Page 1 of Koyo D4-RM and PLC Direct D4-RM Spec Sheet

Spec sheet · Koyo

Koyo D4-RM and PLC Direct D4-RM Spec Sheet

Spec sheet2 pagesPDF 525 KB

Both pages are below, each with its text.

Download the PDF525 KB

Covers · 2 models

The models it covers

From the sheet · read page by page

Key facts from this sheet

Each line names its page in the PDF.

A two-page catalog spec sheet for DL405 serial remote I/O: the D4-RM remote I/O master module and the D4-RS and D4-RSDC remote slave units. It explains how a master in the CPU base links remote DL405 bases and gives the capacity per CPU and the specifications of master and slave.

Module type
Remote I/O master for the DL405 CPU base; controls up to seven remote slaves p. 1
Communication
RS485 via shielded twisted pair at 38.4K baud p. 2
Cable
Belden 9841 or equivalent p. 2
Distance
3,300 ft. (1000m) maximum, daisy-chained p. 1
Masters per CPU
Two for D4-430 and D4-440, three for D4-450, counting Slice Master modules p. 2
Operating environment
0°C to 60°C (32°F to 140°F), 5% to 95% humidity, non-condensing p. 2
Slave points per CPU
512 for D4-430, 1024 for D4-440, 1536 for D4-450 p. 2
Internal power
300 mA maximum p. 2
Remote slaves
D4-RS (110 VAC/220 VAC) and D4-RSDC (24VDC) p. 2
Built into D4-450
The D4-450 CPU has D4-RM function on its 25-pin port p. 1
Manufacturer
Koyo Electronics p. 2

What this sheet walks you through

  • How DL405 remote I/O links remote bases to the CPU p. 1
  • Remote I/O capacity of the D4-430, D4-440 and D4-450 CPUs p. 1
  • Assigning I/O addresses to remote points p. 2

Good to know

  • Master to CPU communication is asynchronous to the CPU scan, so remote points should not need updating every scan. p. 1
  • On the D4-450, at most 2 D4-RM modules; one channel is the CPU 25-pin port. p. 1

Questions this sheet answers

How many remote slaves can a D4-RM control?

Up to seven remote slaves per channel, each attached to a DL405 base of any size. p. 1

How long can the D4-RM remote I/O cable be?

Up to 3300 feet (1000m) of twisted pair, run daisy-chain from slave to slave. p. 1

What cable does the D4-RM use?

Belden 9841 or equivalent, shielded twisted pair carrying RS485 at 38.4K baud. p. 2

How many D4-RM modules can a DL405 CPU take?

Two for the D4-430 and D4-440, three for the D4-450; the count includes Slice Master modules. p. 2

The file

Size and text

Pages2
PDF525 KB
TextText from the PDF itself.

Every page · 2

Read it here

Each page as it is printed, and its words beside it, so a phone can search and copy them.

Page 1 of Koyo D4-RM and PLC Direct D4-RM Spec Sheet

The text of page 1, from the PDF itself

DL405 Remote I/O

SERIAL REMOTE I/O MASTER/SLAVE MODULES Remote master

Remote I/O Master Module D4-RM

Remote I/O Slave Module

3300ft (1000m) Max.

Remote slaves

Maximum of seven remote bases per channel

1 - 80 0 - 633 - 0405D4-RS D4-RSDCRemote slaveRemote master

Overview The DL405 offers full-size remote I/O. The goal of remote I/O is to reduce wiring costs, by allowing I/O points to be located near the devices they are controlling. The chart at the bottom of this page shows the capacity for each CPU. The D4-450 has the D4-RM functionality built into the 25-pin port directly on the CPU. However, you can also choose to use the D4-RM discussed here. Here’s how it works: A special module called the Remote Master is placed in the CPU base. This Master module controls up to seven Remote Slaves. The Remote Slaves are connected to the Master in a daisy-chain manner over a twisted pair communication cable (maximum length of 3300 feet or 1000m). Each Remote Slave attaches to a DL405 base (any size). Standard DL405

562

PLC and PC Products

Maximum number of remote masters supported Maximum I/O points supported Maximum I/O points supported per channel Maximum number of remote I/O bases per channel

D4-450D4-440D4-4303*2215361024512512512512777

*max. of 2 D4-RM, 1 channel is via 25-pin CPU port

modules populate the remote bases. You can assign normal input and output addresses to the remote points, or you can assign special remote I/O addresses. The Remote Master sends the remote I/O information to the CPU. The communication between the Remote Master and

the CPU is asynchronous to the CPU scan. For this reason, remote I/O applications should be limited to those that do not require the remote I/O points to be updated with every CPU scan.

Page 2 of Koyo D4-RM and PLC Direct D4-RM Spec Sheet

The text of page 2, from the PDF itself

DL405 Remote I/O PLC/PC

SERIAL REMOTE I/O Remote Slave

Remote Master

RE MOTE I/O MAS TE R P WR R UN

D4--R S 110/220VAC R E MOTE I/O

PAR LINKDIAG I/O MS TR D4--R MUNIT ADRSPWRI/ORUNPARDIAGLINK

Run relay 24V auxiliary Power

T 1Logic ground2Chassis groundT

Remote Channel Connector

1AC powerG2110/220 voltage select30VDC 1A CLAS S 23 GD4--RM

Remote Slave Specifications

Remote Master Specifications Module Type

Intelligent device

Number of Master per CPU

Two maximum for D4-430 and D4-440 Three maximum for D4-450 (max. number must include both Remote Master modules and Slice Master modules)

Maximum Slaves Supported

Seven slaves per channel

Communication to Slaves Recommended Cable Transmission Distance Terminal Type

RS485 via twisted pair with shield @ 38.4K baud

Operating Environment

0°C to 60°C (32°F to 140°F), 5% to 95% humidity (non-condensing)

Internal Power Consumption Manufacturer

for D4-430 Maximum Slave Points per 512 1024 for D4-440 CPU 1536 for D4-450

I/O Addresses Used

I/O modules in slave bases do not automatically consume any standard input and output points. They consume remote I/O points at a rate equal to the number of I/O points in each base. However, you can choose to use standard I/O addresses as an option

Terminal Type Operating Environment

Fixed

Power required

110 VAC/220 VAC (D4-RS) 24VDC (D4-RSDC)

Manufacturer

Koyo Electronics

0°C to 60°C (32°F to 140°F), 5% to 95% humidity (non-condensing)

w w w. a u to m at i o n d i re c t . c o m / d l 405

3

UNIT ADRS

Belden 9841 or equivalent 3,300 ft. maximum Fixed

300 mA maximum Koyo Electronics

PLC and PC Products

563