Spec sheet · Koyo
Koyo D4-450DC-1 Spec Sheet
Spec sheet4 pagesPDF 1.3 MB
All 4 pages are below, each with its text.
Covers · 1 model
The models it covers
From the sheet · read page by page
Key facts from this sheet
Each line names its page in the PDF.
Four catalog pages on the DL405 D4-450 CPU, which comes in three power supply versions: D4-450 (110/220 VAC), D4-450DC-1 (24 VDC) and D4-450DC-2 (125 VDC). They describe the communication ports, memory, instruction set, scan control and PID loop features. They help a reader check whether this CPU fits an existing DL405 system.
- What it is
- D4-450DC-1: the 24 VDC version of the DL405 D4-450 CPU, with the power supply built in p. 1
- Communication ports
- Four built-in ports: 15-pin port 0, a 6-pin phone jack, and a 25-pin connector holding ports 1 and 3 p. 1, 2
- Port 0 (15-pin)
- RS232C, 9600 baud, K-sequence; for the D4-HPP-1 handheld, DirectSOFT, DV-1000 or C-more panels p. 1, 2
- Ports 1 and 3 (25-pin)
- RS232C and RS422, up to 38.4K baud; K-sequence, DirectNET and Modbus master/slave, ASCII out; RS485 remote I/O master on port 3 only p. 2
- Memory
- 7.5K of flash on board; 15.5K with an optional memory cartridge p. 3
- PID loops
- Up to 16 loops in the CPU; automatic, manual or cascade control p. 1, 4
- Instructions
- Over 200, including four types of drum sequencers (16 steps, up to 16 outputs), trigonometric functions and IBox instructions p. 3
- Math
- IEEE format floating-point math p. 1
- Programming software
- Rel. 2.1 of DirectSOFT is required to program the D4-450 p. 3
- Keyswitch
- RUN, TERM and STOP positions p. 2
- Status indicators
- PWR, RUN, CPU, BATT, DIAG, I/O, TXD and RXD LEDs p. 2
- Scan control
- Variable, limited or fixed scan p. 3
- PID memory and ramp/soak
- 32 V-memory locations per loop (32 more with ramp/soak); up to 16 ramp/soak steps per loop p. 4
- Lower port adapter
- DN-25TB ZIPLink adapter gives screw terminals for the 25-pin port, RS-232/422 by DIP switch p. 2
What this sheet walks you through
- Choosing a power supply version of the D4-450 p. 1
- Matching each communication port to its protocols and devices p. 1, 2
- Choosing a variable, limited or fixed scan p. 3
- Setting up PID loops, alarms and tuning p. 4
Good to know
- Specialty modules with an F4 prefix (not analog modules) may need an upgrade to work with the D4-450. p. 1
- In RUN, the keyswitch locks the communication port so it will not receive incoming data. p. 2
- With all 16 loops in use, the smallest sample rate is limited to 0.2 seconds or scan time times number of loops. p. 4
- The built-in PID still needs analog input modules and output modules to complete each loop. p. 4
Questions this sheet answers
What power does the D4-450DC-1 use?
It is the 24 VDC version of the D4-450 CPU, with the supply built into the CPU. p. 1
How much memory does the D4-450 have?
7.5K of flash on board, or 15.5K with the optional memory cartridge. p. 3
How many PID loops can the D4-450 run?
Up to 16 PID loops directly in the CPU. p. 1
Which DirectSOFT version programs the D4-450?
Release 2.1 of DirectSOFT is required. p. 3
Which D4-450 port can be a remote I/O master?
Port 3 on the 25-pin connector, using RS485. p. 2
The file
Size and text
Every page · 4
Read it here
Each page as it is printed, and its words beside it, so a phone can search and copy them.
Page1of 4
Open in the PDF
The text of page 1, from the PDF itself
D4-450 Key Features 16 PID loops
DL450 CPU D4-450 <---> D4-450DC-1 <---> D4-450DC-2 <--->
The D4-450 CPU can process up to 16 PID loops directly in the CPU. You can select from various control modes including automatic control, manual control, and cascade control. There are a wide variety of alarms including Process Variable, Rate of Change, and Deviation. The various loop operation parameters are stored in V-memory, which allows easy access from operator interfaces. Setup is accomplished with our DirectSOFT Programming Software. An overview of the various loop specifications and features is on page 6-17.
Floating-point math The D4-450 CPU supports IEEE format floating-point math calculations. This feature means the D4-450 includes full trigonometric functions and various forms of integer/floating point number conversions.
Power supplies We offer a choice of three power supplies for the DL450 CPU. The power supplies are built into the CPU. Available power supplies are:
- 110/220 VAC version - D4-450
- 24 VDC version - D4-450DC-1
- 125 VDC version - D4-450DC-2
D4-450 CPU The D4-450 provides all the capabilities of the D4-430 and D4-440 CPUs, plus several additional features such as DirectSOFT5 IBox instructions.
D4–450 four built-in communication ports
Built-in CPU communications ports The D4-450 offers four built-in ports for extra convenience. The 15-pin port offers our proprietary K-sequence protocol and is primarily used for programming connections to a D4-HPP-1 handheld programmer or to a PC running DirectSOFT software. It can also be used to connect to a C-more panel or other operator interfaces. The 6-pin phone jack also supports K-sequence; plus, it can be a DirectNET slave port or an ASCII output port. The bottom 25-pin port contains two logical ports with different pins for each port. It is primarily a networking port that supports DirectNET master/slave or Modbus master/slave protocols. The bottom port can be used as an ASCII output port for connections to printers or other devices that can accept ASCII input. It can also be used as a remote I/O Master. The Communications Ports table on the next page has a complete description of each port.
Note: if you are considering a D4-450 CPU to replace a CPU in an existing system, and the system uses specialty modules with an F4 prefix, then these modules may require an upgrade to operate with the D4-450. Contact our Technical Services group prior to placing your order for more information. (This note does not apply to analog modules.)
6–12PLC Products1 - 80 0 - 633 - 0405
Page2of 4
Open in the PDF
The text of page 2, from the PDF itself
D4-450 Features
PLC Overview DL05/06 PLC
The diagrams on this page show the various hardware features found on the D4-450 CPU.
CPU Keyswitch RUN
Forces CPU to RUN mode. Locks Comm port - will not receive incoming data.
TERM
Allows peripherals (HPP, DCM, DirectSOFT, etc.) to select operating mode
STOP
Forces CPU out of RUN
CPU Status Indicators PWR
ON OFF
CPU power good CPU power failure
RUN
ON OFF
CPU is in RUN mode CPU is in STOP mode
CPU
ON OFF
CPU self-diagnostics error CPU self-diagnostics good
BATT
ON OFF
CPU battery is low CPU battery is good or disabled
DIAG
ON OFF
CPU diagnostics or local bus error CPU diagnostics or local bus good
I/O
ON OFF
I/O self-diagnostics error I/O self-diagnostics good
TXD
ON OFF
Data is being transmitted No data is being transmitted
RXD
ON OFF
Data is being transmitted No data is being transmitted
DL105 PLC DL205 PLC Wiring terminals CPU battery
DL405 PLCRun relayField I/O
24V auxiliary power (400ma)
Slot for optional memory cartridge
Logic ground
Programming Port, RS232C, baud rate selectable up to 38.4Kb. Connects to DirectSOFT DV-1000, C-more panels, network, etc. K-sequence protocol DirectNET protocol (slave only). ASCII out
Software C-more HMIs
Chassis ground AC power
Other HMI110/220 voltage selectAC Drives Motors
DN-25TB ZIPLink cables and communications adapter modules offer fast and convenient screw terminal connections for the D4-450 lower port. RS-232/422 DIP switch selectable. See the Connection Systems section in this desk reference for part numbers and descriptions.
Communications Ports Phone Jack Port 2
DL305 PLC
Steppers/ Servos Motor Controls Proximity Sensors Photo Sensors
D4-450 communications ports pin-out
Limit Switches15-pin connectorEncodersPhone jack15-pin Port 0
Programming port, RS232C, 9600 baud, connects to HPP, DirectSOFT, DV-1000, C-more panels, etc. Ksequence protocol (fixed station address=1)
Pushbuttons/ Lights Process
25-pin Ports 1 and 3
General purpose port for RS232C and RS422. (RS485 Remote I/O Master available on Port 3 only.) Baud rate selectable via software up to 38.4K baud. Connects to DirectSOFT, C-more panels, network, etc. Two logical ports (separate pins on connector). Software selectable protocol includes: Protocol Port 1 Port 3 K-sequence
- DirectNETMaster/Slave
- Modbus Master/Slave
- Modbus Master/Slave
- Remote I/O n/a
- ASCII Out
Relays/ TimersPort 2Comm.Port 0
TB’s & Wiring 25-pin connector
25-pin connector
Power Enclosures Appendix Part Index
Port 1
w w w. a u to m at i o n d i re c t . c o m / d l 405
Port 3PLC Products6–13
Page3of 4
Open in the PDF
The text of page 3, from the PDF itself
D4-450 Fixed or Variable Scan D4-450 Scan control The D4-450 CPU provides several scan control options, which are useful in some highspeed machine control applications. Variable, The scan varies as necessary from scan to scan. The actual scan time depends on the instructions being executed. Limited, This is similar to a variable scan in that the scan varies as necessary. However, if the actual scan time exceeds a specified target scan time, then a scan overrun condition is indicated. Fixed, If the scan is finished before the time specified, idle time is added to ensure a fixed scan period. If the scan exceeds the time specified, the scan is extended to ensure all instructions are executed. A scan overrun condition is also reported.
Memory
Rel. 2.1 of DirectSOFT, is required to program the D4-450.
The D4-450 has 7.5K of flash memory on board. Upgrade to 15.5K by choosing an optional memory cartridge. The memory cartridge is recommended since it is removable in the event of problems.
Full array of instructions Imagine if someone asked you to write a book, but then told you that you could only use 50 different words? That would be a tough job! The same is true for writing a PLC program. The right instruction can greatly simplify your control program. The D4-450 supports over 200 powerful instructions. These include:
- Four types of drum sequencers, each with 16 steps and up to 16 outputs
- Leading and trailing edge triggered oneshots
- Bit of word manipulation (bit set, reset, etc.)
- Trigonometric functions
- Floating point conversions
- Ibox instructions that simplify tasks such as configuring analog modules or performing complex math equations
Note: if you are considering a D4-450 CPU to replace a CPU in an existing system, and the system uses specialty modules with an F4 prefix, then these modules may require an upgrade to operate with the D4-450. Contact our Technical Services group prior to placing your order for more information. (This note does not apply to Analog modules.)
6–14PLC Products1 - 80 0 - 633 - 0405
Page4of 4
Open in the PDF
The text of page 4, from the PDF itself
D4-450 PID loops
PLC Overview DL05/06 PLC DL105 PLC
PID Loop Specifications and Key Features Number of Loops CPU V-memory Required PID Algorithm Auto Tuning
Selectable, 16 maximum
Open loop step response method and closed loop limit cycle method.
DL305 PLC
Sample Rate
Specify the time interval between PV samples, 0.05 to 99.99 in units of seconds or minutes. If using all 16 loops, the smallest sample rate is limited to either 0.2 seconds or (PLC scan time x number of loops).
DL405 PLC
Loop Operation Modes Ramp/Soak Square Root PV Limit SP Limit OUT Gain Reset Rate Rate Limiting
Loop can be in automatic control, manual (operator) control, or cascade control. PV alarm monitoring continues when loops are in manual mode.
Field I/O
Bumpless Transfer I
Bias and setpoint are initialized automatically when the loop is switched from manual to automatic. This provides for a bumpless transfer, which reduces the chance of sharp changes in the output as a result of entering automatic mode.
Bumpless Transfer II
Bias is set equal to the Output when the module is switched from manual to automatic. This allows switching in and out of automatic mode without having to re-enter the setpoint.
Steppers/ Servos
Step Bias
Provides proportional bias adjustment for large setpoint changes. This may stabilize the loop faster and reduce the chance of the output going out of range. Step bias should be used in conjunction with the normal adjusted bias operation.
Motor Controls
Anti-windup
If the position form of the PID equation is specified, the reset action is stopped when the PID output reaches 0 or 100%. Select adjusted bias or freeze bias operation.
Proximity Sensors
Error Deadband Error Squared
Specify an incremental value above and below the setpoint in which no change in output is made.
Photo Sensors
DL205 PLC
32 V-memory locations per loop selected (An additional 32 V-memory locations per loop required if using Ramp/Soak) Position or velocity form of the PID equation. Optionally specify direct or reverse acting, square root of the error and error squared control.
Up to 16 steps (8 ramp, 8 soak) per loop, with indication of Ramp/Soak step. Specify a square root of the PV for a flow control application.
Software
Specify a maximum and minimum value for allowable setpoint changes.
C-more HMIs
Specify a maximum and minimum value for the output range. Specify proportional gain of 0.01 to 99.99.
Other HMI
Specify integral time of 0.1 to 99.98 in units of seconds or minutes. AC Drives
Specify the derivative time, 0.00 to 99.99 seconds. Specify a derivative gain limiting coefficient to filter the PV used in calculating the derivative term (0 to 20).
Squaring the error minimizes the effect a small error has on the Loop output, however, both Error Squared and Error Deadband control may be enabled.
Limit Switches
Alarm Specifications Deadband
Specify 0.1% to 5% alarm deadband on all alarms except Rate of Change.
PV Alarm Points
Specify PV alarm settings for low-low, low, high, and high-high conditions. You can also specify a deadband to minimize the alarm cycles when the PV approaches alarm limits.
Process
If you're only interested in controlling temperature, then there may be a better solution than the D4-450 CPU. Check out the F4-4LTC module. This module has the capabilities of our single loop controllers built into one economical module! Detailed specifications can be found later in this section. This module can directly control up to four loops and it even includes built-in relay outputs for heater or chiller control! If you use the built-in PID capability of the D4-450 CPU, you still have to purchase the analog input modules and the output modules (either discrete or analog) in order to complete the loop. This can result in a much higher overall cost when compared to the F4-4LTC.
D4–450 CPU
Encoders Pushbuttons/ Lights
Specify alarms to indicate two ranges of PV deviation from the setpoint value (yellow and red deviation). PV Deviation Specify a rate-of-change limit for the PV. Rate of Change Need Temperature Control?
Operator Interface
Motors
Relays/ Timers Comm. TB’s & Wiring
DL405 Analog Output or Discrete Output
Power Enclosures Appendix
PID Loop Control Block Diagram
Part Index
DL405 Analog Input Modules
w w w. a u to m at i o n d i re c t . c o m / d l 405
PLC Products
6–15