DL305 User Manual: Chapter 12: RLLPLUS Instruction Set, pages 296 to 303

Pages 296 to 303 of 357, from DL305 User Manual

The original document is the PDF (3.4 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the PLC Direct D3-08TD1, PLC Direct D3-16NA, Koyo D3-08TD1 and Koyo D3-16NA

Page 296

RLL PLUS Instruction Set

1 12

In This Chapter. . . ., Introduction, Stage Instructions, Comparative Boolean Instructions, Timer, Counter, and Shift Register Instructions

Page 297

12--2

RLL PLUS Instruction Set Stage Instructions

Instruction Set

Introduction This chapter provides information concerning the instructions used with RLL PLUS CPUs. If you are not familiar with RLL PLUS programming concepts, you should read Chapter 10 first. Chapter 10 will help you understand the basic concepts. The following table provides a quick reference listing of the instruction mnemonic and the page(s) defining the instruction. (The mnemonics are very similar to the instruction names and should be easy to become familiar with in a short time.) For example ISG is the mnemonic for Initial Stage. Each instruction definition will show in parentheses the keystrokes used to enter the instruction.

RLLPLUS Instructions

NOTE: Don’t assume that the instructions in this chapter are the only ones you can use with your RLL PLUS CPU. There are many others that are discussed in Chapter 11 that you can use as well. If you are using a RLL PLUS CPU, such as the DL330P, then you should always consult this chapter before you use one of the instructions shown in Chapter 11. There may be differences in the way the instruction operates in an RLL PLUS CPU. This chapter provides a description of several instructions that are similar, but slightly different from their RLL CPU counterparts. For example, you’ll notice that a Counter instruction has two input lines in a RLL CPU but only one input line in an RLL PLUS CPU.

There are two ways to quickly find the instruction you need. S

If you know the instruction category (Stage, Comparative Boolean, etc.) just use the header at the top of the page to find the pages that discuss the instructions in that category.

S

If you know the individual instruction mnemonic, use the following table to find the page that discusses the instruction.

Instruction

Page

Instruction

Page

AND CNT

12--17

ORN TMR

12--14

AND SG

12--9

RST

12--10

AND TMR

12--16

RST (counter)

12--20

ANDN CNT

12--17

RST SG

12--11

ANDN SG

12--9

SET

12--10

ANDN TMR

12--16

SET SG

12--11

CNT

12--19

SG

12--3

ISG

12--3

SR

12--21

JMP

12--5

STR CNT

12--13

NJMP

12--5

STR TMR

12--12

OR CNT

12--15

STR SG

12--7

OR SG

12--8

STRN CNT

12--13

OR TMR

12--14

STRN SG

12--7

ORN CNT

12--15

STRN TMR

12--12

ORN SG

12--8

TMR

12--18

DL305 User Manual, Rev. D

Page 298

RLL PLUS Instruction Set Stage Instructions

12--3

Stage Instructions

Stage (SG) DL330P Only

The Stage instruction creates segments of a RLL PLUS program. Stages are activated by transitional logic, a jump or set stage executed from an active stage. Stages are de--activated one scan after transitional logic, a jump, or a reset stage instruction is executed. Data Type

Stages

SG

D3--330 Range

D3--340 Range aaaa aaaa aaaa

----

----

0--177

ISG

S aaa

SG

S aaa

D3--330P Range

DL305 User Manual, Rev. D

RLLPLUS Instructions

The Initial Stage instruction is normally used as the first segment of a RLL PLUS program. Initial stages are activated when the CPU enters the run mode, this creates a starting point in the program. The Initial Stage can be made inactive by either jumping from it or resetting it. Multiple Initial Stages are allowed in a program.

Instruction Set

Initial Stage (ISG) DL330P Only

Page 299

12--4

RLL PLUS Instruction Set Stage Instructions

Instruction Set

The following example is a simple RLL PLUS program. This program utilizes the Initial Stage, Stage, and Jump instructions to create a structured program. DirectSOFT Display

ISG

Handheld Programmer Keystrokes

S0

000

010 OUT

001

S2 SET

RLLPLUS Instructions

005

S1 JMP

SG

S1

002

011 OUT

SG

S2

006

012 OUT

007

S1

S0 JMP

DL305 User Manual, Rev. D

ISG STR

SHF SHF

0 0

ENT ENT

OUT STR SET

SHF SHF SG

1 1 SHF

0 ENT 2

STR JMP SG STR

SHF SG SHF SHF

5 1 1 2

ENT ENT ENT ENT

OUT SG STR

SHF SHF SHF

1 2 6

1 ENT ENT

ENT

OUT STR AND JMP

SHF SHF SG SG

1 7 1 0

2 ENT ENT ENT

ENT

ENT ENT

Page 300

RLL PLUS Instruction Set Stage Instructions

Not Jump (NOT JMP) DL330P Only

The Not Jump instruction allows the program to transition from an active stage which contains the jump instruction to another which is specified in the instruction. The jump will occur when the input logic is false. The active stage that contains the Not Jump will be de--activated 1 scan after the Not Jump instruction is executed. Data Type

Stages

SG

SG aaa JMP

SG aaa NJMP

RLLPLUS Instructions

The Jump instruction allows the program to transition from an active stage which contains the jump instruction to another which is specified in the instruction. The jump will occur when the input logic is true. The active stage that contains the Jump will be de--activated 1 scan after the Jump instruction is executed.

Instruction Set

Jump (JMP) DL330P Only

12--5

D3--330 Range

D3--340 Range aaaa aaaa

D3--330P Range aaaa

----

----

0--177

DL305 User Manual, Rev. D

Page 301

12--6

RLL PLUS Instruction Set Stage Instructions

Instruction Set

The following example is a simple RLL PLUS program. This program utilizes the Initial Stage, Stage, Jump, and Not Jump instructions to create a structured program. DirectSOFT Display

Handheld Programmer Keystrokes

ISG

ISG STR

SG SHF

SHF 0

0 ENT

ENT

OUT STR JMP

SHF SHF SG

1 1 SHF

0 ENT 1

ENT

JMP SG STR

NOT SHF SHF

SG 1 002

SHF ENT ENT

2

OUT STR JMP

SHF SHF SG

1 3 SHF

1 ENT 2

ENT

SG STR OUT STR

SHF SHF SHF SHF

2 4 1 5

ENT ENT 2 ENT

JMP

SG

SHF

0

S0

000

010 OUT

001

S1 JMP

RLLPLUS Instructions

S2 NJMP

SG

S1

002

011 OUT

003

S2 JMP

SG

S2

004

012 OUT

005

S0 JMP

DL305 User Manual, Rev. D

ENT

ENT

ENT ENT

ENT

Page 302

RLL PLUS Instruction Set Stage Instructions

The Store instruction begins a new rung or additional branch in a rung with a normally open stage contact. Status of the contact will be the same state as the associated Stage memory location.

Store Not Stage (STR NOT SG) DL330P Only

The Store Not instruction begins a new rung or additional branch in a rung with a normally closed stage contact. Status of the contact will be opposite the state of the associated stage memory location.

Stages

SG

SG aaa

D3--330 Range

D3--340 Range aaaa aaaa aaaa

----

----

0--177

RLLPLUS Instructions

Data Type

SG aaa

Instruction Set

Store Stage (STR SG) DL330P Only

12--7

D3--330P Range

In the following Store example, when stage contact 000 is on, output 010 will energize. DirectSOFT Display SG 000

Handheld Programmer Keystrokes 010 OUT

STR OUT

SG SHF

SHF 1

0 0

ENT ENT

In the following Store Not example, when stage contact 000 is off output 010 will energize. DirectSOFT Display SG 000

Handheld Programmer Keystrokes 010 OUT

STR OUT

NOT SHF

SG 1

SHF 0

0 ENT

ENT

DL305 User Manual, Rev. D

Page 303

RLLPLUS Instructions

Instruction Set

12--8

RLL PLUS Instruction Set Stage Instructions

Or Stage (OR SG) DL330P Only

The Or instruction logically ors a normally open stage contact in parallel with another contact in a rung. The status of the contact will be the same state as the associated stage memory location.

Or Not Stage (OR NOT SG) DL330P Only

The Or Not instruction logically ors a normally closed stage contact in parallel with another contact in a rung. The status of the contact will be opposite the state of the associated stage memory location. Data Type

Stages

SG

SG aaa

SG aaa

D3--330 Range

D3--340 Range

D3--330P Range aaaa aaaa aaaa

----

----

0--177

In the following Or example, when input 000 or stage contact 001 is on output 010 will energize. DirectSOFT Display 000

Handheld Programmer Keystrokes 010 OUT

STR OR OUT

SHF SG SHF

0 SHF 1

ENT 1 0

ENT ENT

SG 001

In the following Or Not example, when input 000 is on or stage contact 001 is off output 010 will energize. DirectSOFT Display

000

Handheld Programmer Keystrokes 010 OUT

SG 001

DL305 User Manual, Rev. D

STR OR OUT

SHF NOT SHF

0 SG 1

ENT SHF 0

1 ENT

ENT