Page 41

2--20

Entering RLL Programs

Entering RLL Programs

Entering RLL Programs

Entering Shift Registers

The DL305 CPUs allow you to use Control Relays with a Shift Register. You can have any number of Shift Registers, but there are only 128 Control Relays that can be used (400--577). Also, you cannot use these bits as Control Relays and Shift Register bits. (See the DL305 User Manual for more details.) The Shift Register has three input contacts. S Data, used to determine a value (1 or 0) that will be shifted through the register S Clock, on each low to high transition, the value that is on the data line will be shifted into the shift register. S Reset, if the reset contact comes on, then the Shift Register is reset and all Control Relays are reset. The following diagram shows a brief example of how the Shift Register works. 001

Data

002

Clock

003

Reset

SR

SR420

Inputs on Successive Scans Data

Clock

Reset

1

1

0

0

1

0

0

1

0

1

1

0

0

1

0

0

0

1

SR400

Shift Register Bits 400

417

-- indicates ON

REV A

-- indicates OFF

Page 42

2--21

Entering RLL Programs You can use the following keystrokes to enter a Shift Register. Enter the Data input STR

SHF

1

Data Display before ENT is pressed

001

ENT

ADDRESS/DATA ON/OFF

RUN BATT PWR CPU

0 MCS 1 MCR 2 SET 3 RST

4 ADR 5 SHF 6 DATA 7 REG

0 AND 1 OR 2 STR 3 NOT

4 OUT 5 TMR 6 CNT 7 SR

0 MCS 1 MCR 2 SET 3 RST

4 ADR 5 SHF 6 DATA 7 REG

0 AND 1 OR 2 STR 3 NOT

4 OUT 5 TMR 6 CNT 7 SR

0 MCS 1 MCR 2 SET 3 RST

4 ADR 5 SHF 6 DATA 7 REG

0 AND 1 OR 2 STR 3 NOT

4 OUT 5 TMR 6 CNT 7 SR

0 MCS 1 MCR 2 SET 3 RST

4 ADR 5 SHF 6 DATA 7 REG

0 AND 1 OR 2 STR 3 NOT

4 OUT 5 TMR 6 CNT 7 SR

0 MCS 1 MCR 2 SET 3 RST

4 ADR 5 SHF 6 DATA 7 REG

Enter the Clock input STR

SHF

2

002

ENT

ADDRESS/DATA ON/OFF

RUN BATT PWR CPU

Enter the Reset input STR

SHF

3

003

ENT

ADDRESS/DATA ON/OFF

RUN BATT PWR CPU

Enter the Shift Register and starting location SR

SHF

4

0

400

0

ADDRESS/DATA

ENT

ON/OFF

RUN BATT PWR CPU

Enter the end of the Shift Register SHF

4

1

7

ENT

417

ADDRESS/DATA ON/OFF

RUN BATT PWR CPU

Entering RLL Programs

4 OUT 5 TMR 6 CNT 7 SR

Entering RLL Programs

0 AND 1 OR 2 STR 3 NOT

Page 43

2--22

Entering RLL Programs

Entering Data Instructions

In addition to the simple RLL instructions, the DL305 CPUs also provide Data Instructions that allow you to manipulate words of data. For example, you may want to perform simple math operations on register values. The following table provides a listing of the various Data Operation Instructions. You should see the DL305 User Manual for complete details on how the instructions operate.

Entering RLL Programs

Entering RLL Programs

Category

Data Load Instructions

Mnemonic

Function #

Description

DSTR

F50

Load a 4-digit constant or 2-bytes of register data into the accumulator

DSTR 1

F51

Load 1-byte of register data into the accumulator

DSTR 2

F52

Load the upper 4 bits of a register into the lower 4 bits of the accumulator

DSTR 3

F53

Load the lower 4 bits of a register into the upper 4 bits of the accumulator

DSTR 5

F55

Load the digital value of a 16 point module (2 bytes) into the accumulator

DOUT

F60

Write the accumulator to 2 sequential registers

DOUT 1

F61

Write the lower byte of the accumulator to a register

DOUT 2

F62

Write the lower 4 bits of the accumulator to the upper 4 bits of a register

DOUT 3

F63

Write the lower 4 bits of the accumulator to the lower 4 bits of a register

DOUT 5

F65

Write the contents of the accumulator to a 16-point output module (2 bytes)

CMP

F70

Compare a 2-byte BCD reference or a 4-digit BCD constant to the accumulator

ADD

F71

Add a 2-byte BCD reference or a 4-digit BCD constant to the accumulator

SUBTRACT

F72

Subtract a 2-byte BCD reference or a 4-digit BCD constant from the accumulator

MULTIPLY

F73

Multiply a 2-byte BCD reference or a 4-digit BCD constant by the value in the accumulator

DIVIDE

F74

Divide the accumulator by a 2-byte BCD reference or a 4-digit BCD constant

Data Out Instructions

Math Instructions

Page 44

Entering RLL Programs

Category

Bit Manipulation Instructions

Function #

Description

DAND

F75

Performs a bit “AND” on a 2-byte reference or a 4-digit BCD constant and the bits in the accumulator

DOR

F76

Performs a bit “OR” on a 2-byte reference or a 4-digit BCD constant and the bits in the accumulator

SHIFT RIGHT

F80

Shifts the contents of the accumulator to the right a specified number of times. 1 -- 15 bits can be shifted.

SHIFT LEFT

F81

Shifts the contents of the accumulator to the left a specified number of times. 1 -- 15 bits can be shifted.

DECODE

F82

Decodes the first 4 bits of the accumulator into a decimal number.

ENCODE

F83

Encodes an accumulator bit into a 4-bit code that represents the decimal number (0--15).

INV

F84

Logically inverts the bit pattern contained in the accumulator (1 to 0, 0 to 1).

BCD--BIN

F85

Converts the accumulator value from BCD to Binary

BIN--BCD

F86

Converts the accumulator value from Binary to BCD

FAULT

F20

Sends a 4-digit BCD number, from a 2-byte reference or a constant, to the programmer display

The following pages show you how to enter these functions with the Handheld Programmer.

Entering RLL Programs

Fault Detection Instructions

Mnemonic

Entering RLL Programs

Data Conversion Instructions

2--23

Page 45

2--24

Entering RLL Programs If you examine the Handheld Programmer keypad, you’ll notice two keys labeled F and R. These keys are used to access the various Data Operation Instructions. We’ll use the following example to show how the keys are used. 001

DSTR

F50

K1234

DOUT

Constant

Register

The example uses the DSTR and DOUT instructions. As you enter the instructions you will use the Function Numbers that were shown in the previous instruction table.

Entering RLL Programs

Entering RLL Programs

R400

F60

Instruction

REV A

Page 46

Entering RLL Programs

2--25

Enter the contact STR

SHF

1

001

ENT

ADDRESS/DATA ON/OFF

RUN BATT PWR CPU

4 OUT 5 TMR 6 CNT 7 SR

0 MCS 1 MCR 2 SET 3 RST

4 ADR 5 SHF 6 DATA 7 REG

0 AND 1 OR 2 STR 3 NOT

4 OUT 5 TMR 6 CNT 7 SR

0 MCS 1 MCR 2 SET 3 RST

4 ADR 5 SHF 6 DATA 7 REG

0 AND 1 OR 2 STR 3 NOT

4 OUT 5 TMR 6 CNT 7 SR

0 MCS 1 MCR 2 SET 3 RST

4 ADR 5 SHF 6 DATA 7 REG

0 AND 1 OR 2 STR 3 NOT

4 OUT 5 TMR 6 CNT 7 SR

0 MCS 1 MCR 2 SET 3 RST

4 ADR 5 SHF 6 DATA 7 REG

0 AND 1 OR 2 STR 3 NOT

4 OUT 5 TMR 6 CNT 7 SR

0 MCS 1 MCR 2 SET 3 RST

4 ADR 5 SHF 6 DATA 7 REG

Enter the DSTR instruction F

5

0

F50

ENT

(Notice that you did not have to press the SHF key before entering the numbers.)

ADDRESS/DATA ON/OFF

RUN BATT PWR CPU

Entering RLL Programs

0 AND 1 OR 2 STR 3 NOT

Enter the constant 1

2

3

4

1234

ADDRESS/DATA

ENT

ON/OFF

RUN BATT PWR CPU

Enter the DOUT instruction F

6

0

F60

ENT

ADDRESS/DATA ON/OFF

RUN BATT PWR CPU

Enter the Register location R

4

0

0

ENT

(Notice that the R key is used for entering registers and that you do not have to press the SHF key before entering the numbers.)

r400

ADDRESS/DATA ON/OFF

RUN BATT PWR CPU

Entering RLL Programs

SHF

Page 47

2--26

Entering RLL Programs

Checking for Program Errors Automatic Error Checking Syntax Check

The Handheld automatically checks for some errors during program entry. Chapter 6 provides a complete listing of the error codes. You can also execute a program syntax check which will identify programming errors. This check can be performed in either Program mode or Run mode. The following example shows how the syntax check works.

Entering RLL Programs

001

CNT

CT601 K50

Counter Reset Leg is missing Execute the syntax check CLR

E07

SCH

Entering RLL Programs

ADDRESS/DATA ON/OFF

RUN BATT PWR CPU

0 AND 1 OR 2 STR 3 NOT

4 OUT 5 TMR 6 CNT 7 SR

0 MCS 1 MCR 2 SET 3 RST

4 ADR 5 SHF 6 DATA 7 REG

0 MCS 1 MCR 2 SET 3 RST

4 ADR 5 SHF 6 DATA 7 REG

Press CLR to display the address where the error occurred

0003 ....

CLR

ADDRESS/DATA ON/OFF

RUN BATT PWR CPU

0 AND 1 OR 2 STR 3 NOT

4 OUT 5 TMR 6 CNT 7 SR

Correct the problem and continue running the Syntax check until the E07 message no longer appears.

REV A

Page 48

Entering RLL PLUS Programs In This Chapter. . . ., RLL PLUS Programming Basics, Entering an Initial Stage, Entering Jump Instructions, Entering Stage Instructions, Entering Timers, Entering Counters, Entering Shift Registers

13

Page 49

3--2

Entering RLL Plus Programs

Entering RLL Programs

Entering Programs

RLL PLUS Programming Basics RLL PLUS is a simplified programming method that makes program design and troubleshooting much easier. This programming method is similar to Sequential Function Chart programming and only uses a few new instructions. Before you continue, make sure you have a Handheld Programmer that supports the extra instructions needed with this style of programming (part number DL3--HPP). This chapter does not provide a complete discussion of these instructions. Instead, it just provides a quick overview of how to enter the instructions with the DL305 Handheld Programmer. The primary benefit from this programming method is the number of logic interlocks is significantly reduced. This is because the individual program segments, called “stages” are completely self contained. When a program segment is active, the inputs and outputs in that stage will be examined and updated as appropriate. If the stage is not active, that portion of the program is not even scanned. How does this remove the interlocking burden? Simple, most interlocks are used because you not only have to make something happen, but you also have to prevent unwanted actions from happening. See the DL305 User Manual for details on RLL PLUS programming. We’ll use the following cutoff saw example to show the different instructions that are used. This example is not intended to show you how to design RLL PLUS programs, but is merely used to point out the instructions and the Handheld Programmer keystrokes needed to enter the instructions. If you want to know more about this style of programming, see the DL305 User Manual for complete details. This simple cutoff saw operates in the following manner. 1. Once the operator presses a start switch, the pipe conveyor is started. (The operator can also press a Stop switch to stop the operation at any time.) 2. The pipe travels along a conveyor until it reaches a physical stop. The stop contains a limit switch that signals the system to stop the conveyor and begin the cutting operation. 3. The pipe is clamped in place. 4. The saw motor is started and the saw cuts the pipe. 5. The saw is retracted, the motor is turned off and the clamp is released. 6. If the saw is in one-cycle mode, the operator must press the start switch again. If it is not in one-cycle mode, the saw continues the operations sequence.

Cutoff Saw

The operator can stop the process at any time just by pressing a stop switch.

Page 50

3--3

Entering RLL Plus Programs

The instructions used to create this program are very similar to the ones used in normal RLL programs. For example, you still enter contacts and output coils the same way. There are a couple of new instructions and these instructions have keys on the Handheld Programmer. You’ll notice the Initial Stage (ISG) instruction begins the program. If you examine the Handheld you’ll notice a key for the ISG instruction. Here’s a list of the primary instructions you’ll use with RLL PLUS programs. S Initial Stage (ISG) S Stage (SG) S Jump to Stage (JMP) There are also a few other instructions that are used differently (and entered differently) in RLL PLUS programs. S Timers S Counters S Shift Registers The following pages show you how to enter these instructions.

ISG S0000

Wait for start Start

S1 JMP

000 SG

Move pipe down conveyor

S0001

S10 JMP Conveyor OUT 020

Pipe Limit

S2 JMP

001 SG

Lock the clamp

S0002

Clamp SET 021 S3 JMP

Pipe Locked 002 SG

Cut the pipe

S0003

Saw On SET 022 Saw Down OUT 023

Lower Limit

S4 JMP

003 SG

Raise the saw

S0004

TMR

T600 50

Top Limit

600

Saw Off RST 022 Clamp RST 021

004

S5 JMP SG

One cycle or automatic?

S0005

One Cycle

S0 JMP

005 One Cycle

S1 JMP

005 SG

Monitor for Stop

S0010 Stop

S0 -- S5 RST

010 S0 JMP

Entering RLL Programs

WARNING: The example program shown is not suitable for actual applications. There are many safety aspects that have not been considered, which could result in a risk of personal injury or damage to equipment.

Only executes logic in stages that are active

Entering Programs

The following diagram shows a very simple RLL PLUS program that would control this operation. This representation is what you could expect to see if you were using our DirectSOFT programming software. You may notice the diagram doesn’t appear very different from a normal RLL program. However, there are significant advantages that aren’t obvious at first glance. If you want to know more, take a few extra minutes to read about this time-saving approach in the DL305 User Manual.