Page 1 of Koyo D4-16TD2 and PLC Direct D4-16TD2 Spec Sheet

Spec sheet · Koyo

Koyo D4-16TD2 and PLC Direct D4-16TD2 Spec Sheet

Spec sheet4 pagesPDF 809 KB

All 4 pages are below, each with its text.

Download the PDF809 KB

Covers · 2 models

The models it covers

From the sheet · read page by page

Key facts from this sheet

Each line names its page in the PDF.

A catalog spec sheet for DL405 DC output modules: the D4-16TD2 with 16 current-sourcing outputs and the D4-16TD1 with 16 current-sinking outputs. It also gives the ZIPLink wiring compatibility table for DL405 I/O modules and the tables for working out the power budget of a DL405 base.

Outputs
16, current sourcing p. 1
Commons
2, isolated p. 1
Operating voltage
10.2-26.4VDC p. 1
Output type
NPN emitter follower p. 1
Max current
0.5A per point; 3A per common at 50 C, 2.5A per common at 60 C p. 1
ON voltage drop
1.5VDC @ 0.5A p. 1
Max leakage
0.1mA @ 40VDC p. 1
Max inrush
2A for 10ms, 1A for 100ms p. 1
Fuses
One 5A fuse per common, not replaceable p. 1
Terminal block
Removable, D4-16IOCON (included) p. 1
Status indicators
Logic side p. 1
Minimum load
0.2mA p. 1
ZIPLink cable lengths
Part number suffix: blank = 0.5m, -1 = 1.0m, -2 = 2.0m p. 2

What this sheet walks you through

  • Choosing ZIPLink cables and connector modules for DL405 I/O modules p. 2
  • Calculating the power budget of a DL405 base p. 3
  • DL405 CPU power supply specifications p. 3
  • Looking up the current each DL405 unit supplies or consumes p. 4

Good to know

  • Exceeding the power budget may make the system operate unpredictably, with a risk of injury or equipment damage. p. 3
  • If more than the 400mA of auxiliary 24VDC is needed, an external 24VDC power supply can be added. p. 3
  • The ZIPLink cable part number shows which connector modules and I/O modules work together. p. 2

Questions this sheet answers

Is the D4-16TD2 a sinking or sourcing output module?

It has 16 current-sourcing outputs of the NPN emitter follower type, in 2 isolated commons. p. 1

What voltage does the D4-16TD2 switch?

Its operating voltage is 10.2-26.4VDC, with a peak voltage of 40VDC. p. 1

How much current can a D4-16TD2 output carry?

0.5A per point, and 3A per common at 50 C or 2.5A per common at 60 C. p. 1

What terminal block does the D4-16TD2 use?

A removable terminal block, D4-16IOCON, which is included. p. 1

The file

Size and text

Pages4
PDF809 KB
TextText from the PDF itself.

Every page · 4

Read it here

Each page as it is printed, and its words beside it, so a phone can search and copy them.

Page 1 of Koyo D4-16TD2 and PLC Direct D4-16TD2 Spec Sheet

The text of page 1, from the PDF itself

DC Output Modules

Company Information Systems Overview

D4-16TD1 DC Output

<--->

Outputs per Module Commons per Module Operating Voltage Output Type Peak Voltage

16 (current sinking)

ON Voltage Drop

0.5VDC @ 0.5A 0.2VDC @ 0.1A

Max Current (resistive) Max Leakage Current

0.5A/point - 3A/common

Max Inrush Current

2A for 10ms 1A for 100ms

Minimum Load Base Power Required 5V External DC Required OFF to ON Response ON to OFF Response Terminal Type (included) Status Indicators Weight

0.2mA

Fuses

1 (5A) per common Non-replaceable

2 internally connected 4.5-26.4VDC NPN Open collector 40VDC

D4-16TD2 DC Output Outputs per Module Commons per Module Operating Voltage Output Type Peak Voltage ON Voltage Drop

Programmable Controllers

<--->16 (current sourcing)Field I/O2 (isolated) Software

10.2-26.4VDC NPN Emitter Follower

C-more & other HMI40VDC 1.5VDC @ 0.5ADrives

Max Current (resistive)

0.5A/point 3A/common @ 50° C 2.5A/common @ 60° C

Soft StartersMax Leakage Current0.1mA @ 40VDCMax Inrush Current

2A for 10ms 1A for 100ms

Minimum Load Base Power Required 5V External DC Required OFF to ON Response ON to OFF Response Terminal Type (included) Status Indicators Weight

0.2mA

Fuses

1 (5A) per common Non-replaceable

0.1mA @ 40VDC

200mA max 24VDC ± 10% @ 125mA 0.5ms 0.5ms Removable (D4-16IOCON) Logic side 9.5oz. (270g)

See page 6-57 for part numbers of ZIPLink cables and connection modules compatible with this I/O module.

Motors & Gearbox Steppers/ Servos Motor Controls

400mA max None

Proximity Sensors

1ms 1ms Removable (D4-16IOCON)

Photo Sensors Limit Switches

Logic side 9.8oz. (280g)

Encoders Current Sensors

See page 6-57 for part numbers of ZIPLink cables and connection modules compatible with this I/O module.

Pressure Sensors Temperature Sensors Pushbuttons/ Lights Process Relays/ Timers Comm. Terminal Blocks & Wiring Power Circuit Protection Enclosures Tools Pneumatics Appendix Product Index Part # Index

Volume 13

w w w. a u to m at i o n d i re c t . c o m / d l 405

Programmable Controllers

e6-67

Page 2 of Koyo D4-16TD2 and PLC Direct D4-16TD2 Spec Sheet

The text of page 2, from the PDF itself

Wiring System for DL405 PLCs

Company Information Systems Overview Programmable Controllers

Cut PLC wiring time to minutes instead of hours The ZIPLink wiring system eliminates the normally tedious process of wiring PLC I/O to terminal blocks. Simply plug one end of a ZIPLink pre-wired terminal block cable into your I/O module and the other end into a ZIPLink connector module. It’s that easy. ZIPLinks use half the space, at a fraction of the total cost of terminal blocks.

Field I/O Software C-more & other HMI

ZIPLinks are available in a variety of styles to suit your needs, including fused, relay and sensor/LED connector modules. ZIPLinks are available for all DL405 Series PLC discrete and analog input and output modules.

Drives

For complete information see ZIPLinks in the Terminal Blocks and Wiring Solutions section.

Soft Starters

Specify your ZIPLink system

Motors & Gearbox

Use the Compatibility Matrix table below: Steppers/ Servos

Step 1 Step 2 Step 3

Locate the I/O module part number. Locate Connector Module Type. (Feedthrough Module, Fuse Module, etc...) Select the cable length by replacing the # symbol with: Blank = 0.5m, -1 = 1.0m, -2 = 2.0m1 1 Note: Cable part number denotes compatibility between Connector Module and I/O Modules.

Motor Controls Proximity Sensors

ZipLink Wiring System Compatibility Matrix for DL405 PLCs Step 2: Connector Module Feedthrough Modules Type ZL-RTB40 Step 1: I/O Number of ZL-RTB20 Module Terminals Step 3: Cables

Fuse ModulesRelay ModulesSensor Input ModulesZL-RFU20ZL-RRL16-24ZL-LTB16-24ZL-RFU40Pigtail CableZL-LTB32-24Limit SwitchesI/O Module

Inputs D4-08ND3S D4-16ND2 D4-16ND2F D4-32ND3-1 D4-32ND3-2 D4-64ND2* D4-08NA** D4-16NA D4-16NA-1 D4-16NE3 F4-08NE3S

20 20 20 40 40 40 11 20 20 20 20

ZL-D4-CBL20# ZL-D4-CBL20# ZL-D4-CBL20#

Encoders

ZL-D4-CBL20# ZL-D4-CBL20# ZL-D24-CBL40# ZL-D24-CBL40# ZL-D24-CBL40#

Current Sensors

ZL-D24-CBL40# ZL-D24-CBL40#P ZL-D24-CBL40# ZL-D24-CBL40#P ZL-D24-CBL40# ZL-D24-CBL40#P

Pressure Sensors Temperature Sensors

ZL-D4-CBL20# ZL-D4-CBL20# ZL-D4-CBL20# ZL-D4-CBL20#

Pushbuttons/ Lights

ZL-D4-CBL20# Process

Outputs 11 D4-08TD1** 20 F4-08TD1S** 20 D4-16TD1 20 D4-16TD2 40 D4-32TD1 40 D4-32TD1-1 40 D4-32TD2 40 D4-64TD1* 11 D4-08TA** 20 D4-16TA 11 D4-08TR** F4-08TRS-1**** 20 F4-08TRS-2**** 20 20 D4-16TR***

Photo Sensors

ZL-D4-CBL20# ZL-D4-CBL20#

Relays/ Timers Comm.

ZL-D4-CBL20# ZL-D4-CBL20# ZL-D24-CBL40# ZL-D24-CBL40# ZL-D24-CBL40# ZL-D24-CBL40#

ZL-D24-CBL40# ZL-D24-CBL40# ZL-D24-CBL40# ZL-D24-CBL40#

ZL-D24-CBL40#P ZL-D24-CBL40#P ZL-D24-CBL40#P ZL-D24-CBL40#P

Terminal Blocks & Wiring Power Circuit Protection

ZL-D4-CBL20#

ZL-D4-CBL20# Enclosures

ZL-D4-CBL20# ZL-D4-CBL20# ZL-D4-CBL20#

ToolsZL-D4-CBL20#Pneumatics

  • The D4-64ND2 and D4-64TD1 modules have two 32-point connectors and require 2 ZIPLink cables and 2 ZIPLink connector modules. Appendix

** These modules are not supported by the ZIPLink wiring system. *** Caution: The D4-16TR relay outputs are derated not to exceed 2 Amps per point and 4 Amps per common when used with the ZIPLink wiring system.

Product Index

**** The F4-08TRS-1 and F4-08TRS-2 are derated not to exceed 2 Amps per point and 2 Amps per common when used with the ZIPLink wiring system. ZIPLinks Connector Modules specifications begin on page 26-56

Part # Index

ZIPLinks Cables specifications begin on page 26-74 Volume 13

w w w. a u to m at i o n d i re c t . c o m / d l 405

Programmable Controllers

e6-57

Page 3 of Koyo D4-16TD2 and PLC Direct D4-16TD2 Spec Sheet

The text of page 3, from the PDF itself

Check the Power Budget Verify your power budget requirements

This logo is placed next to I/O modules that are supported by the ZIPLink connection systems. See the I/O module specifi-

Calculating your power usage

Your I/O configuration choice can be affected by the power requirements of the I/O modules you choose. When determining the types and quantity of I/O modules you will be using, it is important to remember there is a limited amount of power available from the power supply.

cations at the end of this section.

The following example shows how to calculate the power budget for the DL405 system. The example is constructed around a single 8-slot base using the devices shown. It is recommended you construct a similar table for each base in your system.

The chart on the opposite page indicates the power supplied and used by each DL405 device. The adjacent chart shows an example of how to calculate the power used by your particular system. These two charts should make it easy for you to determine if the devices you have chosen fit within the power budget of your system configuration.

A Base Number 0

B

Use ZIPLinks to reduce power requirements If your application requires a lot of relay outputs, consider using the ZipLink AC or DC relay output modules. These modules can switch high current (10A) loads without putting a load on your base power budget. Refer to page 6-57 for more information.

5 VDC (mA)

External 24 VDC Power (mA)

CURRENT SUPPLIED CPU/Expansion Unit /Remote Slave

D4-440 CPUC3700400

CURRENT REQUIRED SLOT 0 SLOT 1 SLOT 2 SLOT 3 SLOT 4 SLOT 5 SLOT 6 SLOT 7

D4-16ND2+150+0D4-16ND2+150+0F4-04DA+120+100D4-08ND3S+100+0D4-08ND3S+100+0D4-16TD2+100+0D4-16TD2+100+0D4-16TR+1000+0

BASE Handheld Programmer

D4-08B+80+0D4-HPP+320+0

E Maximum Current Required

2820

100

F Remaining Current Available

3700-2820=880

400-100=300

If the I/O you have chosen exceeds the maximum power available from the power supply, you can resolve the problem by shifting some of the modules to an expansion base or remote I/O base (if you are using remote I/O). Warning: It is extremely important to calculate the power budget correctly. If you exceed the power budget, the system may operate in an unpredictable manner which may result in a risk of personal injury or equipment damage.

Device TypeDOTHER

1. Using a chart similar to the 3one above, fill in column 2. 2. Using the tables on the opposite page, enter the current supplied and used by each device (columns 3 and 4). Pay special attention to the current supplied by the CPU, Expansion Unit, and Remote Slave since they differ. Devices which fall into the "Other" category (Row D) are devices such as the Base and the Handheld programmer, which also have power requirements, but do not plug directly into the base. 3. Add the current used by the system devices (columns 3 and 4) starting with Slot 0 and put the total in the row labeled "maximum current required" (Row E). 4. Subtract the row labeled "Maximum current required" (Row E), from the row labeled "Current Supplied" (Row B). Place the difference in the row labeled "Remaining Current Available" (Row F). 5. If "Maximum Current Required" is greater than "Current Supplied" in either column 3 or 4, the power budget will be exceeded. It will be unsafe to use this configuration and you will need to restructure your I/O configuration. Note the auxiliary 24 VDC power supply does not need to supply all the external power. If you need more than the 400mA supplied, you can add an external 24VDC power supply. This will help keep you within your power budget for external power.

DL405 CPU power supply specifications and power requirements Specification Part Numbers

AC Powered Units D4-450, D4-440, D4-430, D4-EX (expansion base unit), D4-RS (remote slave unit)

Voltage Withstand (dielectric) Insulation Resistance

24 VDC Powered Units D4-450DC-1, D4-440DC-1, D4-EXDC (expansion base unit), D4-RSDC (remote slave unit)

125 VDC Powered Units D4-450DC-2 D4-440DC-2

1 minute @ 1,500 VAC between primary, secondary, field ground, and run relay > at 500VDC

Input Voltage Range

85-132 VAC (110 range) 170-264 VAC (220 range

20-28 VDC (24 VDC) with less than 10% ripple

90-146 VDC (125 VDC) with less than 10% ripple

Maximum Inrush Current Maximum Power

20 A20 A20 A50 VA38 W30 WVolume 13e6-24

Programmable Controllers

1 - 80 0 - 633 - 0405

Page 4 of Koyo D4-16TD2 and PLC Direct D4-16TD2 Spec Sheet

The text of page 4, from the PDF itself

Power Requirements

Company Information Systems Overview Programmable Controllers

Power Supplied CPUs/Remote Units/ Expansion Units

5 VDC Current Supplied in mA

24V Aux Power Supplied in mA

CPUs/Remote Units/Expansion Units

5V Current Supplied in mA

24VAux. Power Supplied in mA

D4-430 CPU D4-440 CPU D4-440DC-1 CPU D4-440DC-2 CPU D4-450 CPU D4-450DC-1 CPU D4-450DC-2 CPU

3700 3700 3700 3700 3100 3100 3100

400 400 NONE NONE 400 NONE NONE

D4-EX D4-EXDC D4-EXDC-2 D4-RS D4-RSDC H4-EBC H4-EBC-F

4000 4000 3700 3700 3700 3470 3300

400 NONE NONE 400 NONE 400 400

Field I/O Software C-more & other HMI Drives

Power Consumed Power-consuming Device I/O Bases

5V Current Consumed

D4-04B-1 D4-06B-1 D4-08B-1

80 80 80

External 24VD Current Required

NONE NONE NONE

DC Input Modules

D4-08ND3S D4-16ND2 D4-16ND2F D4-32ND3-1 D4-32ND3-2 D4-64ND2

100 150 150 150 150 300 max.

NONE NONE NONE NONE NONE NONE

Power-consuming 5V Current Device Consumed Analog Modules (continued)

External 24VDC Current Required

F4-16AD-1 F4-16AD-2 F4-04DA-1 F4-04DA-2 F4-04DAS-1 F4-04DAS-2 F4-08DA-1 F4-08DA-2 F4-16DA-1 F4-16DA-2 F4-08RTD F4-08THM-n F4-08THM

100 100 75+20per circuit 90 60 per circuit 60 per circuit 100+20 per circuit 150 100+20 per circuit 25 max. NONE 50 60

75 75 70 90 60 60 90 80 90 80 80 120 110

Motors & Gearbox

100 150

Photo Sensors Limit Switches

NONE NONEH4-ERM H4-ERM-F D4-RM320 450 300NONE NONE NONE

Pressure Sensors Temperature Sensors

150 90

D4-08TD1 F4-08TD1S D4-16TD1 D4-16TD2 D4-32TD1 D4-32TD1-1 D4-32TD2

150 295 200 400 250 250 350

D4-64TD1800NONE NONE

35 NONE 125 NONE 140 140 (15V) 120 (4A max including loads) NONE

Communications and Networking H4-ECOM100 H4-ECOM H4-ECOM-F D4-DCM F4-MAS-MB FA-UNICON

300 530 670 500 235 NONE

Pushbuttons/ Lights

NONE NONE NONE NONE NONE 65

Process Relays/ Timers Comm.

CoProcessors F4-CP128-1

Terminal Blocks & Wiring

305

NONE Power

AC Output Modules 250 450

NONE NONE

Relay Output Modules D4-08TR F4-08TRS-1 F4-08TRS D4-16TR

Proximity SensorsCurrent SensorsDC Output ModulesD4-08TA D4-16TAMotor ControlsEncoders

AC/DC Input Modules D4-16NE3 F4-08NE3S

Steppers/ Servos

Remote I/O

AC Input Modules D4-08NA D4-16NA

Soft Starters550 575 575 1000NONE NONE NONE NONE

Specialty Modules H4-CTRIO D4-INT D4-HSC F4-16PID F4-8MPI D4-16SIM F4-4LTC

Circuit Protection

400 100 300 160 225 150 280

NONE NONE NONE NONE 170 NONE 75

Enclosures Tools Pneumatics Appendix

Analog ModulesProgramming 320NONEProduct IndexDV-1000150NONEPart # IndexC-more Micro-Graphic210NONE

D4-HPP-1 (Handheld Prog.) F4-04AD F4-04ADS F4-08AD

85 270 75100 120 90Operator InterfaceVolume 13

w w w. a u to m at i o n d i re c t . c o m / d l 405

Programmable Controllers

e6-25

More documents · 1

For the same models