Spec sheet · Koyo
Koyo D4-16TD2 and PLC Direct D4-16TD2 Spec Sheet
Spec sheet4 pagesPDF 809 KB
All 4 pages are below, each with its text.
Covers · 2 models
The models it covers
From the sheet · read page by page
Key facts from this sheet
Each line names its page in the PDF.
A catalog spec sheet for DL405 DC output modules: the D4-16TD2 with 16 current-sourcing outputs and the D4-16TD1 with 16 current-sinking outputs. It also gives the ZIPLink wiring compatibility table for DL405 I/O modules and the tables for working out the power budget of a DL405 base.
- Outputs
- 16, current sourcing p. 1
- Commons
- 2, isolated p. 1
- Operating voltage
- 10.2-26.4VDC p. 1
- Output type
- NPN emitter follower p. 1
- Max current
- 0.5A per point; 3A per common at 50 C, 2.5A per common at 60 C p. 1
- ON voltage drop
- 1.5VDC @ 0.5A p. 1
- Max leakage
- 0.1mA @ 40VDC p. 1
- Max inrush
- 2A for 10ms, 1A for 100ms p. 1
- Fuses
- One 5A fuse per common, not replaceable p. 1
- Terminal block
- Removable, D4-16IOCON (included) p. 1
- Status indicators
- Logic side p. 1
- Minimum load
- 0.2mA p. 1
- ZIPLink cable lengths
- Part number suffix: blank = 0.5m, -1 = 1.0m, -2 = 2.0m p. 2
What this sheet walks you through
- Choosing ZIPLink cables and connector modules for DL405 I/O modules p. 2
- Calculating the power budget of a DL405 base p. 3
- DL405 CPU power supply specifications p. 3
- Looking up the current each DL405 unit supplies or consumes p. 4
Good to know
- Exceeding the power budget may make the system operate unpredictably, with a risk of injury or equipment damage. p. 3
- If more than the 400mA of auxiliary 24VDC is needed, an external 24VDC power supply can be added. p. 3
- The ZIPLink cable part number shows which connector modules and I/O modules work together. p. 2
Questions this sheet answers
Is the D4-16TD2 a sinking or sourcing output module?
It has 16 current-sourcing outputs of the NPN emitter follower type, in 2 isolated commons. p. 1
What voltage does the D4-16TD2 switch?
Its operating voltage is 10.2-26.4VDC, with a peak voltage of 40VDC. p. 1
How much current can a D4-16TD2 output carry?
0.5A per point, and 3A per common at 50 C or 2.5A per common at 60 C. p. 1
What terminal block does the D4-16TD2 use?
A removable terminal block, D4-16IOCON, which is included. p. 1
The file
Size and text
Every page · 4
Read it here
Each page as it is printed, and its words beside it, so a phone can search and copy them.
Page1of 4
Open in the PDF
The text of page 1, from the PDF itself
DC Output Modules
Company Information Systems Overview
D4-16TD1 DC Output
<--->
Outputs per Module Commons per Module Operating Voltage Output Type Peak Voltage
16 (current sinking)
ON Voltage Drop
0.5VDC @ 0.5A 0.2VDC @ 0.1A
Max Current (resistive) Max Leakage Current
0.5A/point - 3A/common
Max Inrush Current
2A for 10ms 1A for 100ms
Minimum Load Base Power Required 5V External DC Required OFF to ON Response ON to OFF Response Terminal Type (included) Status Indicators Weight
0.2mA
Fuses
1 (5A) per common Non-replaceable
2 internally connected 4.5-26.4VDC NPN Open collector 40VDC
D4-16TD2 DC Output Outputs per Module Commons per Module Operating Voltage Output Type Peak Voltage ON Voltage Drop
Programmable Controllers
<--->16 (current sourcing)Field I/O2 (isolated) Software
10.2-26.4VDC NPN Emitter Follower
C-more & other HMI40VDC 1.5VDC @ 0.5ADrives
Max Current (resistive)
0.5A/point 3A/common @ 50° C 2.5A/common @ 60° C
Soft StartersMax Leakage Current0.1mA @ 40VDCMax Inrush Current
2A for 10ms 1A for 100ms
Minimum Load Base Power Required 5V External DC Required OFF to ON Response ON to OFF Response Terminal Type (included) Status Indicators Weight
0.2mA
Fuses
1 (5A) per common Non-replaceable
0.1mA @ 40VDC
200mA max 24VDC ± 10% @ 125mA 0.5ms 0.5ms Removable (D4-16IOCON) Logic side 9.5oz. (270g)
See page 6-57 for part numbers of ZIPLink cables and connection modules compatible with this I/O module.
Motors & Gearbox Steppers/ Servos Motor Controls
400mA max None
Proximity Sensors
1ms 1ms Removable (D4-16IOCON)
Photo Sensors Limit Switches
Logic side 9.8oz. (280g)
Encoders Current Sensors
See page 6-57 for part numbers of ZIPLink cables and connection modules compatible with this I/O module.
Pressure Sensors Temperature Sensors Pushbuttons/ Lights Process Relays/ Timers Comm. Terminal Blocks & Wiring Power Circuit Protection Enclosures Tools Pneumatics Appendix Product Index Part # Index
Volume 13
w w w. a u to m at i o n d i re c t . c o m / d l 405
Programmable Controllers
e6-67
Page2of 4
Open in the PDF
The text of page 2, from the PDF itself
Wiring System for DL405 PLCs
Company Information Systems Overview Programmable Controllers
Cut PLC wiring time to minutes instead of hours The ZIPLink wiring system eliminates the normally tedious process of wiring PLC I/O to terminal blocks. Simply plug one end of a ZIPLink pre-wired terminal block cable into your I/O module and the other end into a ZIPLink connector module. It’s that easy. ZIPLinks use half the space, at a fraction of the total cost of terminal blocks.
Field I/O Software C-more & other HMI
ZIPLinks are available in a variety of styles to suit your needs, including fused, relay and sensor/LED connector modules. ZIPLinks are available for all DL405 Series PLC discrete and analog input and output modules.
Drives
For complete information see ZIPLinks in the Terminal Blocks and Wiring Solutions section.
Soft Starters
Specify your ZIPLink system
Motors & Gearbox
Use the Compatibility Matrix table below: Steppers/ Servos
Step 1 Step 2 Step 3
Locate the I/O module part number. Locate Connector Module Type. (Feedthrough Module, Fuse Module, etc...) Select the cable length by replacing the # symbol with: Blank = 0.5m, -1 = 1.0m, -2 = 2.0m1 1 Note: Cable part number denotes compatibility between Connector Module and I/O Modules.
Motor Controls Proximity Sensors
ZipLink Wiring System Compatibility Matrix for DL405 PLCs Step 2: Connector Module Feedthrough Modules Type ZL-RTB40 Step 1: I/O Number of ZL-RTB20 Module Terminals Step 3: Cables
Fuse ModulesRelay ModulesSensor Input ModulesZL-RFU20ZL-RRL16-24ZL-LTB16-24ZL-RFU40Pigtail CableZL-LTB32-24Limit SwitchesI/O Module
Inputs D4-08ND3S D4-16ND2 D4-16ND2F D4-32ND3-1 D4-32ND3-2 D4-64ND2* D4-08NA** D4-16NA D4-16NA-1 D4-16NE3 F4-08NE3S
20 20 20 40 40 40 11 20 20 20 20
ZL-D4-CBL20# ZL-D4-CBL20# ZL-D4-CBL20#
Encoders
ZL-D4-CBL20# ZL-D4-CBL20# ZL-D24-CBL40# ZL-D24-CBL40# ZL-D24-CBL40#
Current Sensors
ZL-D24-CBL40# ZL-D24-CBL40#P ZL-D24-CBL40# ZL-D24-CBL40#P ZL-D24-CBL40# ZL-D24-CBL40#P
Pressure Sensors Temperature Sensors
ZL-D4-CBL20# ZL-D4-CBL20# ZL-D4-CBL20# ZL-D4-CBL20#
Pushbuttons/ Lights
ZL-D4-CBL20# Process
Outputs 11 D4-08TD1** 20 F4-08TD1S** 20 D4-16TD1 20 D4-16TD2 40 D4-32TD1 40 D4-32TD1-1 40 D4-32TD2 40 D4-64TD1* 11 D4-08TA** 20 D4-16TA 11 D4-08TR** F4-08TRS-1**** 20 F4-08TRS-2**** 20 20 D4-16TR***
Photo Sensors
ZL-D4-CBL20# ZL-D4-CBL20#
Relays/ Timers Comm.
ZL-D4-CBL20# ZL-D4-CBL20# ZL-D24-CBL40# ZL-D24-CBL40# ZL-D24-CBL40# ZL-D24-CBL40#
ZL-D24-CBL40# ZL-D24-CBL40# ZL-D24-CBL40# ZL-D24-CBL40#
ZL-D24-CBL40#P ZL-D24-CBL40#P ZL-D24-CBL40#P ZL-D24-CBL40#P
Terminal Blocks & Wiring Power Circuit Protection
ZL-D4-CBL20#
ZL-D4-CBL20# Enclosures
ZL-D4-CBL20# ZL-D4-CBL20# ZL-D4-CBL20#
ToolsZL-D4-CBL20#Pneumatics
- The D4-64ND2 and D4-64TD1 modules have two 32-point connectors and require 2 ZIPLink cables and 2 ZIPLink connector modules. Appendix
** These modules are not supported by the ZIPLink wiring system. *** Caution: The D4-16TR relay outputs are derated not to exceed 2 Amps per point and 4 Amps per common when used with the ZIPLink wiring system.
Product Index
**** The F4-08TRS-1 and F4-08TRS-2 are derated not to exceed 2 Amps per point and 2 Amps per common when used with the ZIPLink wiring system. ZIPLinks Connector Modules specifications begin on page 26-56
Part # Index
ZIPLinks Cables specifications begin on page 26-74 Volume 13
w w w. a u to m at i o n d i re c t . c o m / d l 405
Programmable Controllers
e6-57
Page3of 4
Open in the PDF
The text of page 3, from the PDF itself
Check the Power Budget Verify your power budget requirements
This logo is placed next to I/O modules that are supported by the ZIPLink connection systems. See the I/O module specifi-
Calculating your power usage
Your I/O configuration choice can be affected by the power requirements of the I/O modules you choose. When determining the types and quantity of I/O modules you will be using, it is important to remember there is a limited amount of power available from the power supply.
cations at the end of this section.
The following example shows how to calculate the power budget for the DL405 system. The example is constructed around a single 8-slot base using the devices shown. It is recommended you construct a similar table for each base in your system.
The chart on the opposite page indicates the power supplied and used by each DL405 device. The adjacent chart shows an example of how to calculate the power used by your particular system. These two charts should make it easy for you to determine if the devices you have chosen fit within the power budget of your system configuration.
A Base Number 0
B
Use ZIPLinks to reduce power requirements If your application requires a lot of relay outputs, consider using the ZipLink AC or DC relay output modules. These modules can switch high current (10A) loads without putting a load on your base power budget. Refer to page 6-57 for more information.
5 VDC (mA)
External 24 VDC Power (mA)
CURRENT SUPPLIED CPU/Expansion Unit /Remote Slave
D4-440 CPUC3700400
CURRENT REQUIRED SLOT 0 SLOT 1 SLOT 2 SLOT 3 SLOT 4 SLOT 5 SLOT 6 SLOT 7
D4-16ND2+150+0D4-16ND2+150+0F4-04DA+120+100D4-08ND3S+100+0D4-08ND3S+100+0D4-16TD2+100+0D4-16TD2+100+0D4-16TR+1000+0
BASE Handheld Programmer
D4-08B+80+0D4-HPP+320+0
E Maximum Current Required
2820
100
F Remaining Current Available
3700-2820=880
400-100=300
If the I/O you have chosen exceeds the maximum power available from the power supply, you can resolve the problem by shifting some of the modules to an expansion base or remote I/O base (if you are using remote I/O). Warning: It is extremely important to calculate the power budget correctly. If you exceed the power budget, the system may operate in an unpredictable manner which may result in a risk of personal injury or equipment damage.
Device TypeDOTHER
1. Using a chart similar to the 3one above, fill in column 2. 2. Using the tables on the opposite page, enter the current supplied and used by each device (columns 3 and 4). Pay special attention to the current supplied by the CPU, Expansion Unit, and Remote Slave since they differ. Devices which fall into the "Other" category (Row D) are devices such as the Base and the Handheld programmer, which also have power requirements, but do not plug directly into the base. 3. Add the current used by the system devices (columns 3 and 4) starting with Slot 0 and put the total in the row labeled "maximum current required" (Row E). 4. Subtract the row labeled "Maximum current required" (Row E), from the row labeled "Current Supplied" (Row B). Place the difference in the row labeled "Remaining Current Available" (Row F). 5. If "Maximum Current Required" is greater than "Current Supplied" in either column 3 or 4, the power budget will be exceeded. It will be unsafe to use this configuration and you will need to restructure your I/O configuration. Note the auxiliary 24 VDC power supply does not need to supply all the external power. If you need more than the 400mA supplied, you can add an external 24VDC power supply. This will help keep you within your power budget for external power.
DL405 CPU power supply specifications and power requirements Specification Part Numbers
AC Powered Units D4-450, D4-440, D4-430, D4-EX (expansion base unit), D4-RS (remote slave unit)
Voltage Withstand (dielectric) Insulation Resistance
24 VDC Powered Units D4-450DC-1, D4-440DC-1, D4-EXDC (expansion base unit), D4-RSDC (remote slave unit)
125 VDC Powered Units D4-450DC-2 D4-440DC-2
1 minute @ 1,500 VAC between primary, secondary, field ground, and run relay > at 500VDC
Input Voltage Range
85-132 VAC (110 range) 170-264 VAC (220 range
20-28 VDC (24 VDC) with less than 10% ripple
90-146 VDC (125 VDC) with less than 10% ripple
Maximum Inrush Current Maximum Power
20 A20 A20 A50 VA38 W30 WVolume 13e6-24
Programmable Controllers
1 - 80 0 - 633 - 0405
Page4of 4
Open in the PDF
The text of page 4, from the PDF itself
Power Requirements
Company Information Systems Overview Programmable Controllers
Power Supplied CPUs/Remote Units/ Expansion Units
5 VDC Current Supplied in mA
24V Aux Power Supplied in mA
CPUs/Remote Units/Expansion Units
5V Current Supplied in mA
24VAux. Power Supplied in mA
D4-430 CPU D4-440 CPU D4-440DC-1 CPU D4-440DC-2 CPU D4-450 CPU D4-450DC-1 CPU D4-450DC-2 CPU
3700 3700 3700 3700 3100 3100 3100
400 400 NONE NONE 400 NONE NONE
D4-EX D4-EXDC D4-EXDC-2 D4-RS D4-RSDC H4-EBC H4-EBC-F
4000 4000 3700 3700 3700 3470 3300
400 NONE NONE 400 NONE 400 400
Field I/O Software C-more & other HMI Drives
Power Consumed Power-consuming Device I/O Bases
5V Current Consumed
D4-04B-1 D4-06B-1 D4-08B-1
80 80 80
External 24VD Current Required
NONE NONE NONE
DC Input Modules
D4-08ND3S D4-16ND2 D4-16ND2F D4-32ND3-1 D4-32ND3-2 D4-64ND2
100 150 150 150 150 300 max.
NONE NONE NONE NONE NONE NONE
Power-consuming 5V Current Device Consumed Analog Modules (continued)
External 24VDC Current Required
F4-16AD-1 F4-16AD-2 F4-04DA-1 F4-04DA-2 F4-04DAS-1 F4-04DAS-2 F4-08DA-1 F4-08DA-2 F4-16DA-1 F4-16DA-2 F4-08RTD F4-08THM-n F4-08THM
100 100 75+20per circuit 90 60 per circuit 60 per circuit 100+20 per circuit 150 100+20 per circuit 25 max. NONE 50 60
75 75 70 90 60 60 90 80 90 80 80 120 110
Motors & Gearbox
100 150
Photo Sensors Limit Switches
NONE NONEH4-ERM H4-ERM-F D4-RM320 450 300NONE NONE NONE
Pressure Sensors Temperature Sensors
150 90
D4-08TD1 F4-08TD1S D4-16TD1 D4-16TD2 D4-32TD1 D4-32TD1-1 D4-32TD2
150 295 200 400 250 250 350
D4-64TD1800NONE NONE
35 NONE 125 NONE 140 140 (15V) 120 (4A max including loads) NONE
Communications and Networking H4-ECOM100 H4-ECOM H4-ECOM-F D4-DCM F4-MAS-MB FA-UNICON
300 530 670 500 235 NONE
Pushbuttons/ Lights
NONE NONE NONE NONE NONE 65
Process Relays/ Timers Comm.
CoProcessors F4-CP128-1
Terminal Blocks & Wiring
305
NONE Power
AC Output Modules 250 450
NONE NONE
Relay Output Modules D4-08TR F4-08TRS-1 F4-08TRS D4-16TR
Proximity SensorsCurrent SensorsDC Output ModulesD4-08TA D4-16TAMotor ControlsEncoders
AC/DC Input Modules D4-16NE3 F4-08NE3S
Steppers/ Servos
Remote I/O
AC Input Modules D4-08NA D4-16NA
Soft Starters550 575 575 1000NONE NONE NONE NONE
Specialty Modules H4-CTRIO D4-INT D4-HSC F4-16PID F4-8MPI D4-16SIM F4-4LTC
Circuit Protection
400 100 300 160 225 150 280
NONE NONE NONE NONE 170 NONE 75
Enclosures Tools Pneumatics Appendix
Analog ModulesProgramming 320NONEProduct IndexDV-1000150NONEPart # IndexC-more Micro-Graphic210NONE
D4-HPP-1 (Handheld Prog.) F4-04AD F4-04ADS F4-08AD
85 270 75100 120 90Operator InterfaceVolume 13
w w w. a u to m at i o n d i re c t . c o m / d l 405
Programmable Controllers
e6-25