The text of a manual · part 2 of 5
AC Tech Variable Speed AC Motor Drives SCN Series Installation and Operation Manual, pages 11 to 20
Pages 11 to 20 of 47
The original document is the PDF (269 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the AC Tech SN103S and Lenze SN103S
Page 11
Minimum voltage rating of the protection device should be 250 Vac for 120/208/240 Vac and 208/240 Vac rated drives. UL Class CC fast-acting, current limiting type fuses should be used when input fusing is required. Select fuses with low I 2 T values, rated at 200,000 AIC. Recommended fuses are Bussman KTK-R. Similar fuses with equivalent ratings by other manufacturers may also be acceptable.
8.0
POWER WIRING
WARNING! Hazard of electrical shock! Capacitors retain charge after power is removed. Disconnect incoming power and wait until the voltage between terminals B+ and B- is 0 VDC before servicing the drive. Note drive input and output current ratings and check applicable electrical codes for required wire type and size, grounding requirements, over-current protection, and incoming power disconnect, before wiring the drive. Size conservatively to minimize voltage drop. Strip off 0.20 to 0.25 inches of insulation for input power, output power, and DC Bus wiring. The input power, output power, and DC Bus terminals must be tightened to a torque of 4.0 to 4.5 lb-in. Input fusing and a power disconnect switch or contactor MUST be wired in series with terminals L1, L2, and L3 for three phase input models. For 208/240 Vac single phase input models, use terminals L1 and L2. For 120 Vac single phase input models, use terminals L1 and N. This disconnect must be used to power down the drive when servicing, or when the drive is not to be operated for a long period of time, but should not be used to start and stop the motor. Repetitive cycling of a disconnect or input contactor (more than once every two minutes) may cause damage to the drive. 8.1
WIRING FOR SINGLE PHASE OR THREE PHASE INPUT
If the drive is rated for 120/208/240 Vac single phase input (SN100S models), wire the input to terminals L1 and N for 120 Vac voltage, or wire to terminals L1 and L2 (do not wire to N) for 208/240 Vac input voltage. Refer to Section 9.0 - SCN POWER WIRING DIAGRAM. If the drive is rated for 208/240 Vac single phase input (SN200S models), wire the input to terminals L1 and L2. If the drive is rated for three phase input (SN200 models), wire the input to terminals L1, L2, and L3. All three power output wires, from terminals T1, T2, and T3 to the motor, must be kept tightly bundled and run in a separate conduit away from all other power and control wiring. Do not install contactors between the drive and motor without consulting AC Technology Corporation for more information. Operating such devices while the drive is running can potentially cause damage to the drive's power components. If such a device is required, it should only be operated when the drive is in a STOP state.
8
Page 12
9.0
SCN POWER WIRING DIAGRAM THREE PHASE INPUT (SN200 SERIES)
L1
L2
120 Vac SINGLE PHASE INPUT (SN100 SERIES)
L1
L3
208/240 Vac SINGLE PHASE INPUT (SN100 AND SN200S SERIES)
L2
N
OUTPUT (ALL SERIES) T1 T2 T3 B- B+
L1
L2
L3*
*On SN100 models, this terminal
+ is labeled N.
3 PHASE AC MOTOR
DC BUS VOLTAGE
WARNING! Do not connect incoming AC power to output terminals T1, T2, or T3. Severe damage to the drive will result.
NOTES: 1. WIRE AND GROUND IN ACCORDANCE WITH NEC OR CEC, AND ALL APPLICABLE LOCAL CODES. 2. Motor wires MUST be run in a separate steel conduit away from control wiring and incoming AC power wiring. 3. Do not install contactors between the drive and the motor without consulting AC Technology for more information. Failure to do so may result in drive damage. 4. Use only UL and CSA listed and approved wire. 5. Minimum wire voltage ratings: 300 V for 120, 208 and 240 Vac systems. 6. Wire gauge must be based on a minimum of 125% of the rated input/output current of the drive, and a minimum 75°C insulation rating. Use copper wire only. 7. Strip off 0.20 to 0.25 inches of insulation for input power, output power, and DC Bus wiring.
9
Page 13
10.0
CONTROL WIRING
WARNING! Hazard of electrical shock! The SCN control terminals are not isolated from line voltage! Line voltage is present between the control terminals and ground. Do not touch! Disconnect input power and wait three minutes before making connections to the control terminals. Devices (such as switches, pushbuttons, potentiometers, relays, etc) and wiring connected to the control terminals are hot to ground and must have an insulation rating of at least 240 Vac or a dielectric rating of at least 1500 volts to prevent damage to equipment and/or injury to personnel. 10.1
CONTROL WIRING VS. POWER WIRING
External control wiring MUST be run in a separate conduit away from all other input and output power wiring. If control wiring is not kept separate from power wiring, electrical noise may be generated on the control wiring that will cause erratic drive behavior. Use twisted wires or shielded cable rated for 300 VDC minimum (do not ground the shield). 10.2
SURGE SUPPRESION ON RELAYS
Current and voltage surges and spikes in the coils of contactors, relays, and solenoids, near or connected to the drive, can cause erratic drive operation. Snubbers should be used on any coils associated with the drive. For AC loads, snubbers should consist of a resistor and a capacitor in series across the coil. For DC loads, a free-wheeling or flyback diode should be placed across the coil. 10.3
START/STOP CONTROL
There are various control schemes that allow for 2-wire and 3-wire Start/Stop circuits. Refer to the wiring diagrams in Section 11.0 - SCN CONTROL WIRING DIAGRAMS. 10.4
SPEED REFERENCE SIGNALS
SPEED POT
Connect the wiper to terminal TB-5, and connect the high and low end leads to terminals TB-6 and TB-3, respectively. The speed pot can be 5kΩ up to 10kΩ.
0-10 VDC
Wire the positive to terminal TB-5 and the negative to terminal TB-3. The 0-10 VDC signal must be isolated, as the control terminals are at line voltage potential.
DO NOT connect the low side of the speed pot or 0-10 VDC signal to ground.
10
Page 14
10.5
SPEED REFERENCE SELECTION
If a speed pot is to be used to control the drive speed, terminal TB-13A, 13B, or 13C (Parameter 10, 11, or 12) may be programmed as the input select for the speed pot. When that TB-13 terminal is then closed to TB-11, the drive will follow the speed pot input. If the speed pot is not selected on the terminal strip using TB-13A, 13B, or 13C, speed control will default to STANDARD mode, which is governed by the setting of Parameter 05 - STANDARD SPEED SOURCE. The STANDARD SPEED SOURCE can be the ! and " buttons on the front of the drive, PRESET SPEED #1 (Parameter 31), or a speed pot. PRESET SPEEDS TB-13A can be programmed to select PRESET SPEED #1, TB-13B to select PRESET SPEED #2, and TB-13C to select PRESET SPEED #3. There are a total of seven preset speeds, which are activated by different combinations of contact closures between TB-13A, 13B, 13C and TB-11. Refer to Parameters 31-37 in Section 15.0 - DESCRIPTION OF PARAMETERS. JOG TB-13B can be programmed to select either JOG FORWARD or JOG REVERSE. The Jog speed is set by PRESET SPEED #2. Close TB-13B to TB-11 to JOG, and open the contact to STOP. WARNING! When operating in JOG mode, the STOP signal and the AUXILIARY STOP function (see Parameters 10-12) WILL NOT stop the drive. To stop the drive, remove the JOG command. JOG REVERSE will operate the drive in reverse rotation even if ROTATION DIRECTION (Parameter 17) is set to FORWARD ONLY. NOTE: If the drive is commanded to JOG while running, the drive will enter JOG mode and run at PRESET SPEED #2. When the JOG command is removed, the drive will STOP. MOTOR OPERATED POT (MOP) / FLOATING POINT CONTROL TB-13B and TB-13C are required for this function, which controls the drive speed using normally open contacts wired to the terminal strip. Program TB-13B for DECREASE FREQ, and program TB13C for INCREASE FREQ. Closing the contacts between the TB-13 terminals and TB-11 will cause the speed setpoint to increase or decrease until the contact is opened. The INCREASE FREQ function will only operate while the drive is running. NOTE: If TB-13A, TB-13B, and TB-13C are all programmed to select speed references, and two or three of the terminals are closed to TB-11, the higher terminal has priority and will override the others. For example, if TB-13A is programmed to select a speed pot, and TB-13C is programmed to select PRESET SPEED #3, closing both terminals to TB-11 will cause the drive to respond to PRESET SPEED #3, because TB-13C overrides TB-13A.
11
Page 15
10.7
DRIVE STATUS DIGITAL OUTPUTS
There is one open-collector output at terminal TB-14. The open-collector circuit is a current-sinking type rated at 30 VDC and 50 mA maximum. The open-collector output can be programmed to indicate any one of the following: RUN, FAULT, INVERSE FAULT, FAULT LOCKOUT, AT SPEED, ABOVE PRESET SPEED #3, CURRENT LIMIT, AUTO SPEED MODE, and REVERSE. Refer to Parameter 06 in Section 15.0 - DESCRIPTION OF PARAMETERS.
SCN TERMINAL STRIP
DIODE SNUBBER (RECOMMENDED) TB-11
RELAY COIL
TB-14
WARNING! Hazard of electrical shock! The SCN control terminals are not isolated from line voltage! Line voltage is present between the control terminals and ground. Do not touch! Only use relays with an insulation rating of at least 240 Vac or a dielectric rating of at least 1500 volts to prevent damage to equipment and/or injury to personnel.
NOTE: When the optional remote keypad is used, TB-14 is wired to the remote keypad and cannot be used for status indication.
12
Page 16
11.0
SCN CONTROL WIRING DIAGRAMS
11.1
TWO-WIRE START/STOP CONTROL
WARNING! Hazard of electrical shock! The SCN control terminals are not isolated from line voltage! Line voltage is present between the control terminals and ground. Do not touch! Disconnect input power and wait three minutes before making connections to the control terminals.
13B
13C
14
OPEN-COLLECTOR OUTPUT
13A
TB-13C FUNCTION SELECT
SPEED POT INPUT
11
TB-13B FUNCTION SELECT
SPEED POT COMMON
6
TB-13A FUNCTION SELECT (RUN REVERSE)
5
DIGITAL INPUT REFERENCE
3
SPEED POT POWER SUPPLY
1
RUN
Devices (such as switches, pushbuttons, potentiometers, relays, etc) and wiring connected to the control terminals are hot to ground and must have an insulation rating of at least 240 Vac or a dielectric rating of at least 1500 volts to prevent damage to equipment and/or injury to personnel.
SPEED POT
MAINTAINED RUN/STOP CONTACT (FORWARD)
MAINTAINED RUN/STOP CONTACT (REVERSE)
NOTES: 1. Close TB-1 to TB-11 to RUN, and open to STOP. TB-1 functions as a RUN input for two-wire start/stop circuits, and a STOP input for three-wire start/stop circuits. Refer to Section 11.2. 2. If reverse direction is required, set ROTATION (Parameter 17) to FORWARD AND REVERSE (02), and program TB-13A (Parameter 10) to RUN REVERSE (05). Close TB-13A to TB-11 to RUN in the reverse direction, and open to STOP. 3. For speed pot control, set STANDARD SPEED SOURCE (Parameter 05) to SPEED POT (03). 13
Page 17
11.2
THREE-WIRE START/STOP CONTROL
WARNING! Hazard of electrical shock! The SCN control terminals are not isolated from line voltage! Line voltage is present between the control terminals and ground. Do not touch! Disconnect input power and wait three minutes before making connections to the control terminals.
13C
14
OPEN-COLLECTOR OUTPUT
13B
REV
SPEED POT
MOMENTARY STOP CONTACT
13A
TB-13C FUNCTION SELECT (START FORWARD)
SPEED POT INPUT
11
TB-13B FUNCTION SELECT
SPEED POT COMMON
6
TB-13A FUNCTION SELECT (START REVERSE)
5
DIGITAL INPUT REFERENCE
3
SPEED POT POWER SUPPLY
1
STOP
Devices (such as switches, pushbuttons, potentiometers, relays, etc) and wiring connected to the control terminals are hot to ground and must have an insulation rating of at least 240 Vac or a dielectric rating of at least 1500 volts to prevent damage to equipment and/or injury to personnel.
FWD
MOMENTARY START CONTACT
NOTES: 1. Program TB-13C (Parameter 12) for START FORWARD (05). 2. If reverse direction is required, set ROTATION (Parameter 17) to FORWARD AND REVERSE (02), and program TB-13A (Parameter 10) for START REVERSE (06). 3. Momentarily close TB-13C to TB-11 to START in the forward direction, or close TB-13A to TB11 to START in the reverse direction. Momentarily open TB-1 to TB-11 to STOP the drive. 4. For speed pot control, set STANDARD SPEED SOURCE (Parameter 05) to SPEED POT (03). 14
Page 18
11.3
PRESET SPEEDS (WITH TWO-WIRE START/STOP CONTROL)
WARNING! Hazard of electrical shock! The SCN control terminals are not isolated from line voltage! Line voltage is present between the control terminals and ground. Do not touch! Disconnect input power and wait three minutes before making connections to the control terminals.
13B
13C
14
OPEN-COLLECTOR OUTPUT
13A
TB-13C FUNCTION SELECT (PRESET SPEED #3)
SPEED POT INPUT
11
TB-13B FUNCTION SELECT (PRESET SPEED #2)
SPEED POT COMMON
6
TB-13A FUNCTION SELECT (PRESET SPEED #1)
5
DIGITAL INPUT REFERENCE
3
SPEED POT POWER SUPPLY
1
RUN
Devices (such as switches, pushbuttons, potentiometers, relays, etc) and wiring connected to the control terminals are hot to ground and must have an insulation rating of at least 240 Vac or a dielectric rating of at least 1500 volts to prevent damage to equipment and/or injury to personnel.
SPEED POT
MAINTAINED RUN/STOP CONTACT NOTES: 1. For preset speed control, all or some of the TB-13 terminals must be programmed as preset speed selects. If only two or three preset speeds are required, only two of the TB-13 terminals must be used. Refer to the table in the description of Parameters 31-37 in Section 15.0. 2. Program the PRESET SPEEDS (Parameters 31-37) to the desired values. 3. If speed pot control is desired when none of the preset speeds are selected (all preset speed selects are open to TB-11), set STANDARD SPEED SOURCE (Parameter 05) to SPEED POT (03). 15
Page 19
12.0
INITIAL POWER UP AND MOTOR ROTATION
WARNING! DO NOT connect incoming AC power to output terminals T1, T2, and T3! Severe damage to the drive will result. Do not continuously cycle input power to the drive more than once every two minutes. Damage to the drive will result.
WARNING! Hazard of electrical shock! The SCN control terminals are not isolated from line voltage! Line voltage is present between the control terminals and ground. Do not touch! Capacitors retain charge after power is removed. Disconnect input power and wait until the voltage between terminals B+ and B- is 0 VDC before making control connections or servicing the drive.
WARNING! Severe damage to the drive can result if it is operated after a long period of storage or inactivity without reforming the DC bus capacitors!
If input power has not been applied to the drive for a period of time exceeding three years (due to storage, etc), the electrolytic DC bus capacitors within the drive can change internally, resulting in excessive leakage current. This can result in premature failure of the capacitors if the drive is operated after such a long period of inactivity or storage. In order to reform the capacitors and prepare the drive for operation after a long period of inactivity, apply input power to the drive for 8 hours prior to actually operating the motor. Before attempting to operate the drive, motor, and driven equipment, be sure all procedures pertaining to installation and wiring have been properly followed. If possible, disconnect the driven load from the motor. Verify that the drive input terminals (L1, L2, and L3 or N) are wired to the proper input voltage per the nameplate rating of the drive. Energize the incoming power line. The LED display will flash a two-digit number (15 in the example below) that identifies the parameter version contained in the drive ("15" actually means parameter version 315). The display should then read “- -", which indicates that the drive is in a STOP condition. This is shown below:
Apply input power Display flashes parameter version (00-99) Display then reads "- -" 16
Page 20
Follow the procedure below to check the motor rotation. This procedure assumes that the drive has been powered up for the first time, and that none of the parameters have been changed. 1. Use the ! button to decrease the speed setpoint to 0 Hz. The left decimal point will illuminate as the speed setpoint is decreased. Once 0 Hz is reached, the display will toggle between “00” and “- -”, which indicates that the drive is in a STOP condition with a speed setpoint of 0 Hz. 2. Give the drive a START command. This can be done using one of several wiring methods described in Section 11.0 - SCN CONTROL WIRING DIAGRAMS. Once the START command is issued, the display will read “00”, indicating that the drive is in a RUN condition with a speed setpoint of 0 Hz. 3. Use the " button to increase the speed setpoint until the motor starts to rotate. The left decimal point will light as the speed setpoint is increased. 4. If the motor is rotating in the wrong direction, give the drive a STOP command and remove power from the drive. Wait three minutes for the bus capacitors to discharge, and swap any two of the motor wires connected to T1, T2, and T3. NOTE: The drive is phase insensitive with respect to incoming line voltage. This means that the drive will operate with any phase sequence of the incoming three phase voltage. Therefore, to change the motor rotation, the phases must be swapped at the drive output terminals or at the motor.
17