Page 51

3--4

Entering RLL Plus Programs

Entering Programs

Entering an Initial Stage The Initial Stage identifies a starting point in the program. When the CPU enters Run mode, this is where the program execution will begin. The following keystrokes are used to enter an initial stage. (Remember, the RLL PLUS Handheld programmer keypad layout and display is different from the RLL Handheld programmer.)

Only executes logic in stages that are active ISG S0000

Wait for start Start

S1 JMP

000 SG

Move pipe down conveyor

S0001

S10 JMP Conveyor OUT 020

Pipe Limit

S2 JMP

001 SG

Lock the clamp

S0002

Clamp SET 021 S3 JMP

Pipe Locked

Entering RLL Programs

002

Enter the initial stage ISG

SHF

0

ENT

Data display before ENT is pressed

000 ADDRESS/DATA ON/OFF

RUN BATT PWR CPU

0 STR 1 AND 2 OR 3 NOT

4 ISG 5 JMP 6 SET 7 RST

0 SG 1 OUT 2 TMR 3 CNT

4 ADR 5 SHF 6 DATA 7 REG

0 STR 1 AND 2 OR 3 NOT

4 ISG 5 JMP 6 SET 7 RST

0 SG 1 OUT 2 TMR 3 CNT

4 ADR 5 SHF 6 DATA 7 REG

Enter the contact STR

SHF

0

ENT

000 ADDRESS/DATA ON/OFF

RUN BATT PWR CPU

Page 52

3--5

Entering RLL Plus Programs

Entering Jump Instructions Only executes logic in stages that are active ISG S0000

Wait for start Start

S1 JMP

000 SG

Move pipe down conveyor

S0001

S10 JMP Conveyor OUT 020

Pipe Limit

S2 JMP

001 SG

Lock the clamp

S0002

Clamp SET 021 S3 JMP

Pipe Locked

Entering Programs

The Jump (JMP) instruction provides a way to transition to multiple points in the program. If you look at the example program you’ll notice the program branches to two locations after the operator presses the start switch. The Jump instruction provides this transition. Since the program is jumping to two locations, you’ll use two Jump instructions.

002

Monitor for Stop

S0010 Stop

S0 -- S5 RST

010 S0 JMP

Enter the first jump JMP

SHF

1

Data display before ENT is pressed

001

ENT

ADDRESS/DATA ON/OFF

RUN BATT PWR CPU

0 STR 1 AND 2 OR 3 NOT

4 ISG 5 JMP 6 SET 7 RST

0 SG 1 OUT 2 TMR 3 CNT

4 ADR 5 SHF 6 DATA 7 REG

0 STR 1 AND 2 OR 3 NOT

4 ISG 5 JMP 6 SET 7 RST

0 SG 1 OUT 2 TMR 3 CNT

4 ADR 5 SHF 6 DATA 7 REG

Enter the second jump JMP

SHF

1

0

ENT

010 ADDRESS/DATA ON/OFF

RUN BATT PWR CPU

Entering RLL Programs

SG

Page 53

3--6

Entering RLL Plus Programs

Entering RLL Programs

Entering Programs

Entering Stage Instructions The Stage (SG) instruction identifies the starting point of a program segment. Unlike an initial stage, a regular stage does not automatically activate when the CPU enters Run mode. There are three ways to activate a stage. S Jump Transition, if you jump from a stage to another stage, then the destination stage is automatically activated. (Remember the jump example.) S Power Flow Transition, power can flow through the stages which will activate the next stage. S SET, just as you can use a SET instruction to turn on an output, you can use a SET to turn on a stage. With this method, the stage will stay on until it is reset (RST) or, until the logic within that stage causes a jump or power flow transition.

Only executes logic in stages that are active ISG S0000

Wait for start Start

S1 JMP

000 SG

Move pipe down conveyor

S0001

S10 JMP Conveyor OUT 020

Pipe Limit 001

SG

Lock the clamp

S0002

Pipe Locked

Clamp SET 021 S3 JMP

002 SG

Monitor for Stop

S0010 Stop

S0 -- S5 RST

010 S0 JMP

The keystrokes on the following page show how to enter stages 1 and 2. Notice we have changed Stage 2 slightly. This is an example of how a power flow transition looks. A JMP instruction is not required in this example to move from Stage 1 to Stage 2. How do you know when to use a JMP instruction? Simple, if you’re moving from one stage to a single stage, you may use a power flow transition. If you’re moving from one stage to multiple stages, you must use the JMP instruction.

Page 54

3--7

Entering RLL Plus Programs

Enter Stage 1 SG

SHF

Data display before ENT is pressed 1

001

ENT

ADDRESS/DATA ON/OFF

RUN BATT PWR CPU

0 SG 1 OUT 2 TMR 3 CNT

4 ADR 5 SHF 6 DATA 7 REG

0 STR 1 AND 2 OR 3 NOT

4 ISG 5 JMP 6 SET 7 RST

0 SG 1 OUT 2 TMR 3 CNT

4 ADR 5 SHF 6 DATA 7 REG

0 STR 1 AND 2 OR 3 NOT

4 ISG 5 JMP 6 SET 7 RST

0 SG 1 OUT 2 TMR 3 CNT

4 ADR 5 SHF 6 DATA 7 REG

0 STR 1 AND 2 OR 3 NOT

4 ISG 5 JMP 6 SET 7 RST

0 SG 1 OUT 2 TMR 3 CNT

4 ADR 5 SHF 6 DATA 7 REG

Enter the output for the conveyor OUT

SHF

2

0

ENT

020 ADDRESS/DATA ON/OFF

RUN BATT PWR CPU

Enter the Pipe Limit contact STR

SHF

1

ENT

001 ADDRESS/DATA ON/OFF

RUN BATT PWR CPU

Enter Stage 2 SG

SHF

2

ENT

002 ADDRESS/DATA ON/OFF

RUN BATT PWR CPU

Entering RLL Programs

4 ISG 5 JMP 6 SET 7 RST

Entering Programs

0 STR 1 AND 2 OR 3 NOT

Page 55

3--8

Entering RLL Plus Programs

Entering RLL Programs

Entering Programs

Entering Timers Timers work differently in RLL PLUS programs because they do not require the entry of a preset value. Once the timer input contact has started the timer, the timer continues until the input contact SG Raise the saw S0004 is turned off. TMR T600 You may recall RLL timers have a timer contact associated with them. When the Saw Off T600 50 timer reaches the preset, it turns on the RST 022 contact, which can then be used as an Top input contact for other parts of the Limit Clamp RST program. 021 004 S5 As well as not having a preset value, Relational Contact JMP RLL PLUS timers also do not have a timer contact. Instead of using the timer contact, relational contacts are used to examine the timer value. The following example shows how a time delay was added when the saw was being raised. We wanted to keep the saw motor running for 5 seconds so the saw could clear the pipe before being turned off. (Note, the keystrokes only show how to enter the timer and the relational contact, not the whole stage.)

Page 56

3--9

Entering RLL Plus Programs

Enter the Timer TMR

SHF

6

Data display before ENT is pressed 0

0

600 ADDRESS/DATA

ENT

ON/OFF

RUN BATT PWR CPU

0 SG 1 OUT 2 TMR 3 CNT

4 ADR 5 SHF 6 DATA 7 REG

0 STR 1 AND 2 OR 3 NOT

4 ISG 5 JMP 6 SET 7 RST

0 SG 1 OUT 2 TMR 3 CNT

4 ADR 5 SHF 6 DATA 7 REG

0 STR 1 AND 2 OR 3 NOT

4 ISG 5 JMP 6 SET 7 RST

0 SG 1 OUT 2 TMR 3 CNT

4 ADR 5 SHF 6 DATA 7 REG

Enter the comparative timer contact STR

TMR

0

ENT

SHF

6

0

600 ADDRESS/DATA ON/OFF

RUN BATT PWR CPU

Enter the compare value SHF

5

0

ENT

050 ADDRESS/DATA ON/OFF

RUN BATT PWR CPU

Entering RLL Programs

4 ISG 5 JMP 6 SET 7 RST

Entering Programs

0 STR 1 AND 2 OR 3 NOT

Page 57

3--10

Entering RLL Plus Programs

Entering RLL Programs

Entering Programs

Entering Counters Counters also work differently in RLL PLUS programs because they do not require either a reset input or a preset value. Once the stage is active, the counter input contact controls the value of the counter. Each time the counter input contact has an off to on transition, the counter will increment one count. When the stage becomes inactive, the counter is disabled and reset to 0. (Remember, the CPU does not even scan the logic contained in an inactive stage.) You may recall RLL counters have a counter contact associated with them. When the counter reaches the preset, it turns on the contact, which can then be used as an input contact for other parts of the program. As well as not having the reset input and preset value, the RLL PLUS counters also do not have a counter contact. Instead of using the counter contact, relational contacts are used to examine the counter value.

SG

Raise the saw

S0004

TMR T0 K0050 Saw Off RST 022

T0 50

Top Limit

Clamp RST 021

004

S5 JMP SG

One cycle or automatic?

S0005

One Cycle

S0 JMP

005 One Cycle

S1 JMP

005 SG

Monitor for Stop

S0010 Stop

S0 -- S5 RST

010 S0 JMP SG

Automatic shut off

S0011

Count Switch 006 C601 R400

CTR 601 R400 S0 -- S10 RST S0 JMP

Let’s say we wanted to use an operator interface to tell the machine how many pipes to cut. (We’ll assume the number is loaded into a register, R400.) Once the correct number of pipes have been cut, the saw should automatically stop. The following example shows how you would add an automatic shutoff stage to the cutoff saw example by using a counter and a relational contact. (Note, the keystrokes only show how to enter the counter and the relational contact, not the whole program.)

Page 58

3--11

Entering RLL Plus Programs

Enter the Counter CNT

SHF

6

Data display before ENT is pressed 0

1

601 ADDRESS/DATA

ENT

ON/OFF

RUN BATT PWR CPU

0 SG 1 OUT 2 TMR 3 CNT

4 ADR 5 SHF 6 DATA 7 REG

0 STR 1 AND 2 OR 3 NOT

4 ISG 5 JMP 6 SET 7 RST

0 SG 1 OUT 2 TMR 3 CNT

4 ADR 5 SHF 6 DATA 7 REG

0 STR 1 AND 2 OR 3 NOT

4 ISG 5 JMP 6 SET 7 RST

0 SG 1 OUT 2 TMR 3 CNT

4 ADR 5 SHF 6 DATA 7 REG

Enter the relational contact STR

CNT

1

ENT

SHF

6

0

601 ADDRESS/DATA ON/OFF

RUN BATT PWR CPU

Enter the relational contact comparison register R

4

0

0

ENT

(Notice you did not have to press the SHF key before entering the numbers.)

r400 ADDRESS/DATA ON/OFF

RUN BATT PWR CPU

Entering RLL Programs

4 ISG 5 JMP 6 SET 7 RST

Entering Programs

0 STR 1 AND 2 OR 3 NOT

Page 59

3--12

Entering RLL Plus Programs

Entering Shift Registers

Entering RLL Programs

Entering Programs

Shift Registers operate the same in RLL PLUS programs as they do in RLL programs. However, the keystrokes required to enter a Shift Register are different because the SR key is not on the RLL PLUS Handheld Programmer. Also, you do not have a separate range of bits available for use as shift register bits. Instead you have to use the control relays. The following page shows the keystrokes used with this type of Handheld. 001

Data Input

002

Clock Input

SR 200

003

Reset Input

217

Page 60

3--13

Entering RLL Plus Programs

Enter the Data input STR

SHF

1

Data Display before ENT is pressed

001

ENT

ADDRESS/DATA ON/OFF

RUN BATT PWR CPU

0 SG 1 OUT 2 TMR 3 CNT

4 ADR 5 SHF 6 DATA 7 REG

0 STR 1 AND 2 OR 3 NOT

4 ISG 5 JMP 6 SET 7 RST

0 SG 1 OUT 2 TMR 3 CNT

4 ADR 5 SHF 6 DATA 7 REG

0 STR 1 AND 2 OR 3 NOT

4 ISG 5 JMP 6 SET 7 RST

0 SG 1 OUT 2 TMR 3 CNT

4 ADR 5 SHF 6 DATA 7 REG

0 STR 1 AND 2 OR 3 NOT

4 ISG 5 JMP 6 SET 7 RST

0 SG 1 OUT 2 TMR 3 CNT

4 ADR 5 SHF 6 DATA 7 REG

0 STR 1 AND 2 OR 3 NOT

4 ISG 5 JMP 6 SET 7 RST

0 SG 1 OUT 2 TMR 3 CNT

4 ADR 5 SHF 6 DATA 7 REG

Enter the Clock input STR

SHF

2

002

ENT

ADDRESS/DATA ON/OFF

RUN BATT PWR CPU

Enter the Reset input STR

SHF

3

003

ENT

ADDRESS/DATA ON/OFF

RUN BATT PWR CPU

Enter the Shift Register and starting location SET

RST

0

ENT

SHF

2

200

0

ADDRESS/DATA ON/OFF

RUN BATT PWR CPU

Enter the end of the Shift Register SHF

2

1

7

ENT

217 ADDRESS/DATA ON/OFF

RUN BATT PWR CPU

Entering RLL Programs

4 ISG 5 JMP 6 SET 7 RST

Entering Programs

0 STR 1 AND 2 OR 3 NOT