0 ENT

2

ENT

In the following And Not Counter example, when input 002 is on and the current value in counter 602 is < the preset value output 050 will energize. DirectSOFT Display 002

Handheld Programmer Keystrokes C 602

050 OUT

DL305 User Manual, Rev. D

STR AND OUT

SHF NOT SHF

2 TMR 5

ENT SHF 0

6 ENT

0

2

ENT

Page 252

11--13

Instruction Set Boolean Instructions

Or Store (OR STR)

The And Store instruction logically ands two branches of a rung in series. Both branches must begin with the Store instruction.

OUT

The Or Store instruction logically ors two branches of a rung in parallel. Both branches must begin with the Store instruction.

OUT

In the following And Store example, the branch consisting of contacts 000 and 002 have been anded with the branch consisting of contacts 001 and 003. DirectSOFT Display 000

Handheld Programmer Keystrokes 001

010 OUT

002

003

STR OR STR OR

SHF SHF SHF SHF

0 2 1 3

ENT ENT ENT ENT

AND OUT

STR SHF

ENT 1

0

ENT

In the following Or Store example, the branch consisting of 000 and 001 have been ored with the branch consisting of 002 and 003. DirectSOFT Display 000

Handheld Programmer Keystrokes 001

010 OUT

002

003

STR AND STR AND

SHF SHF SHF SHF

0 1 2 3

ENT ENT ENT ENT

OR OUT

STR SHF

ENT 1

0

ENT

DL305 User Manual, Rev. D

Instruction Set

And Store (AND STR)

Page 253

11--14

Instruction Set Boolean Instructions

Instruction Set

There are limits to what you can enter with these simple boolean instructions. This is because the DL305 CPUs use an 8-level stack to evaluate the various logic elements. The stack is a temporary storage area that helps solve the logic for the rung. Each time you enter a Store instruction, the instruction is placed on the top of the stack. Any other instructions on the stack are pushed down a level. The And, Or, And Store, and Or Store instructions combine levels of the stack when they are encountered. Since the stack is only eight levels, an error will occur if the CPU encounters a rung that uses more than the eight levels of the stack. The following example shows how the stack is used to solve simple boolean logic.

000

001

STR

STR

STR

ORSTR

AND 004

050

Output

OUT 002 AND 003

005

ANDSTR

OR

¡ STR 000

© STR 001

¢ STR 002

£ AND 003

1

1

STR 001

1

STR 002

1

002 AND 003

2

2

STR 000

2

STR 001

2

STR 001

3

3

3

STR 000

3

STR 000

4

4

4

4

5

5

5

5

6

6

6

6

7

7

7

7

8

8

8

8

STR 000

¤ ORSTR

¥ AND 004

¦ OR 005

1

001 OR (002 AND 003)

1

004 AND [001 OR (002 AND 003)]

1

005 OR 004 AND [001 OR (002 AND 003)]

2

STR 000

2

STR 000

2

STR 000

3

3 S S

3 S S

8

8

§ ANDSTR 1

000 AND (005 OR 004) AND [001 OR (002 AND 003)]

2 3 S S

8

DL305 User Manual, Rev. D

S S

8

Page 254

Instruction Set Boolean Instructions

The Out instruction reflects the status of the rung (on/off) and outputs the discrete (on/off) state to the specified image register point or memory location. Multiple Out instructions referencing the same discrete location should not be used because only the last Out instruction in the program will control the physical output point. Data Type aaa OUT

D3--330 Range

D3--340 Range aaa aaa

D3--330P Range aaa

Outputs

000--167 700--767

000--177 700--767

000--167 700--767

Control Relays

160--373

160--373 1000--1067

160--174 200--77

Shift Register Bits

400--577

400--577

----

In the following Out example, when input 000 is on output 010 will energize. DirectSOFT Display

Handheld Programmer Keystrokes

000

010 OUT

STR OUT

SHF SHF

0 1

ENT 0

ENT

In the following Out example, two Out instructions using output 10 are used in the program. The status of output 010 being controlled by input 001 will override the instance of output 010 being controlled by input 000. The physical output would always be controlled by input 001. 000

010 OUT

O

O

O

001

O

010 OUT

DL305 User Manual, Rev. D

Instruction Set

Out (OUT)

11--15

Page 255

Instruction Set

11--16

Instruction Set Boolean Instructions

Set (SET) DL330/340 Only

The Set instruction sets or turns on an output. Once the output is set it will remain on until it is reset using the Reset instruction. It is not necessary for the input controlling the Set instruction to remain on. The Set instruction is sometimes known as a latch. The Reset instruction is used to reset the output.

Reset (RST) DL330/340 Only

The Reset instruction resets or turns off an output. Once the output is reset it is not necessary for the input to remain on. The Reset instruction is sometimes known as an unlatch instruction. Data Type aaa SET aaa RST

D3--330 Range

D3--340 Range

D3--330P Range* aaa aaa aaa

Outputs

000--167 700--767

000--177 700--767

----

Control Relays

160--373

160--373 1000--1067

----

Shift Register Bits

400--577

400--577

----

* See Chapter 12 for similar RLL PLUS instructions In the following Set example, when input 000 is on output 010 will be energized. DirectSOFT Display 000

Handheld Programmer Keystrokes 010 SET

STR SET

SHF SHF

0 1

ENT 0

ENT

In the following Reset example, when input 001 is on output 010 will de--energize. DirectSOFT Display 001

Handheld Programmer Keystrokes 010 RST

DL305 User Manual, Rev. D

STR RST

SHF SHF

1 1

ENT 0

ENT

Page 256

Instruction Set Boolean Instructions

The Set Out instruction reflects the status of the rung (on/off) and outputs the discrete (on/off) state to the specified image register location. This instruction is similar to the Out instruction except the output disable coil (special relay 376) will not override and disable the output. Multiple Set Out instructions referencing the same discrete location should not be used because only the last Set Out instruction in the program will control the physical output point. Data Type

Outputs aaa

Instruction Set

Set Out (SET OUT)

11--17

SET OUT

D3--330 Range

D3--340 Range

D3--330P Range aaa aaa aaa

000--167 700--767

000--177 700--767

000--167 700--767

In the following Set Out example, when input location 000 is on output 020 will energize. The output disable coil (special relay 376) will not override this output coil. DirectSOFT Display 000

Handheld Programmer Keystrokes 020 SET OUT

STR SET

SHF OUT

0 SHF

ENT 2

0

ENT

DL305 User Manual, Rev. D

Page 257

Instruction Set

11--18

Instruction Set Boolean Instructions

Set Out Reset (SET OUT RST)

The Set Out Reset instruction is typically known as a one shot. When the input logic produces an off to on transition the output will turn on for one CPU scan.

Data Type aaa OUT RST

D3--330 Range

D3--340 Range aaa aaa

D3--330P Range aaa

Outputs

000--167 700--767

000--177 700--767

000--167 700--767

Control Relays

160--373

160--373 1000--1067

160--174 200--77

In the following Set Out Reset example, when input 007 transitions from off to on, control relay 160 will energize for the remainder of the CPU scan. DirectSOFT Display 007

Handheld Programmer Keystrokes 160 OUT RST

DL305 User Manual, Rev. D

STR SHF 7 SET OUT RST

ENT SHF

1

6

0

ENT

Page 258

11--19

Instruction Set Comparative Boolean Instructions

Comparative Boolean Instructions The Store If Equal instruction begins a new rung or additional branch in a rung with a normally open comparative counter contact. The contact will be on if the specified counter CT aaa = B bbbb.

CTaaa

Instruction Set

Store If Equal (STR) DL330/DL340 Only

B bbbb

CT

Store Not If Equal (STR NOT) DL330/DL340 Only

The Store Not If Equal instruction begins a new rung or additional branch in a rung with a normally closed comparative counter contact. The contact will be on if the specified counter CT aaa ¸ B bbbb. Operand Data Type

Counters

CT aaa

D3--330 Range

B bbbb

D3--340 Range

D3--330P Range*

B aaa bbbb aaa bbbb aaa bbbb

CT

600--677

----

600--677

----

----

----

----

400--577

----

400--577 700--777

----

----

----

0--9999

----

0--9999

----

----

Data registers

R

Constant

K

* See Chapter 12 for similar RLL PLUS instructions In the following Store If Equal example, when CT600 = 2510 output 012 will energize. DirectSOFT Display CT600

K2510

Handheld Programmer Keystrokes 012 OUT

STR SHF

SHF 2

6 5

0 1

0 0

ENT ENT

OUT

SHF

0

1

2

ENT

In the following Store Not If Equal example, when CT600 is ¸ the value in R400 output 020 will energize. DirectSOFT Display CT600

R400

Handheld Programmer Keystrokes 020 OUT

STR R

NOT 4

SHF 0

6 0

0 ENT

0

OUT

SHF

0

1

2

ENT

ENT

DL305 User Manual, Rev. D

Page 259

Instruction Set

11--20

Instruction Set Comparative Boolean Instructions

Or If Equal (OR) DL330/DL340 Only

The Or If Equal instruction connects a normally open comparative counter contact in parallel with another contact. The contact will be on if the specified counter CT aaa = B bbbb.

Or Not If Equal (OR NOT) DL330/DL340 Only

The Or Not If Equal instruction connects a normally closed comparative counter contact in parallel with another contact. The contact will be on if the specified counter CT aaa ¸ B bbbb. Operand Data Type

Counters

D3--330 Range

CT aaa

B bbbb

CT aaa

B bbbb

D3--340 Range

D3--330P Range*

B aaa bbbb aaa bbbb aaa bbbb

CT

600--677

----

600--677

----

----

----

----

400--577

----

400--577 700--777

----

----

----

0--9999

----

0--9999

----

----

Data registers

R

Constant

K

* See Chapter 12 for similar RLL PLUS instructions In the following Or If Equal example, when input contact 001 is on or CT600 = 2510 output 012 will energize. DirectSOFT Display

Handheld Programmer Keystrokes 012

001

OUT CT600

K2510

STR OR SHF

SHF SHF 2

1 6 5

ENT 0 1

0 0

ENT ENT

OUT

SHF

0

1

2

ENT

In the following Or Not If Equal example, when input contact 001 is on or CT600 ¸ the value in R400 output 012 will energize. DirectSOFT Display

Handheld Programmer Keystrokes 012

001

OUT CT600

R400

DL305 User Manual, Rev. D

STR OR R

SHF NOT 4

1 6 0

ENT 0 0

0 ENT

ENT

OUT

SHF

0

1

2

ENT