11--21

Instruction Set Comparative Boolean Instructions

The And If Equal instruction connects a normally open comparative counter contact in series with another contact. The contact will be on if the specified counter CT aaa = B bbbb.

And Not If Equal (AND NOT) DL330/DL340 Only

The And Not If Equal instruction connects a normally closed comparative counter contact in series with another contact. The contact will be on if the specified counter CT aaa ¸ B bbbb. Operand Data Type

Counters

D3--330 Range

CT aaa

B bbbb

CT aaa

B bbbb

D3--340 Range

D3--330P Range*

B aaa bbbb aaa bbbb aaa bbbb

CT

600--677

----

600--677

----

----

----

----

----

----

----

Data registers

R

----

400--577

----

400--577 700--777

Constant

K

----

0--9999

----

0--9999

* See Chapter 12 for similar RLL PLUS instructions In the following And If Equal example, when input contact 001 is on and CT600 = 2510 the contact will turn on and output 012 will energize. DirectSOFT Display 001

Handheld Programmer Keystrokes CT600

K2510

012 OUT

STR AND SHF

SHF SHF 2

1 6 5

ENT 0 1

0 0

ENT ENT

OUT

SHF

0

1

2

ENT

In the following And Not If Equal example, when input contact 001 is on and CT600 ¸ the value in R400 output 012 will energize. DirectSOFT Display 001

Handheld Programmer Keystrokes CT600

R400

012 OUT

STR AND R

SHF NOT 4

1 6 0

ENT 0 0

0 ENT

ENT

OUT

SHF

0

1

2

ENT

DL305 User Manual, Rev. D

Instruction Set

And If Equal (AND) DL330/DL340 Only

Page 261

11--22

Instruction Set Timer, Counter, and Shift Register Instructions

Instruction Set

Timer, Counter, and Shift Register Instructions Timer (TMR) DL330/DL340 Only

The Timer instruction provides a single input timer with a 0.1 second increment (0--999.9 seconds) in the normal operating mode, or a 0.01 second increment (0--99.99 seconds) in the fast timer mode when relay 770 is turned on. The timer will time up to 9999 and stop. It will reset to zero when the input is turned off. The discrete bit associated with the timer will be on when the current value is equal to or greater than the preset value. Operand Data Type

Timers

TMR

D3--330 Range

T aaa Bbbbb

D3--340 Range

D3--330P Range

B aaa bbbb aaa bbbb aaa bbbb

T

600--677

----

600--677

----

----

----

----

----

----

----

Data registers

R

----

400--577

----

400--577 700--777

Constant

K

----

0--9999

----

0--9999

* See Chapter 12 for similar RLL PLUS instructions In the following Timer example, timer 600 will begin timing up when input 000 turns on. The timer bit associated with timer 600 will turn on when the current value in timer 600 is ² the preset value K30 (3 seconds). When input 000 turns off the timer discrete bit and current value are reset. DirectSOFT Display

Handheld Programmer Keystrokes

000

TMR

STR TMR K

T600 K30

T600

SHF SHF 3

0 6 ENT

ENT 0

10 OUT

Timing Diagram

0

1

2

3

4

5

6

7

0

10

20

30

40

50

60

8

000

010 Current Value

DL305 User Manual, Rev. D

0

0

ENT

Page 262

11--23

Instruction Set Timer, Counter, and Shift Register Instructions

The Counter instruction provides a counter with a count and reset input. The range of this counter is 0--9999 and it will increment when the count input transitions from off to on. The counter is reset to 0 when you turn on the reset input. The counter bit associated with the counter will turn on when the current value is equal to or greater than the preset value. Operand Data Type

Counters

COUNT

CNT

CTaaa Bbbbb

Instruction Set

Counter (CNT) DL330/DL340 Only

RESET

D3--330 Range

D3--340 Range

B aaa bbbb aaa

CT

600--677

----

D3--330P Range bbbb aaa bbbb

600--677

----

----

----

----

----

----

----

Data registers

R

----

400--577

----

400--577 700--777

Constant

K

----

0--9999

----

0--9999

* See Chapter 12 for similar RLL PLUS instructions In the following Counter example, counter 604 will increment by one count when input 000 transitions from off to on. When input contact 001 is turned on the counter will reset to zero. The counter bit associated with counter 604 will turn on when the current value in counter 604 is ² the preset constant value K3 (3). DirectSOFT Display

Handheld Programmer Keystrokes

000

CNT

STR STR CNT SHF

CT604 K3

001

CT604

SHF SHF SHF 3

0 1 6 ENT

ENT ENT 0

4

ENT

10 OUT

000

001

010 Current Value

1

2

3

4

0

DL305 User Manual, Rev. D

Page 263

Instruction Set

11--24

Instruction Set Timer, Counter, and Shift Register Instructions

Shift Register (SR) DL330/340 Only

The Shift Register instruction shifts data through a predefined number of shift register bits. There are 128 bits allocated for use in shift registers. There is no limit to the number of shift registers which can be used in a program, however the total number of bits used cannot exceed 128. The Shift Register has three contacts. S Data, determines the value (1 or 0) that will enter the register S Clock, shifts the bits one position on each off to on transition S Reset, resets the Shift Register to all zeros.

DATA

SR From A aaa

CLOCK To

B bbb

RESET

With each off to on transition of the clock input, the bits which make up the shift register block are shifted by one bit position and the status of the data input is shifted into the starting bit position in the block. The direction of the shift depends on the entry in the From and To fields. From 400 to 407 would define a block of eight bits to be shifted from bit 400 to bit 407. From 407 to 400 would also define a block of eight bits, but would shift from bit 407 to bit 400. The maximum size of the shift register block is limited to 128 bits. There is no minimum block size. Operand Data Type

D3--330 Range

Shift Register Bits

D3--340 Range bbbb aaa bbbb aaa bbbb

400--577

400--577

400--577

400--577

----

----

DirectSOFT Display 000

Handheld Programmer Keystrokes

Data Input

001

SR From

400

To

417

Clock Input

002

D3--330P Range aaa

STR STR STR SR SHF

SHF SHF SHF SHF 4

0 1 2 4 1

Reset Input

Inputs on Successive Scans Data

Clock

Reset

1

1

0

0

1

0

0

1

0

1

1

0

0

1

0

0

0

1

-- indicates on

DL305 User Manual, Rev. D

Shift Register Bits 400

417

-- indicates off

ENT ENT ENT 0 7

0 ENT

ENT

Page 264

11--25

Instruction Set Accumulator Load and Output Instructions

Accumulator Load and Output Instructions The Data Store (F50) is a 16--bit instruction that loads the value of a 16--bit register, two consecutive 8--bit registers (specify starting location), or a 4--digit BCD value into the accumulator.

DSTR (F50) A aaaa

Data Out DOUT (F60)

The Data Out (F60) is a 16--bit instruction that copies the 16--bit value in the accumulator to a 16--bit reference or two consecutive 8--bit registers (specify starting location).

DOUT (F60) A aaaa

Data Type

D3--330 Range

D3--340 Range

A aaaa aaaa aaaa

Inputs / Outputs

R

000--014 070--075

000--014 070--075

000--014 070--075

Control Relays

R

016--036

016--036 100--105

016, 020--027

Shift Registers

R

040--056

040--056

----

Stages

R

----

----

100--116

Timer /Counters (16 bit)

R

600--677

600--677

600--677 400--577 0000--9999

Data Registers

R

400--577

400--577 700--777

*Constant (4--digit BCD)

K

0000--9999

0000--9999

Instruction Set

Data Store DSTR (F50)

D3--330P Range

* A constant is not a valid data type for the DOUT (F60) instruction.

In the following example, when input 000 is on the value (7502) in R402 and R403 is loaded into the accumulator using the Data Store (F50) instruction. The value in the accumulator is output to data registers R404 and R405 using the Data Out (F60) instruction. DirectSOFT Display 000 DSTR (F50) R 402

R 403

R 402

Handheld Programmer Keystrokes

7

0

2

STR F

SHF 5

0 0

ENT ENT

2

Accumulator

0

2

R F R

4 6 4

0 0 0

2 ENT 4

5 7

DOUT (F60) R 404 7

5

0

5

R405

ENT ENT

R404

In the following example, when input 001 is on the BCD constant value K7502 is loaded into the accumulator using the Data Store (F50) instruction. The value in the accumulator is output to data registers R404 and R405 using the Data Out (F60) instruction. DirectSOFT Display

K

001 DSTR (F50) K 7502 DOUT (F60) R 404

7

Handheld Programmer Keystrokes

7

5

0

2

7

5

0

2

Accumulator

0

2

5

R405

R404

STR F

SHF 5

1 0

ENT ENT

SHF F R

7 6 4

5 0 0

0 ENT 4

DL305 User Manual, Rev. D

2 ENT

ENT

Page 265

Instruction Set

11--26

Instruction Set Accumulator Load and Output Instructions

Data Store 1 DSTR (F51)

The Data Store 1 (F51) is an 8--bit instruction that loads the value from a specified 8--bit register into the lower 8 bits of the accumulator. The upper 8 bits of the accumulator are set to zero.

DSTR1 (F51) R aaa

Data Out 1 DOUT (F61)

The Data Out 1 (F61) is an 8--bit instruction that copies the value in the lower 8 bits of the accumulator to a specified 8--bit register.

DOUT1 (F61) R aaa

Data Type

D3--330 Range

D3--340 Range

D3--330P Range aaaa aaaa aaaa

000--014 070--075

000--014 070--075 016, 020--027

Inputs / Outputs

R

000--014 070--075

Control Relays

R

016--036

016--036 100--105

Shift Registers

R

040--056

040--056

----

Stages

R

----

----

100--116

Data Registers

R

400--577

400--577 700--777

400--577

In the following example, when input 000 is on the value (89) in R410 is loaded into the lower 8 bits of the accumulator using the Data Store 1 (F51) instruction. The value in the least significant 8 bits of the accumulator is output to data register R500 using the Data Out 1 (F61) instruction. DirectSOFT Display

Handheld Programmer Keystrokes

000

R410

DSTR1 (F51) R 410 Load the value in register R410 into the accumulator

DOUT1 (F61) R 500 Copy the value in the accumulator to registers R500

DL305 User Manual, Rev. D

0

0

8

9

8

9

8

9

R500

Accumulator

STR F

SHF 5

0 1

ENT ENT

R F R

4 6 5

1 1 0

0 ENT 0

ENT ENT

Page 266

11--27

Instruction Set Accumulator Load and Output Instructions

The Data Store 2 (F52) is a 4--bit instruction that loads the value of the most significant 4 bits of a specified 8--bit register into the least significant 4 bits of the accumulator. The remaining 12 bits of the accumulator are set to zero.

Data Out 2 DOUT (F62)

The Data Out 2 (F62) is a 4--bit instruction that copies the value in the least significant 4 bits of the accumulator into the most significant 4 bits of a specified 8--bit register. The lower 4 bits of the register are not altered . Data Type

DSTR2 (F52) R aaa

Instruction Set

Data Store 2 DSTR (F52)

DOUT2 (F62) R aaa

D3--330 Range

D3--340 Range aaaa aaaa

D3--330P Range aaaa

000--014 070--075

000--014 070--075 016, 020--27

Inputs / Outputs

R

000--014 070--075

Control Relays

R

016--036

016--036 100--105

Shift Registers

R

040--056

040--56

----

Stages

R

----

----

100--116

Data Registers

R

400--577

400--577 700--777

400--577

In the following example, when input 000 is on the most significant 4 bits of R1 are loaded into the lower 4 bits of the accumulator using the Data Store 2 (F52) instruction. The value in the least significant 4 bits of the accumulator is output to most significant 4 bits of data register R400 using the Data Out 2 (F62) instruction. DirectSOFT Display

Handheld Programmer Keystrokes

000

R001

DSTR2 (F52) R 001 Load the upper 4 bits in register 1 into the lower 4 bits of the accumulator DOUT2 (F62) R 400

5 0

0

*

0

5

5

*

R400

The lower 4 bits (*) of R1 are not loaded into the accumulator Accumulator

STR F

SHF 5

0 2

ENT ENT

R F R

1 6 4

ENT 2 0

ENT 0

The lower 4 bits (*) of R400 are not altered

Copy the lower 4 bits of the accumulator to the upper 4 bits or registers R400

DL305 User Manual, Rev. D

ENT

Page 267

Instruction Set

11--28

Instruction Set Accumulator Load and Output Instructions

Data Store 3 DSTR (F53)

The Data Store 3 (F53) is a 4--bit instruction that loads the value of the least significant 4 bits of a specified 8--bit register into the least significant 4 bits of the accumulator. The upper 12 bits of the accumulator are set to zero.

Data Out 3 DOUT (F63)

The Data Out 3 (F63) is a 4--bit instruction that copies the value in the least significant 4 bits of the accumulator to the least significant 4 bits of a specified 8 bit register. The upper 4 bits of the register are not altered. Data Type

DSTR3 (F53) R aaa

DOUT3 (F63) R aaa

D3--330 Range

D3--340 Range aaaa aaaa

D3--330P Range aaaa

000--014 070--075

000--014 070--075 016, 020--027

Inputs / Outputs

R

000--014 070--075

Control Relays

R

016--036

016--036 100--105

Shift Registers

R

040--056

040--056

----

Stages

R

----

----

100--116

Data Registers

R

400--577

400--577 700--777

400--577

In the following example, when input 000 is on the least significant 4 bits of R005 are loaded into the accumulator using the Data Store 3 (F53) instruction. The data in the least significant 4 bits of the accumulator is output to the least significant 4 bits of R016 using the Data Out 3 (F63) instruction. DirectSOFT Display

Handheld Programmer Keystrokes

000 DSTR3 (F53) R 005 Load the lower 4 bits in register 5 into the lower 4 bits of the accumulator DOUT3 (F63) R 016

R005 The upper 4 bits (*) of R5 are not loaded into the accumulator 0

0

The upper 4 bits (*) of R400 are not altered

Output the lower 4 bits of the accumulator to the lower 4 bits of R16

DL305 User Manual, Rev. D

*

8

0

8

*

8

R016

Accumulator

STR F

SHF 5

0 3

ENT ENT

R F R

5 6 1

ENT 3 6

ENT ENT

Page 268

Instruction Set Accumulator Load and Output Instructions

The Data Store 5 (F55) is a 16--bit instruction that loads the value of 16 image register locations for a specified 16 point input module into the accumulator.

DSTR 5 (F55) R aaa

Data Out 5 DOUT (F65)

The Data Out 5 (F65) is a 16--bit instruction that outputs the 16 bit value in the accumulator to the image register of a specified 16 point output module.

DOUT 5 (65) R aaa

Data Type

D3--330 Range

Inputs / Outputs

R

D3--340 Range

D3--330P Range aaaa aaaa aaaa

000--014 070--075

000--014 070--075

000--014 070--075

In the following example, when input 000 is on the binary status of a 16 point I/O module in slot 1 (R000 and R010) is loaded into the accumulator using the Data Store 5 (F55) instruction. The value in the accumulator is copied to I/O register locations in slot 2 (R001 and R011) using the Data Out 5 (F65) instruction. DirectSOFT Display

Handheld Programmer Keystrokes

000 DSTR5 (F55) R 000

R

Loads status of 16 point input image register (R000 and R010) to accumulator

0

1

0

R

0

0

0

7

I/O Points 100--107 6 5 4 3 2 1 0

7

I/O Points 000--007 6 5 4 3 2 1 0

0

1

0

0

0

0

0

0

0

0

0

0

1

0

0

STR F

SHF 5

0 5

ENT ENT

R F

0 6 1

ENT 5 ENT

ENT

R

1

Load status of 16 pt. input module into the accumulator

Acc.

15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

0

0

0

0

0

0

0

1

0

0

1

1

0

0

0

0

0

I/O Points 100--107

R

DOUT5 (F65) R 001 Copy the value in the accumulator to R001 and R011

0

1

I/O Points 000--007

1

R

I/O Points 110--117

0

0

1

I/O Points 010--017

7

6

5

4

3

2

1

0

7

6

5

4

3

2

1

0

0

1

0

0

0

0

0

0

0

0

0

0

1

0

0

1

DL305 User Manual, Rev. D

Instruction Set

Data Store 5 DSTR (F55)

11--29

Page 269

11--30

Instruction Set Accumulator Logic Instructions

Instruction Set

Accumulator Logic Instructions Data And DAND (F75)

The Data And (F75) is a 16--bit instruction that logical ands the value in a 16--bit reference, two consecutive 8--bit registers (specify starting location), or a 4--digit BCD constant with the value in the accumulator. The result resides in the accumulator. Data Type

D3--330 Range

DAND (F75) A aaaa

D3--340 Range

D3--330P Range

A aaaa aaaa aaaa

Inputs / Outputs

R

000--014 070--075

000--014 070--075

000--014 070--075

Control Relays

R

016--036

016--036 100--105

016, 020--027

Shift Registers

R

040--056

040--056

----

Stages

R

----

----

100--116

Timer /Counters (16 bit)

R

600--677

600--677

600--677

Data Registers

R

400--577

400--577 700--777

400--577

Constant (4--digit BCD)

K

0000--9999

0000--9999

0000--9999

In the following example, when input 000 is on the value(6489) in R402 and R403 is loaded into the accumulator using the Data Store (F50) instruction. The data in the accumulator is logically anded with the constant K4107 with the result residing in the accumulator. The value in the accumulator is output to data register R404 and R405 using the Data Out (F60) instruction. DirectSOFT Display

Handheld Programmer Keystrokes

000 DSTR (F50) R 402 Load the value in register R402 and R403 into the accumulator Acc.

DAND (F75) K4107 AND the value in the accumulator with the constant value 4107

AND

DOUT (F60) R 404 Output the value in the accumulator to registers R404 and R405

DL305 User Manual, Rev. D

9

STR F

SHF 5

0 0

ENT ENT

R F SHF

4 7 4

0 5 1

2 ENT 0

6 4

0 0

ENT 4

R403

R402

6

8

4

7

6

5

4

3

2

1

0

7

6

5

4

3

2

1

0

0

1

1

0

0

1

0

0

1

0

0

0

1

0

0

1

F R

0

1

1

0

0

1

0

0

1

0

0

0

1

0

0

1

Accumulator

0

1

0

0

0

0

0

1

0

0

0

0

0

1

1

1

Constant (4107)

0

1

0

0

0

0

0

0

0

0

0

0

0

0

0

1

Accumulator

4

0

0

1

R405

R404

ENT 7 ENT

ENT