3. HANDLING /MELSEC-Aq

3. HANDLING

This chapter explains the handling instructions from unpacking to installation and also the nomenclature and setting of various conditions.

3.1 Handling Instructions

This section explains the handling instructions for the unpacking to installation of PC main unit, memory, battery, etc.

3.1.1 CPU

(1) Since the case, terminal block connector, and pin connector of this PC are made of plastic, do not drop or subject to mechanical ‘shock.

(2) Do not remove the printed circuit board of any unit from its case. Removal may cause board damage.

(3) When wiring, take care to prevent entry of wire offcuts into the unit. If any conductive debris has entered the unit, make sure that it is removed.

(4) Tighten the unit mounting screws and terminal screws in the following ranges.

Tightening Torque Screw Range (kg-cm) 1/O unit terminal block terminal screw (M3 screw) 5to8 1/0 unit terminal block mounting screw (M4 screw) 8 to 14

CPU unit terminal block screw

(M4 screw) (Power input section) 10 to 14

Unit mounting screw (not required normally)

(M4 screw) 8 to 12

3.1.2 Memory chips

(1) To load the memory chip into the socket, securely press the memory chip into the socket and then lock.

(2) Never place the chip on metal, which may allow current flow, or on an object which is charged with static electricity, such as wood, plastic, vinyl, fiber, cable, and paper.

(3) Do not touch the legs of the chip. Also, do not bend the legs.

(4) When mounting the memory, be sure to fit the chip as indicated on the socket. If reversely installed, the chip will be damaged.

3-1

IB (NA) 66058-A

Page 12 read from a scan by OCR; it may hold reading errors

3. HANDLING | /MELSEC-Aq

(5) If t(C-RAM is removed from the socket, memory data will! be lost. Therefore, caution should be exercised.

IMPORTANT

Before installing and removing the memory chip to and from the CPU, be sure to turn off the power. If installation or removal is performed during power on, the chip will be damaged.

3.1.3 Battery (1) Do not short-circuit the battery. (2) Do not disassemble the battery. (3) Do not throw the battery into flames. . (4) Do not heat the battery.

(5) Do not solder the poles of the battery.

3-2

IB (NA} 66058-A

Page 13 read from a scan by OCR; it may hold reading errors

3. HANDLING

MELSEC-

3.2 CPU Unit

This section describes the nomenclature and setting of the AOJ2CPU unit. ,

3.2.1 Nomenclature

Connector for 1/O or extension cable

For sending and receiving signals to and from the |/O unit and extension base unit, Used to connect 1/O cable (AQJ2COf3) or extension cable (AOJ2CE#77B).

RUN/STOP key switch

RUN: Executes operation of se- quence program,

STOP: Turns all outputs off and stops the operation of se- quence program, |

L.CLR: Sets all data memories, ex- cept special relay (M) and special register (D), in the latch area to “OFF” or 0",

RESET: Resets hardware. Performs reset at operation error oc- currence and initializes ope- ration. Latch memory is not cleared,

Cover mounting screw

Fixes the front cover.

Unit mounting hole

Fixes the unit onto a panel, such as a control panel, or used to mount 1/0 unit,

STOP; Aov2cru, POWER LicLR pa ARUN r AUN reser Gy RESET

RUN LED indicates CPU operating status. : Indicates that sequence ope- ration is being executed with io) POWER LED Iluminates when AC power is on and 5V DC output is within normal . level, WN Sets memory loading, RAM/ROM )_| selection, and MEMORY PROTECT switch setting, (Capped with a cover) For details, refer to the following page. For setting, refer to Section 3.2.2.

RUN key switch set to RUN or CPU is not in remote STOP state.

OFF: Indicates that RUN key switch is in STOP position or \

Used to connect with the peripheral equipment. (When the peripheral equipment is not installed, be sure to place a cover on this connector.)

CPU is not in remote STOP or RESET state.

Flashing: Indicates that error has been @ detected by self-diagnostic @_ do function or latch clear ope- V/s surat te ts | SaRs ration has been performed. ACI OPEN Aca DEW De:

Peripheral equipment fixing screw Termina} block for power supply

Fixes the peripheral unit. Composed of AC input terminal,

100/200V AC select terminal, LG (line ground) terminal, FG (flame ground) terminal, and 24V DC output terminal. For details and line voltage, refer to the AQJ2 User’s Manual (1/O Unit Edition).

It is necessary to set or install the shaded area before test run and adjustments.

IB (NA) 66058-A

Page 14 read from a scan by OCR; it may hold reading errors

3. HANDLING | | /MELSEC-A

POINT |

(1) RUN LED remains on if the annunciator (F) is set.

(2) For the setting of the RUN/STOP switch to “L.CLR” (Latch Clear), refer to the AQJ2CPU Programming Manual.

(3) Operation is started when the power is turned on with the RUN/STOP switch set to “RUN” position. When the switch is changed from RUN to STOP, the operation is stopped and all outputs are turned off. In this case, all control information in RUN mode completely remains. If the switch is set again to RUN without resetting, the operation is resumed. Usually, the operation may be started by turning on the power with the switch set to RUN.

3.4

IB (NA) 66058-A

Page 15 read from a scan by OCR; it may hold reading errors

3. HANDLING

[ Details of Memory Setting Area |

Fixes the memory in the memory loading socket. (Use a flat-blade screwdriver to Jock or unlock. For the rotating direction, refer to the seal on the socket.)

Socket for installing memory

Loaded with IC-RAM/EP-ROM/EEP ROM.

Selects RAM, ROM, or EPROM. Use the short chip to select.

Selects memory capacity, 4K or 8K, to be used. Set using a short-circuit chip.

Backs up IC-RAM memory and the power failure compensation feature.

Connects the lead wire of the battery. (The battery lead is removed before shipment to prevent battery dis- charge.)

Enables or disables write to the mem- ory when IC-RAM or EEPROM is installed into the memory loading socket.

M.PRO in[ON]position:

disables write

M.PRO in position:

enables write

* For setting, refer to Section 3.2.2, j It is necessary to set or install the shaded area before test run and adjustments.

3-5

IB (NA) 66058-A

Page 16 read from a scan by OCR; it may hold reading errors

3. HANDLING

| Detalis of Power Supply Terminal Block |

A0J2-DC24

Terminal screw ey | eee ve Fe M4 x 0.7 x8 OSS SSS \ Terminal cover Protects the terminal block. Must be kept on the terminal block except during wiring. Power input terminals FG terminal Connect 24V DC power supply. Connected with shielding pattern on the printed circuit board.

LG terminal

Ground terminal for power filter.

3-6

IB (NA) 66058-D

Page 17 read from a scan by OCR; it may hold reading errors

3. HANDLING © | MELSEC-A

3.2.2 Setting

This section describes the setting of IC-RAM, EP-ROM, and EEP- ROM, the setting of the memory protect switch, and the installation of the battery.

(1) Memory loading and setting The following flow chart shows how to instal! the memory into the memory socket and the placement of the setting pin according to the memory type.

P-ROM/EEPROM/IC-RAM operation)

Hold the memory without touching the legs.

Turn and loosen the memory lock in the socket.

Insert the memory with the concave set as indicated on the socket.

i i "

(> Turn and fix the memory lock while pressing the memory with fingers.

| How to hold the memory

Make sure that the memory is not lifted from the socket.

L

Fr

Apply the furnished masking tape to the ROM surface.

f

Insert the setting pin into pin} | Insert the setting pin into pin] | Insert the setting pin into connector. connector. pin connector.

! f i

Insert the setting pin into or! [Insert the setting pin into or} | insert the setting pin into pin pin connector according to pin connector according to connector according to the EEPROM the capacity of the EP-ROM to bef [| the IC-RAM capacity. capacity. C Completed Dp) Memory setting Pin Connector Setting Memory Type Memory Capacity Setting | Memory setting (Memory type) [4k] 4KROM ae Os aM (EROW 8KROM ers Selele| [elololo 4KRAM ers [ROM] RAM [EROM) 16KRAM cbt! RAB (eile 4KEROM oat on pbk] BBB je | indicates the setting pin inserting position.

3-7

1B (NA) 66058-A

Page 18 read from a scan by OCR; it may hold reading errors

3. HANDLING AMIEL SECAA

POINT |

When using 16KRAM, connect a peripheral unit to the CPU and then perform the following memory clear operation.

AG6GPP} Key operation on cursor to "PC MEMORY ALL CLEAR” resto oo Hf v Hf oo | seeesanenes Set the A0J2 key switch to RESET. A7PU} Key operation

STP STP stesvaneaee Set the AOJ2 key switch to RESET.

After completion of operation with one of the above peripheral units, perform normal write operation,

(2) Setting the memory protect switch

When IC-RAM or EEPROM memory is used, the memory protect switch should be set to the[ON| position after writing programs in order to avoid the memory contents from being rewritten due to . misoperation of the peripheral device (AGGPP or A7PU). Set this switch to[OFF| before correcting the memory contents.

Memory Protect Switch Setting

To set to ON To set to OFF

A Z li

OFF OFF

Memory Protect setting switch ale e|

Memory Protect Switch Setting

(3) Installing the battery

Since the battery connector is factory-disconnected, connect the connector according to the following procedure when using the RAM memory or power failure compensation function.

Open the cover of memory setting | area in the CPU front.

f

Make sure that the battery is installed properly.

Connect the battery connector to the printed circuit board connector after checking its direction.

( Completed ) [ Connector for battery lead

Since the battery connector is removed before shipment to prevent discharge during transportation and/or storage, connect the connector when using the battery. ;

3-8

IB (NA) 66058-A

Page 19 read from a scan by OCR; it may hold reading errors

3. HANDLING /MELSEC-A

3.2.3 Latch range setting and latch clear

(1) The latch function retains the data of the specified devices

(devices in the latch range) if: (a) The power is switched off.

(b) The PC is reset.

(2) Devices L, B, T, C and D can be latched. Any of the following latch and non-latch ranges may be defined by the peripheral device: Non-Latch Range Latch Range MO to M2047 TO to T127 No latch CO to C127 DO to D511 BO to B3FF MO to M1023 L1024 to L2047 TO to T39/T80 to T40 to T79/T100 to Seconc’halt | 199/T120 to T123 T119/T124 to 1127 (1/2 latch) CO to C63 C64 to C127 DO to D255 D256 to D511 BO to B1FF B200 to B3FF LO to L2047 TO to T127 Full latch CO to C127 DO to D511 BO to B3FF

(3) The AOJ2 defaults to ‘1/2 latch.” When the AQJ2 is used for the first time, latch clear must be performed or the latch range parameter changed to ‘‘no latch.” (Without this initialization, normal sequence processing may not be ensured because RAM data of the latched devices is indefinite.)

(a) When the latch function is not used, change the latch range parameter to “‘no latch” and reset.

(b} When the latch function is used, perform latch clear. (4) Latch clear procedure

(a) Latch clear initializes the latch and non-latch range data and causes the devices to be as follows:

1) Y, M/L,F,B..... Switched off. 2) Special M (9000 to 9255)

weet eee eae ae Retained. 3) T,C............ Contact and coil are switched off. Present value is set to 0. 4) D,Z2,V......... Contents are reset to 0. 5) Special D (9000 to 9127) vec ete neues Retained.

IB (NA) 66058-D

Page 20 read from a scan by OCR; it may hold reading errors

3. HANDLING /MELSEC-AA

(b) Perform latch clear with the RUN key switch in the following procedure:

1) Move the RUN key switch from “STOP” to “L.CLR” three times. The “RUN LED” flickers to indicate that latch clear is ready.

2) Move the RUN key switch from “STOP” to “L.CLR” once again. This completes latch clear.

POINT

If the RUN key switch is set to “RUN” or “RESET” during the latch clear operation, latch clear is canceled and:

The AOJ2 is run and continues operation if the switch is set to RUN. The AOQJ2 is reset if the switch is set to RESET.

3-10 iB (NA) 66058-D