Page 21

13.0

PROGRAMMING THE SCN DRIVE

The drive may be programmed by one of two methods: using the three buttons and 2-digit LED display on the front of the drive, or programming the Electronic Programming Module (EPM) using the optional EPM Programmer. This section describes programming the drive using the buttons and display, which are shown below:

BUTTONS

DISPLAY

Mode

To enter the PROGRAM mode to access the parameters, press the Mode button. This will activate the PASSWORD prompt (if the password has not been disabled). The display will read “00” and the upper right-hand decimal point will be blinking, as shown below:

Press Mode Display reads "00" Right decimal point blinks

Use the " and ! buttons to scroll to the password value (the factory default password is “25”) and press the Mode button. Once the correct password value is entered, the display will read "01", which indicates that the PROGRAM mode has been accessed at the beginning of the parameter menu (01 is the first parameter), and the upper right decimal point will turn on solid. This is shown below:

Use " and ! to scroll to the password value

Press Mode to enter password

Parameter menu is accessed at the first parameter

Upper right decimal point turns on solid. 18

Page 22

NOTE: If the display flashes “Er”, the password was incorrect, and the process to enter the password must be repeated. Use the " and ! buttons to scroll to the desired parameter number. In the example below, Parameter 19 is being displayed, which is the ACCELERATION TIME of the drive:

Use " and ! to scroll to the desired parameter number

Once the desired parameter number is found, press the Mode button to display the present parameter setting. The upper right-hand decimal point will begin blinking, indicating that the present parameter setting is being displayed, and that it can be changed by using the " and ! buttons.

Press Mode to display present parameter setting (present example setting is 15)

Right decimal point blinks

Use " and ! to change setting (example setting changed to 30)

Press Mode to store new setting

Pressing the Mode will store the new setting and also exit the PROGRAM mode. To change another parameter, press the Mode key again to re-enter the PROGRAM mode (the parameter menu will be accessed at the parameter that was last viewed or changed before exiting). If the Mode key is pressed within two minutes of exiting the PROGRAM mode, the password is not required access the parameters. After two minutes, the password must be entered in order to access the parameters again.

19

Page 23

13.2

ELECTRONIC PROGRAMMING MODULE (EPM)

Every SCN Series drive has an Electronic Programming Module (EPM) installed on the main control board. The EPM stores the user’s parameter settings and special OEM default settings (if programmed). The EPM is removable, allowing it to be installed in another drive for quick set-up. For example, if a drive is being replaced with a new one, the EPM can be taken out of the first drive and installed in the new drive. Downtime is minimized because the new drive does not require programming - it is ready to run when the EPM is installed. The SCN Series drive contains two or three sets of parameter values, depending on whether the drive has been programmed with optional OEM default settings. The first set of values is the factory default settings, which are permanently stored on the main control board and cannot be changed. The second set of values is the user settings, which are stored in the EPM. When the drive leaves the factory, the user settings are the same as the factory default settings, but the user settings can be changed to configure the drive for a particular application. The optional third set of values is the OEM default settings, which are also stored in the EPM. OEM default settings are typically used in cases where many drives are used for the same application, which requires that all of the drives have the same parameter settings. The OEM default settings cannot be changed without the optional EPM Programmer. The drive can be programmed to operate according to the user settings or the OEM default settings (see Parameter 48 in Section 15.0). NOTE: The drive will not operate without the EPM installed. The drive will display “F1” if the EPM is missing or damaged. WARNING! Do not remove the EPM while power is applied to the drive. Damage to the EPM and/or drive may result. An EPM Programmer is available as an option from AC Tech, which has the ability to quickly and easily program many SC Series drives for the same configuration. Once a “master” EPM is programmed with the desired parameter settings, the EPM Programmer can copy those settings to other EPMs, allowing many drives to be configured very quickly. Please consult the EPM Programmer Instruction Manual or contact the factory for more information. If the OEM settings in the EPM become corrupted, the drive will operate normally, until an attempt is made to perform a RESET OEM using Parameter 48 - PROGRAM SELECTION. The drive will then flash “GF” to indicate that the OEM settings are no longer valid. This will require that the EPM be re-programmed using the optional EPM Programmer. If the OEM settings and the user settings are both corrupted, the drive will display “GF” immediately and the drive will require a RESET 60 or RESET 50 using Parameter 48 - PROGRAM SELECTION. Once the RESET is performed, the parameters can then be programmed individually to match the OEM default settings. This will allow the drive to operate as if it were in OEM mode, even though it is actually operating in USER mode. Refer to Parameter 48 in Section 15.0 - DESCRIPTION OF PARAMETERS. NOTE: The drive will also display “GF” if a RESET OEM or OPERATE WITH OEM SETTINGS is attempted when the drive is not equipped with the OEM default option.

20

Page 24

14.0

PARAMETER MENU

NO.

PARAMETER NAME

RANGE OF ADJUSTMENT

01 02 03

LINE VOLTAGE CARRIER FREQUENCY START METHOD

04

STOP METHOD

05

STANDARD SPEED SOURCE TB-14 OUTPUT

HIGH (01), LOW (02) 4kHz (01), 6 kHz (02), 8 kHz (03), 10 kHz (04) NORMAL (01), START ON POWER UP (02), START WITH DC BRAKE (03), AUTO RESTART WITH DC BRAKE (04), FLYING RESTART 1 (05), FLYING RESTART 2 (06), FLYING RESTART 3 (07) COAST (01), COAST WITH DC BRAKE (02), RAMP (03), RAMP WITH DC BRAKE (04) KEYPAD (01), PRESET #1 (02), SPEED POT (03) NONE (01), RUN (02), FAULT (03), INVERSE FAULT (04), FAULT LOCKOUT (05), AT SET SPEED (06), ABOVE PRESET #3 (07), CURRENT LIMIT (08), AUTO SPEED (09), REVERSE (10), DB BRAKE (11) NONE (01), SPEED POT (02), PRESET SPEED #1 (03), START FORWARD (04), RUN REVERSE (05), START REVERSE (06), EXTERNAL FAULT (07), DB FAULT (08), AUXILIARY STOP (09), ACCEL/DECEL #2 (10) NONE (01), SPEED POT (02), PRESET SPEED #2 (03), DECREASE FREQ (04), JOG FORWARD (05), JOG REVERSE (06), EXTERNAL FAULT (07), DB FAULT (08), AUXILIARY STOP (09), ACCEL/DECEL #2 (10) NONE (01), SPEED POT (02), PRESET SPEED #3 (03), INCREASE FREQ (04), START FORWARD (05), EXTERNAL FAULT (06), DB FAULT (07), AUXILIARY STOP (08), ACCEL/DECEL #2 (09)

FACTORY DEFAULT (NOTE 1)

06

10

TB-13A FUNCTION SELECT

11

TB-13B FUNCTION SELECT

12

TB-13C FUNCTION SELECT

NOTE 1:

HIGH (01) 6 kHz (02) NORMAL (01)

COAST (01) KEYPAD (01) NONE (01)

NONE (01)

NONE (01)

NONE (01)

Factory defaults are shown for a 60 Hz base frequency. See Parameter 48 for 50 Hz base frequency.

21

Page 25

NO.

PARAMETER NAME

RANGE OF ADUSTMENT

14

CONTROL

17

ROTATION

TERMINAL STRIP ONLY (01), REMOTE KEYPAD ONLY (02) FORWARD ONLY (01), FORWARD AND REVERSE (02) x0.1 (01), x1.0 (02), x10.0 (03) 0.1 - 990 SEC 0.1 - 990 SEC 0.0 - 990 SEC 0 - 30 % 0 - MAXIMUM FREQUENCY MINIMUM FREQUENCY - 99 Hz 30 - 180 % (NOTE 2) 30 - 100 % 25 - 99 Hz 0 - 30 % 0 - 20 % 0.0 - 5.0 % 0 - MAXIMUM FREQUENCY 0 - 10 Hz 0.1 - 990 SEC 00 - 99 MAINTAIN (01), CLEAR (02) USER SETTINGS (01), OEM SETTINGS (02), RESET OEM (03), RESET 60 (04), RESET 50 (05), TRANSLATE (06) (VIEW-ONLY) (VIEW-ONLY) (VIEW-ONLY) (VIEW-ONLY) (VIEW-ONLY) (VIEW-ONLY) (VIEW-ONLY) (VIEW-ONLY)

FACTORY DEFAULT (NOTE 1)

18 TIME RANGE SELECT 19 ACCELERATION TIME 20 DECELERATION TIME 21 DC BRAKE TIME 22 DC BRAKE VOLTAGE 23 MINIMUM FREQUENCY 24 MAXIMUM FREQUENCY 25 CURRENT LIMIT 26 MOTOR OVERLOAD 27 BASE FREQUENCY 28 FIXED BOOST 29 ACCEL BOOST 30 SLIP COMPENSATION 31-37 PRESET SPEEDS 38 SKIP BANDWIDTH 42 ACCEL / DECEL #2 44 PASSWORD 47 CLEAR HISTORY 48 PROGRAM SELECTION 50 51 52 53 54 55 57 58 NOTE 1: NOTE 2:

FAULT HISTORY SOFTWARE CODE DC BUS VOLTAGE MOTOR VOLTAGE LOAD SPEED POT INPUT TB STRIP STATUS KEYPAD STATUS

TERMINAL STRIP ONLY (01) FORWARD ONLY (01) x1.0 (02) 20 SEC 20 SEC 0 SEC 0% 0 Hz 60 Hz 180 % 100 % 60 Hz 1% 0% 0% 0 Hz 0 Hz 20 SEC 25 MAINTAIN (01) USER SETTINGS (01) (N/A) (N/A) (N/A) (N/A) (N/A) (N/A) (N/A) (N/A)

Factory defaults are shown for a 60 Hz base frequency. See Parameter 48 for 50 Hz base frequency. If LINE VOLTAGE is set to LOW, maximum setting is 150%. 22

Page 26

15.0

DESCRIPTION OF PARAMETERS

01

LINE VOLTAGE SELECTION

This calibrates the drive for the actual applied input voltage, and can be set to HIGH (01) or LOW (02). Refer to the table below for the proper setting depending on the input voltage.

MODEL SN100S

RATED INPUT VOLTAGE 120 / 208 / 240 Vac

INPUT PHASE 1

APPLIED INPUT VOLTAGE 110 - 120 Vac or 220 - 240 Vac

PARAMETER SETTING HIGH (01)

1

200 - 208 Vac

LOW (02)

SN200S

208 / 240 Vac

1 or 3

220 - 240 Vac

HIGH (01)

1 or 3

200 - 208 Vac

LOW (02)

SN200

208 / 240 Vac

3

220 - 240 Vac

HIGH (01)

3

200 - 208 Vac

LOW (02)

NOTE: If this parameter is changed while the drive is running, the new value will not take effect until the drive is stopped. 02

CARRIER FREQUENCY

This sets the switching rate of the output IGBT’s. Increasing the carrier frequency will result in less audible motor noise. Available settings are: 4 kHz, 6 kHz, 8 kHz, and 10 kHz.

PARAMETER SETTING 01 02 03 04

CARRIER FREQUENCY 4 kHz 6 kHz 8 kHz 10 kHz

MAXIMUM OUTPUT FREQUENCY 99 Hz 99 Hz 99 Hz 99 Hz

AMBIENT OR OUTPUT DERATE (NOTE 2) 50 C or 100% 50 C or 100% 43 C or 92% 35 C or 82%

NOTE 1: The SCN drive is fully rated up to 6 kHz carrier frequency. If the 8 kHz or 10 kHz carrier frequency is selected, the drive’s ambient temperature rating OR output current rating must be derated to the value shown in the table above. NOTE 2: If this parameter is changed while the drive is running, the change will not take effect until the drive is stopped.

23

Page 27

03

START METHOD

WARNING! Automatic starting of equipment may cause damage to equipment and/or injury to personnel! Automatic start should only be used on equipment that is inaccessible to personnel. 01

NORMAL: The drive will start when the appropriate contact is closed on the terminal strip. See Section 11 for possible control configurations.

02

START ON POWER UP: The drive will automatically start upon application of input power.

03

START WITH DC BRAKE: When a START command is given, the drive will apply DC BRAKE VOLTAGE (Parameter 22) for the duration of DC BRAKE TIME (Parameter 21) prior to starting the motor to ensure that the motor is not turning.

04

AUTO RESTART WITH DC BRAKING: Upon a START command, after a fault, or upon application of power, the drive will apply DC BRAKE VOLTAGE (Parameter 22) for the duration of DC BRAKE TIME (Parameter 21) prior to starting (or restarting) the motor.

05

FLYING RESTART 1: LOW performance. Slowest synchronization and lowest current level. This setting results in the smoothest synchronization.

06

FLYING RESTART 2: MEDIUM performance. Faster synchronization and higher current level. This setting allows faster synchronization while retaining smoothness.

07

FLYING RESTART 3: HIGH performance. Fastest synchronization and highest current level. This setting allows the fastest synchronization, but sacrifices smoothness.

When programmed for auto-restart (settings 04 - 07), the drive will attempt three restarts after a fault. The interval between restart attempts is 15 seconds for setting 04, and 2 seconds for settings 05, 06 and 07. During the interval between restart attempts, the display will read “SP” to indicate Start Pending. If all three restart attempts fail, the drive will trip into FAULT LOCKOUT (displayed “LC”) and require a manual reset. Refer to Section 16.0 - TROUBLESHOOTING. The FLYING RESTART 1 - 3 settings allow the drive to start into a spinning load after a fault or upon application of input power. They differ in the time required to find the motor and the amount of current required to synchronize with it. The faster the drive attempts to find the motor, the more current is required. The first two restart attempts will try to start into the spinning load, but the third restart attempt will act like AUTO RESTART WITH DC BRAKING. NOTE: Settings 02 and 04 - 07 require a two-wire start/stop circuit to operate. The RUN contact must remain closed for the power-up start and auto-restart functions to operate.

24

Page 28

04

STOP METHOD

01

COAST TO STOP: When a STOP command is given, the drive shuts off the output to the motor, allowing it to coast freely to a stop.

02

COAST WITH DC BRAKE: When a stop command is given, the drive will activate DC braking (after a delay of up to 2 seconds, depending on frequency) to help decelerate the load. Refer to Parameters: 21 - DC BRAKE TIME, and 22 - DC BRAKE VOLTAGE.

03

RAMP TO STOP: When a stop command is given, the drive will decelerate the motor to a stop at the rate determined by Parameter 20 - DECELERATION TIME.

04

RAMP WITH DC BRAKE: When a stop command is given, the drive will decelerate the motor down to 0.2 Hz (at the rate set by Parameter 20 - DECELERATION TIME) and then activate DC braking according to the settings of Parameters 21 - DC BRAKE TIME and 22 - DC BRAKE VOLTAGE. This is used to bring the load to a final stop, as the motor may still be turning slightly after the drive stops.

05

STANDARD SPEED SOURCE

This selects the speed reference source when the drive is in STANDARD speed mode. The following speed references can be selected: 01

KEYPAD: Use the ! and " buttons to scroll to the desired speed.

02

PRESET SPEED #1: The drive will operate at the frequency set into Parameter 31.

03

SPEED POT: The drive will respond to a speed pot. Refer to Section 11.0 for speed pot wiring.

06

TB-14 OPEN COLLECTOR OUTPUT

This selects the status indication for the open-collector output at TB-14. The terms “open” and “close” refer to the state of the internal transistor that activates the circuit. When the transistor is “closed”, TB-14 is at the same potential as TB-11, allowing current to flow. 01

NONE: Disables the open-collector output.

02

RUN: Closes upon a START command. Opens if the drive is in a STOP state, the drive faults, or input power is removed. DC braking is considered a STOP state.

03

FAULT: Closes if there is no fault condition. Opens if the drive faults, or input power is removed.

04

INVERSE FAULT: Closes if the drive faults. Opens if there is no fault condition.

05

FAULT LOCKOUT: Closes when input power is applied. Opens if three restart attempts are unsuccessful, or if input power is removed.

25

Page 29

06

AT SET SPEED: Closes if the drive is within + 0.5 Hz of the speed setpoint.

07

ABOVE PRESET SPEED #3: Closes if the output frequency exceeds PRESET SPEED #3 (Parameter 33). Opens if the output frequency is equal to or less than PRESET SPEED #3.

08

CURRENT LIMIT: Closes if the output current exceeds the CURRENT LIMIT setting. Opens if the output current is equal to or less than CURRENT LIMIT (see Parameter 25).

09

AUTOMATIC SPEED MODE: Closes if an AUTOMATIC (terminal strip) speed reference is active. Opens if a STANDARD (Parameter 5) speed reference is active.

10

REVERSE: Closes when reverse rotation is active. Opens when forward rotation is active (see Parameter 17 - ROTATION DIRECTION).

11

DB BRAKE: TB-14 becomes the "trigger" that activates the optional external Dynamic Braking module. Refer to the instructions included with the Dynamic Braking option.

NOTE: If the optional remote keypad is used, TB-14 is wired to the remote keypad and cannot be used for any of the above listed functions. In this case, this parameter should be set to NONE (01). 10

TB-13A FUNCTION SELECT

This selects the function of terminal TB-13A. Closing TB-13A to TB-11 (or opening in the case of settings 07 and 09) activates the selected function. The following functions can be selected: 01

NONE: Disables the TB-13A function.

02

SPEED POT: Selects a speed pot as the speed reference input. Refer to Section 11.0 for speed pot wiring.

03

PRESET SPEED #1: Selects PRESET SPEED #1 as the speed reference. The drive will operate at the frequency programmed into Parameter 31.

04

START FORWARD: Sets up the drive for a 3-wire start/stop circuit. Momentarily close TB13A to TB-11 to start the drive, and momentarily open TB-1 to TB-11 to stop.

05

RUN REVERSE: Close TB-13A to TB-11 to run in the reverse direction, and open to stop. Close TB-1 to TB-11 to run in the forward direction and open to stop.

06

START REVERSE: Momentarily close TB-13A to TB-11 to start the drive in the reverse direction, and momentarily open TB-1 to TB-11 to stop. Parameter 17 - ROTATION must be set to FORWARD AND REVERSE (02), and TB-13C must be used for START FORWARD.

07

EXTERNAL FAULT: Sets TB-13A as a normally closed external fault input. Open TB-13A to TB-11 to trip the drive.

26

Page 30

08

DB FAULT: Sets TB-13A as a dynamic braking fault input when used with the optional dynamic braking module. When this input is activated by the dynamic braking module, the drive will trip into a "dF" fault and the motor will coast to a stop. Refer to the instructions included with the Dynamic Braking option.

09

AUXILIARY STOP: When TB-13A is opened with respect to TB-11, the drive will decelerate to a STOP (even if STOP METHOD is set to COAST) at the rate set into ACCEL/DECEL #2 (Parameter 42).

10

ACCEL/DECEL #2: Selects the acceleration and deceleration time programmed into ACCEL/ DECEL #2 (Parameter 42).

NOTE: If the optional remote keypad is used, functions 02, 04, 05, and 06 are disabled. Therefore, if this terminal is not being used for any of the other functions, it should be set to NONE (01). 11

TB-13B FUNCTION SELECT

This selects the function of terminal TB-13B. Closing TB-13B to TB-11 (or opening in the case of settings 07 and 09) activates the selected function. The following functions can be selected: 01

NONE: Disables the TB-13B function.

02

SPEED POT: Selects a speed pot as the speed reference input. Refer to Section 11.0 for speed pot wiring.

03

PRESET SPEED #2: Selects PRESET SPEED #2 as the speed reference. The drive will operate at the frequency programmed into Parameter 32.

04

DECREASE FREQ: Closing TB-13B to TB-11 will decrease the speed setpoint until the contact is opened. TB-13C must be programmed for INCREASE FREQ.

05

JOG FORWARD: Close TB-13B to TB-11 to JOG in the forward direction. The drive will run at PRESET SPEED #2 (Parameter 32) when in JOG mode.

06

JOG REVERSE: Close TB-13B to TB-11 to JOG in the reverse direction. The drive will run at PRESET SPEED #2 (Parameter 32) when in JOG mode.

WARNING! When operating in JOG mode, the STOP signal and the AUXILIARY STOP function (see Parameters 10-12) WILL NOT stop the drive. To stop the drive, remove the JOG command. JOG REVERSE will operate the drive in reverse rotation even if ROTATION DIRECTION (Parameter 17) is set to FORWARD ONLY. 07

EXTERNAL FAULT: Sets TB-13B as a normally closed external fault input. Open TB-13B to TB-11 to trip the drive.

27