Key facts from this sheet
Each line names its page in the PDF.
Product brochure (edition 02.13) for the Kromschroder DG range of gas pressure switches, including the DG..T version. It covers applications, the type code that decodes a model name, and the technical data. The name DG50T itself does not appear; the DG..T entries apply to the T version.
- What it is
- Gas pressure switch for positive, negative and differential gas and air pressures, switching point set by hand wheel p. 1, 2
- DG..T version
- DG..T: hand wheel with "WC and mbar scale, NPT conduit for the electrical connection p. 2
- DG..T switching capacity
- DG..T: 30 – 240 V AC, 5 A at cos ϕ = 1, 0.5 A at cos ϕ = 0.6 p. 4
- DG..TG switching capacity
- DG..TG: < 30 V AC, 0.1 A at cos ϕ = 1, 0.05 A at cos ϕ = 0.6 p. 4
- Max inlet pressure
- ± 600 mbar (8.5 psig) p. 4
- Max test pressure
- 2 bar (29 psig), for less than 15 minutes p. 4
- Gas types
- Natural gas, town gas, LPG (gaseous), flue gas, biologically produced methane (max. 0.1 %-by-vol. H2S) and air p. 4
- Medium and ambient temperature
- DG..B, DG..U, DG..I, DG..S: -15 to +80°C (5 to 176°F); DG..H, DG..N: -15 to +60°C (5 to 140°F) p. 4
- Storage temperature
- -40 to +80°C (-40 to 176°F) p. 4
- Materials
- Silicone-free diaphragm (NBR, or IIR for DG..S); glass fibre reinforced PBT housing; AlSi 12 lower housing p. 4
- Enclosure
- IP 54 or IP 65 p. 4
- Type code
- Number = maximum setting in mbar (1.5 – 500); T = T-product, G = gold-plated contacts, -3 to -9 = electrical connection p. 3
- Approvals
- The brochure states DG..T is FM approved and UL listed p. 1
What this sheet walks you through
- Reading the DG type code p. 3
- Gas deficiency and minimum inlet pressure monitoring p. 2
- Monitoring air filters by differential pressure p. 2
- Low-pressure cut-off and high gas pressure protection p. 3
- Monitoring fan air flow in an air line p. 3
Good to know
- The brochure calls for maintenance at least once a year, twice a year with biologically produced methane. p. 4
- The 2 bar test pressure for testing the whole system is allowed for less than 15 minutes only. p. 4
- DG..H and DG..N lock off when they switch and need a manual reset. p. 2
Questions this sheet answers
What is the maximum inlet pressure of a Kromschroder DG pressure switch?
± 600 mbar (8.5 psig). p. 4
What load can a DG..T pressure switch switch?
30 to 240 V AC, 5 A at cos ϕ = 1 or 0.5 A at cos ϕ = 0.6. p. 4
What does the number in a DG model name mean?
In the type code, the number after DG is the maximum setting in mbar, from 1.5 to 500. p. 3
Which gases can the DG pressure switch be used with?
Natural gas, town gas, gaseous LPG, flue gas, biologically produced methane (max. 0.1 % H2S by volume) and air. p. 4
The file
Size and text
Every page · 4
Read it here
Each page as it is printed, and its words beside it, so a phone can search and copy them.
Page1of 4
Open in the PDF
The text of page 1, from the PDF itself
Pressure switch for gas DG Product brochure · GB 4 Edition 02.13
AGA
- Monitoring of gas and air pressures (positive, negative and differential pressures)
- EC type-tested and certified pursuant to EN 1854 and class “S”
- DG..T: FM approved and UL listed
- Certified pursuant to GOST-R and AGA
- Certified for systems up to SIL 3 and PL e
- Pressure switch with internal lock and manual reset
- Suitable for biologically produced methane (can be used on pipes with Zone 2 explosive atmospheres without isolating amplifier)
- With approved isolating amplifier for Zone 1 and 2 hazardous areas
- RoHS 2002/95/EC
- DG..S: special version available for NH3 and O2
Page2of 4
Open in the PDF
The text of page 2, from the PDF itself
2 · DG · Edition 02.13ApplicationDG..H, DG..N
DG..U-3 Adjustable switching point
DG..-6
DG..H: switches and locks off with rising pressure. DG..N: switches and locks off with falling pressure. Manual reset.
The gas pressure switch DG monitors extremely low pressure differentials and triggers switch-on, switch-off or switch-over operations if a set switching point is reached. The switching point is adjustable via a hand wheel.
With fitted socket pursuant to DIN EN 175301-803
DG..T Hand wheel with "WC and mbar scale. NPT conduit for electrical connection.
Examples of application Gas deficiency monitoring
It monitors positive and negative gas pressures on various industrial gas and air appliances, such as boiler fan monitoring and differential pressure monitoring in firing, ventilation and air-conditioning systems. The TÜV-tested special-design pressure switch is used as defined by VdTÜV Code of Practice “Druck 100/1” (Pressure 100/1) in firing installations for steam and hot-water generators in accordance with TRD 604, Para. 3.6.4, as well as class “S” for DG..B, DG..U and DG..I pursuant to EN 1854. Positive pressure Gas, air, flue gas DG..B or biomethane Gas, air, flue gas DG..U, DG..T or biomethane DG..H, DG..N, Gas, air, flue gas DG..HT, DG..NT or biomethane Type
DG..IAir or flue gasDG..SNH3 or O2Negative pressureDifferential pressure––Air or flue gas
Air or flue gas Air or flue gas Air or flue gas –
Air or flue gas Gas, air, flue gas or biomethane –
For monitoring the minimum gas inlet pressure Differential pressure monitoring
Differential pressure switch for monitoring air filters
Page3of 4
Open in the PDF
The text of page 3, from the PDF itself
DG · Edition 02.13 · 3 Systems leak tightness check
Low-pressure cut-off and high gas pressure protection device
AKTGFKKFMGDJKFMDG
If the pressure is either too low or too high, the min./max. pressure switch DG switches in order to avoid start-up or to initiate a safety shut-down. Electronic safety shut-off valve SAV with closed position check of downstream devices. Negative pressure monitoring
Monitoring the negative pressure ensures the correct positioning of the components during fully automatic assembly of gas meters. Air line with minimum pressure and flow monitoring
DG (1)KFM/RFMDG (2)
1/min The air flow generated by the fan may be monitored as follows: The static pressure is monitored by pressure switch DG (1), as long as it can be demonstrated that the display consequently shows an adequate and secured flow of air, or DG (2) controls the flow of air via the differential pressure on the orifice. If there is no air pressure supplied or if there is no differential pressure on the orifice, the system will be blocked.
Type code Code Description DG Pressure switch for gas 1,5 – 500 Maximum setting in mbar B Positive pressure U Positive pressure, negative pressure, differential pressure H Locks off with rising pressure N Locks off with falling pressure I Negative pressure for gas S Positive pressure only, for oxygen and ammonia T T-product G With gold-plated contacts Electrical connection: -3 via screw terminals -4 via screw terminals, IP 65 -5 via 4-pin plug, without socket -6 via 4-pin plug, with socket -9 via 4-pin plug, with socket, IP 65 K2 Red/green pilot LED for 24 V DC/AC T Blue pilot lamp for 230 V AC T2 Red/green pilot LED for 230 V AC N Blue pilot lamp for 120 V AC A External adjustment
VAS..N
Page4of 4
Open in the PDF
The text of page 4, from the PDF itself
4 · DG · Edition 02.13Technical dataMaintenance cycles
Gas type: natural gas, town gas, LPG (gaseous), flue gas, biologically produced methane (max. 0.1 %-by-vol. H2S) and air.
At least once a year, twice a year in the case of biologically produced methane.
DG: max. inlet pressure pu max. ± 600 mbar (8.5 psig). Max. test pressure for testing the entire system: temporarily < 15 minutes 2 bar (29 psig). Switching capacity: DG: U = 24 – 250 V AC, I = 0.05 – 5 A at cos ϕ =1, I = 0.05 – 1 A at cos ϕ = 0.6. DG..G: U = 5 – 250 V AC, I = 0.01 – 5 A at cos ϕ = 1, I = 0.01 – 1 A at cos ϕ = 0.6. DG..G U = 5 – 48 V DC, I = 0.01 – 1 A. DG..T: U = 30 – 240 V AC, I = 5 A at cos ϕ = 1, I = 0.5 A at cos ϕ = 0.6. DG..TG: U = < 30 V AC, I = 0.1 A at cos ϕ = 1, I = 0.05 A at cos ϕ = 0.6. Maximum medium and ambient temperatures: DG..B, DG..U, DG..I, DG..S: -15 to +80°C (5 to 176°F), DG..H, DG..N: -15 to +60°C (5 to 140°F). Storage and transport temperature: -40 to +80°C (-40 to 176°F). RoHS compliant pursuant to 2002/95/EC. Diaphragm pressure switch, silicone-free. Diaphragm: NBR for DG..U, B, N, H, I, IIR for DG..S. Housing: glass fibre reinforced PBT plastic with low gas release. Lower housing section: AlSi 12. Enclosure: IP 54 or IP 65. Safety class: 1.
Contact www.kromschroeder.com ➔ Sales Elster GmbH Postfach 2809 · 49018 Osnabrück Strotheweg 1 · 49504 Lotte (Büren) Germany T +49 541 1214-0 F +49 541 1214-370 info@kromschroeder.com www.kromschroeder.com
http://docuthek.kromschroeder.com/doclib/main.php?language=1&folderid=204020&by_class=6
We reserve the right to make technical modifications in the interests of progress. Copyright © 2013 Elster GmbH All rights reserved.
03250746