Key facts from this manual

Each line names its page in the PDF.

Four catalog pages on DL405 serial remote I/O and the DL405 power budget. They cover the D4-RM remote master and the D4-RS and D4-RSDC remote slaves, and give the power supply specifications of the DL405 CPUs, including the 24 VDC D4-450DC-1. They help the reader plan a remote I/O network and check that a base stays within its power budget.

What it is
D4-450DC-1: a 24 VDC powered DL405 CPU p. 3, 4
Input voltage
20-28 VDC (24 VDC) with less than 10% ripple p. 3
Maximum inrush
20 A p. 3
Dielectric withstand
1 minute @ 1,500 VAC between primary, secondary, field ground, and run relay p. 3
Built-in remote master
D4-450: D4-RM remote master function built into the 25-pin CPU port p. 1
Remote capacity
D4-450: up to three remote masters (at most 2 D4-RM, one channel via the 25-pin CPU port) and 1536 slave points p. 1, 2
Remote link
RS485 over shielded twisted pair at 38.4K baud; Belden 9841 or equivalent; 3,300 ft (1,000 m) maximum p. 1, 2
Slaves per channel
Seven remote slaves per channel, daisy-chained, each on a DL405 base of any size p. 1, 2
Remote slave power
D4-RS: 110VAC/220 VAC; D4-RSDC: 24VDC p. 2
Remote module environment
0 to 60 C (32 to 140 F), 5% to 95% humidity non-condensing p. 2
Remote addressing
Slave I/O uses remote I/O points by default; standard I/O addresses are an option p. 2

What this manual walks you through

  • Planning serial remote I/O with a remote master and up to seven slaves p. 1, 2
  • Calculating the power budget of a DL405 base p. 3, 4
  • Looking up the current each DL405 module consumes p. 4

Good to know

  • Remote I/O updates are not tied to the CPU scan, so use it only where points need not update every scan. p. 1
  • Exceeding the power budget can make the system operate unpredictably. p. 3
  • If the modules exceed the supply, some can be moved to an expansion base or remote I/O base. p. 3

Questions this manual answers

What input voltage does the D4-450DC-1 take?

The 24 VDC powered DL405 units take 20-28 VDC with less than 10% ripple. p. 3

Does the D4-450 need a D4-RM module for remote I/O?

No. The D4-450 has the D4-RM function built into its 25-pin port, though a D4-RM can also be used. p. 1

How far can DL405 remote slaves be from the master?

Up to 3,300 feet (1,000 m) of twisted pair cable, with the slaves daisy-chained. p. 1

What cable is recommended for DL405 remote I/O?

Belden 9841 or equivalent. p. 2

The file

Size and text

Pages4
PDF402 KB
TextText from the PDF itself.

Every page · 4

Read it here

Each page as it is printed, and its words beside it, so a phone can search and copy them.

Page 1 of Koyo D4-450DC-1 Manual

The text of page 1, from the PDF itself

Serial Remote I/O Master/Slave Modules Remote master

Remote I/O Master Module D4-RM

<--->

3,300 ft (1,000 m) Max.

Remote slaves

Remote I/O Slave Module

Maximum of seven remote bases per channel

D4-RS <---> D4-RSDC <--->

Remote master

Remote slave

You can assign normal input and output addresses to the remote points, or you can assign special remote I/O addresses. The Remote Master sends the remote I/O information to the CPU. The communication between the Remote Master and the CPU is asynchronous to the CPU scan. For this reason, remote I/O applications should be

limited to those that do not require the remote I/O points to be updated with every CPU scan.

Overview The DL405 offers full-size remote I/O. The goal of remote I/O is to reduce wiring costs by allowing I/O points to be located near the devices they are controlling. The chart at the bottom of this page shows the capacity for each CPU. The D4-450 has the D4-RM functionality built into the 25-pin port directly on the CPU. However, you can also choose to use the D4-RM discussed here. Here’s how it works: A special module called the Remote Master is placed in the CPU base. This Master module controls up to seven Remote Slaves. The Remote Slaves are connected to the Master in a daisy-chain manner over a twisted pair communication cable (maximum length of 3,300 feet or 1,000m). Each Remote Slave attaches to a DL405 base (any size). Standard DL405 modules populate the remote bases.

D4-450 Maximum number of remote masters supported Maximum I/O points supported Maximum I/O points supported per channel Maximum number of remote I/O bases per channel

D4-440D4-4303*2215361024512512512512777

*max. of 2 D4-RM, 1 channel is via 25-pin CPU port

Volume 14

e6-32

Programmable Controllers

1 - 80 0 - 633 - 0405

Page 2 of Koyo D4-450DC-1 Manual

The text of page 2, from the PDF itself

Serial Remote I/O Master/Slave Modules

Company Information Systems Overview Programmable Controllers

Remote Slave

Remote Master

Field I/O Software C-more & other HMI Drives

Run relay Soft Starters

24 VDC auxiliary Power

Motors & Gearbox

Logic ground Remote Channel Connector

Remote Channel Connector

Chassis groundMotor ControlsAC powerRun relaySteppers/ ServosProximity Sensors110/220 voltage select

Photo Sensors Limit Switches

Module Type

Intelligent device

maximum for D4-430 and Number of Masters Two D4-440 per CPU Three maximum for D4-450

Maximum Slaves Supported

RS485 via twisted pair with shield @ 38.4K baud

Operating Environment

0°C to 60°C (32°F to 140°F), 5% to 95% humidity (non-condensing)

Belden 9841 or equivalent

Current Sensors

Maximum Slave Points per CPU

512 for D4-430 1024 for D4-440 1536 for D4-450

I/O Addresses Used

I/O modules in slave bases do not automatically consume any standard input and output points. They consume remote I/O points at a rate equal to the number of I/O points in each base. However, you can choose to use standard I/O addresses as an option.

Seven slaves per channel

Communication to Slaves Recommended Cable Transmission Distance Terminal Type

Encoders

Remote Slave Specifications

Remote Master Specifications

Pressure Sensors Temperature Sensors

Terminal Type Operating Environment

Fixed

Power Required

110VAC/220 VAC (D4-RS) 24VDC (D4-RSDC)

ProcessManufacturerKoyo ElectronicsRelays/ Timers

0°C to 60°C (32°F to 140°F), 5% to 95% humidity (non-condensing)

3,300 ft. maximumPushbuttons/ LightsComm.Fixed

Terminal Blocks & Wiring Power

Internal Power Consumption Manufacturer

300 mA maximum

Circuit Protection

Koyo Electronics Enclosures Tools Pneumatics Safety Appendix Product Index Part # Index Volume 14

w w w. a u to m at i o n d i re c t . c o m / d l 405

Programmable Controllers

e6-33

Page 3 of Koyo D4-450DC-1 Manual

The text of page 3, from the PDF itself

Check the Power Budget Verify your power budget requirements

This logo is placed next to I/O modules that are supported by the ZIPLink connection systems.

Calculating your power usage

Your I/O configuration choice can be affected by the power requirements of the I/O modules you choose. When determining the types and quantity of I/O modules you will be using, it is important to remember there is a limited amount of power available from the power supply.

See the I/O module specifications at the

The following example shows how to calculate the power budget for the DL405 system. The example is constructed around a single 8-slot base using the devices shown. It is recommended you construct a similar table for each base in your system.

The chart on the opposite page indicates the power supplied and used by each DL405 device. The adjacent chart shows an example of how to calculate the power used by your particular system. These two charts should make it easy for you to determine if the devices you have chosen fit within the power budget of your system configuration.

Aend of this section.Base Number 0Device TypeBD4-440 CPUC400

CURRENT REQUIRED SLOT 0 SLOT 1 SLOT 2 SLOT 3 SLOT 4 SLOT 5 SLOT 6 SLOT 7

+150+0D4-16ND2+150+0F4-04DA+120+100D4-08ND3S+100+0D4-08ND3S+100+0D4-16TD2+100+0D4-16TD2+100+0D4-16TR+1000+0D4-08B+80+0D4-HPP+320+0

E Maximum Current Required

2820

100

F Remaining Current Available

3700-2820=880400-100=300D

OTHER BASE Handheld Programmer

If your application requires a lot of relay outputs, consider using the ZipLink AC or DC relay output modules. These modules can switch high current (10A) loads without putting a load on your base power budget. Refer to Wiring System for DL405 PLCs later in this section for more information.

3700

D4-16ND2

Warning: It is extremely important to calculate the power budget correctly. If you exceed the power budget, the system may operate in an unpredictable manner which may result in a risk of personal injury or equipment damage.

Use ZIPLinks to reduce power requirements

External 24 VDC Power (mA)

CURRENT SUPPLIED CPU/Expansion Unit /Remote Slave

If the I/O you have chosen exceeds the maximum power available from the power supply, you can resolve the problem by shifting some of the modules to an expansion base or remote I/O base (if you are using remote I/O).

5 VDC (mA)

1. Using a chart similar to the 3one above, fill in column 2. 2. Using the tables on the opposite page, enter the current supplied and used by each device (columns 3 and 4). Pay special attention to the current supplied by the CPU, Expansion Unit, and Remote Slave since they differ. Devices which fall into the "Other" category (Row D) are devices such as the Base and the Handheld programmer, which also have power requirements, but do not plug directly into the base. 3. Add the current used by the system devices (columns 3 and 4) starting with Slot 0 and put the total in the row labeled "maximum current required" (Row E). 4. Subtract the row labeled "Maximum current required" (Row E), from the row labeled "Current Supplied" (Row B). Place the difference in the row labeled "Remaining Current Available" (Row F). 5. If "Maximum Current Required" is greater than "Current Supplied" in either column 3 or 4, the power budget will be exceeded. It will be unsafe to use this configuration and you will need to restructure your I/O configuration. Note the auxiliary 24 VDC power supply does not need to supply all the external power. If you need more than the 400mA supplied, you can add an external 24VDC power supply. This will help keep you within your power budget for external power.

DL405 CPU power supply specifications and power requirements Specification Part Numbers

AC Powered Units D4-450, D4-440, D4-430, D4-EX (expansion base unit), D4-RS (remote slave unit)

Voltage Withstand (dielectric) Insulation Resistance

24 VDC Powered Units D4-450DC-1, D4-440DC-1, D4-EXDC (expansion base unit), D4-RSDC (remote slave unit)

125 VDC Powered Units D4-450DC-2 D4-440DC-2

1 minute @ 1,500 VAC between primary, secondary, field ground, and run relay > at 500VDC

Input Voltage Range

85-132 VAC (110 range) 170-264 VAC (220 range

20-28 VDC (24 VDC) with less than 10% ripple

90-146 VDC (125 VDC) with less than 10% ripple

Maximum Inrush Current Maximum Power

20 A20 A20 A50 VA38 W30 WVolume 14e6-24

Programmable Controllers

1 - 80 0 - 633 - 0405

Page 4 of Koyo D4-450DC-1 Manual

The text of page 4, from the PDF itself

Power Requirements

Company Information Systems Overview Programmable Controllers

Power Supplied CPUs/Remote Units/ Expansion Units

5 VDC Current Supplied in mA

24V Aux Power Supplied in mA

CPUs/Remote Units/Expansion Units

5V Current Supplied in mA

24VAux. Power Supplied in mA

D4-430 CPU D4-440 CPU D4-440DC-1 CPU D4-440DC-2 CPU D4-450 CPU D4-450DC-1 CPU D4-450DC-2 CPU

3700 3700 3700 3700 3100 3100 3100

400 400 NONE NONE 400 NONE NONE

D4-EX D4-EXDC D4-EXDC-2 D4-RS D4-RSDC H4-EBC H4-EBC-F

4000 4000 3700 3700 3700 3470 3300

400 NONE NONE 400 NONE 400 400

Field I/O Software C-more & other HMI Drives

Power Consumed Power-consuming Device I/O Bases

5V Current Consumed

D4-04B-1 D4-06B-1 D4-08B-1

80 80 80

External 24VD Current Required

NONE NONE NONE

DC Input Modules

D4-08ND3S D4-16ND2 D4-16ND2F D4-32ND3-1 D4-32ND3-2 D4-64ND2

100 150 150 150 150 300 max.

NONE NONE NONE NONE NONE NONE

Power-consuming 5V Current Device Consumed Analog Modules (continued)

External 24VDC Current Required

F4-16AD-1 F4-16AD-2 F4-04DA-1 F4-04DA-2 F4-04DAS-1 F4-04DAS-2 F4-08DA-1 F4-08DA-2 F4-16DA-1 F4-16DA-2 F4-08RTD F4-08THM-n F4-08THM

100 100 75+20per circuit 90 60 per circuit 60 per circuit 100+20 per circuit 150 100+20 per circuit 25 max. NONE 50 60

75 75 70 90 60 60 90 80 90 80 80 120 110

Motors & Gearbox100 150NONE NONE

Photo Sensors Limit Switches

H4-ERM H4-ERM-F D4-RM320 450 300NONE NONE NONE

Pressure Sensors Temperature Sensors

NONE NONE

D4-08TD1 F4-08TD1S D4-16TD1 D4-16TD2 D4-32TD1 D4-32TD1-1 D4-32TD2

150 295 200 400 250 250 350

D4-64TD1

800

35 NONE 125 NONE 140 140 (15V) 120 (4A max including loads) NONE

DC Output Modules

Communications and Networking H4-ECOM100 H4-ECOM-F D4-DCM F4-MAS-MB FA-UNICON

300 670 500 235 NONEPushbuttons/ LightsNONE NONE NONE NONE 65

Process Relays/ Timers Comm.

CoProcessors F4-CP128-1

Terminal Blocks & Wiring

305NONEAC Output ModulesPower250 450NONE NONE

Relay Output Modules D4-08TR F4-08TRS-1 F4-08TRS D4-16TR

Proximity SensorsCurrent Sensors150 90D4-08TA D4-16TAMotor ControlsEncoders

AC/DC Input Modules D4-16NE3 F4-08NE3S

Steppers/ Servos

Remote I/O

AC Input Modules D4-08NA D4-16NA

Soft Starters550 575 575 1000NONE NONE NONE NONE

Specialty Modules H4-CTRIO D4-INT D4-HSC F4-16PID F4-8MPI D4-16SIM F4-4LTC

Circuit Protection

400 100 300 160 225 150 280

NONE NONE NONE NONE 170 NONE 75

Enclosures Tools Pneumatics Safety

Analog Modules

Programming D4-HPP-1 (Handheld Prog.)

F4-04AD F4-04ADS F4-08AD

85 270 75100 120 90320NONEDV-1000150NONEC-more Micro-Graphic210NONEAppendixOperator Interface

Product Index Part # Index Volume 14

w w w. a u to m at i o n d i re c t . c o m / d l 405

Programmable Controllers

e6-25