Page 21 read from a scan by OCR; it may hold reading errors

MELSEC-AA

4. CONCEPT AND CAUTIONS FOR AOJ2CPU SYSTEM CONFIGURATION

4. CONCEPT AND CAUTIONS FOR AOJ2CPU SYSTEM CONFIGURATION

The AOJ2CPU system is constructed by connecting |/O units, extension power supply units, or extension base units. This chapter describes the system configuration concept and cautions.

4.1 Assignment and Concept of I/O Numbers

1/O number assignment is one of the system configuration requirements. Wrong assignment results in failure. This section explains the |/O number assignment and concept of AOQJ2CPU system.

(1) X and Y represent input and output, respectively. 1/O numbers are addressed in hexadecimal. (0 to F)

(2) 1/O numbers are determined by the I/O unit numbers in each |/O unit. One unit occupies 64 points.

(3) When extension base unit (A65B, A55B) is used, be sure to start 1/0 numbers with X/Y100. One I/O unit loaded in extension base unit occupies 64 points.

i/O number assignment in AOJ2CPU system |

1/0 1) 1 unit occupies 64 I/O points. unit | 1/0 number ; 2) 1/0 numbers are determined by I/O unit numbers No, (0 to 7), (For I/O unit number setting, refer to xoo Y20 Section 3.2.2 of User’s Manual (I/O Unit Edition).) 0 X00 to X1F to to 3) A maximum of 8 I/O units may be connected. Y20 to Y3F 4} 1 unit occupies 64 1/O points. Therefore, for X1F Y37 example, when 24 point unit is used, 40 points 1 X40 to X5F T are not used. In this case, if I/O unit is changed, Y60 to Y7F it is not necessary to change the presently used 1/O 40 numbers. ; ; 2 X80 to X9F X4F 5) Output number corresponding to input number YAO to YBF. Y50 and unused number may be used as internal mem- ¥8p ory (M). However, these numbers cannot be used 3 XCO to XDF for input dedicated unit. YEO to YFF J 6) Exercise care so that the same I/O unit numbers are not used in a system. If the same numbers are | X100 to X11F X80 YAO used, the same I/O numbers will exist, resulting in 4° | ¥120 to Y13F to to failure. X9F YB7 | 7) 1/O unit numbers are 0 to 7. These do not have to 5 X140 to X15F be serial numbers. This is because !/O numbers are Y160 to Y17F | determined by I/O unit numbers as shown in the right side figure. However, it is recommended to 6 X180 to X19F xco YEO set them in serial numbers in consideration of the Y1A0 to Y1BF to to 1/O number concept. XDF YF7 7 X1C0 to X1DF |__ Y1E0 to Y1FF I X100 xidr ¥j}20 Y12B ] X140 [E32] to X15F

X180 Y1A0 to to X19F Y1B7 I Y1E0 > to Y1F7 4-1

IB (NA) 66058-A

Page 22 read from a scan by OCR; it may hold reading errors

4, CONCEPT AND CAUTIONS FOR AQJ2CPU SYSTEM CONFIGURATION A /YJELSEC fA

1/O number assignment in extension base unit combined system |

1/0 X00 E56| | Y20 unit 1/0 number to E86] to No, y 1) 1 unit (this also applies to 1/O unit in extension X1F 37 base) occupies 64 I/O points. 0 X00 to X1F T 2) In extension base unit combined system, a maxi- Y20 to Y3F mum of four AOQJ2 t/O units may be connected. x40 Yeo | 3) Extension base unit should always be located at 1 X40 to X5F to to the final stage of system and its 1/O number should Y60 to Y7F begin with X/Y100. XSF Y77 4) Output number corresponding to input number 2 X80 to XOF | T and unused number may be used as internal mem- YAO to YBF ory (M). However, these numbers cannot be used for input dedicated unit. 3 XCO to XDF X80 YAO 5) In extension base unit combined system, a maxi- YEO to YFF to to mum of four AQJ2 I/O units may be connected. \secanie X9F YB7 In this case, set 1/O unit numbers within 0 to 3. inexterson] = 1/O number ~ tm iz 9 | X100 to X13F xco YEO Y100 to Y13F - to to XDF 4 X140 to X17F YF7 Y140 to Y17F | 2 X180 to X1BF Y180 to Y1BF , ¥ v 3 --=4 . x/Y | X/Y | X/Y 7 X/Y t X1C0 to X1FF 3 Y1C0 to YIFF 100 140 180 1C0 Un- ; to to to to usable H 13F 17F | 1BF | 1FF, t 4 Restrictions on extension base unit Slotunmber> 0 1 2 3 4

1) [In extension base unit, only slots 0 to 3 are usable.

2) Irrespective of used I/O units, 1 slot occupies 64 points. (Vacant slot also occupies 64 points.) Output number corresponding to input unit cannot be used as internal memory (M).

3) When 64 point I/O unit is not used (e.g. 16 or 32 point unit), observe of the following points:

Slot 0 Slot 1 Slot 2 Slot 3 16 point unit 32 point unit 64 point unit 64 point unit rt ! !

X/Y I | X/Y 1 X/lY X/lY

100 | 110 4 120 {130 | 140] 150 | 1601170 180 1CO to | to | to | to | to | to | to | to to to

10F TIF 1126 113F 14F|15F]16F!117F 1BF 1FF | Lt H a | r } j

@® When 64 point unit is used, there is no restriction.

® When 32 point unit is used, the latter half 32 points are not used. Actually, however, the first half 32 points and the latter half 32 points overlap with each other and CPU makes access. Therefore, if the fatter half {/O numbers are accidentally used in a program, the overlapping first half 1/O number area is actually accessed.

For example, 160 overlaps with 140 and 170 with 150. .

When 16 point unit is used, the latter 48 points are not used. Actually, however, four 16 point units overlap with each other. For example, if any of 110, 120, and 130 is accessed, 100 is accessed actually. Be sure to use actual |/O numbers in a program. In the example shown on the feft, Y100 to 10F are actual I/O numbers.

4-2

IB (NA) 66058-A

Page 23 read from a scan by OCR; it may hold reading errors

4.2 Precautions for Use of Type AOJ2PW Extension Power Supply Unit

4, CONCEPT AND CAUTIONS FOR AOJ2CPU SYSTEM CONFIGURATION / MELSEC-AA

(1) Determine the use of extension power supply unit by the total internal current consumption of the AOJ2CPU unit, I/O units, special function units, and peripheral devices. When using the extension base unit A55B, consider the total current consumption of units in the base unit because 5V DC power is supplied by the AQJ2CPU unit’s built-in power supply or extension power supply unit.

Unit Type Rated Output Current (A) 5V DC 24V DC AOJ2CPU unit’s built-in power supply 2 0.5 A0J2-PW extension power supply unit 2.3 1.5 A0J2-DC24CPU unit’s built-in power supply 2 - AOJ2PW-DC24 extension power supply unit 25 -

Table 4.1 Current Capacity of Power Supply Unit

Internal Current Consumption (A) Unit Type 24v DC Sv DC Input Output (7mA/point) cpu AOQJ2CPU 0.3 - - AQJ2CPU-DC24 0.3 - - AOJ2CPUP23 0.52 - - Data link AOJ2CPUR23 0.96 - ~ unit A0J2P25 0.47 - - AOJ2R25 0.89 _ - A0J2-E32A 0.105 -~ - Input unit A0J2-E32D * 0.105 0.224 - AOQJ2E-E32D A0J2-E24R 0.145 _ 0.23 AOJ2-E24S 0.4 - ~ Output unit AOJ2-E24T 0.145 - 0.069 AQJ2E-E24R AOJ2E-E24T A0J2-E28AR 0.14 - 0.125 A0J2-E28AS 0.26 - - A0J2-E28DR 0.13 0.112 0.125 A0J2-E28DS 0.26 0.112 - AOQJ2-E28DT 0.125 0.112 0.035 AQJ2E-E28DR AOJ2E-E28DS . AOJ2E-E28DT 1/0 unit AQJ2-E56AR 0.225 - 0.23 A0J2-ESGAS 0.46 = = A0J2-E56DR 0.23 0.224 0.23 A0J2-E56DS 0.46 0.224 - A0OJ2-E56DT 0.225 0.224 0.069 AOQJ2E-E56DR AOJ2E-E56DS AOQJ2E-E56DT Peripheral A7PU 0.3 = = unit A6BWU *0.3(0.8) - =

(offline).

Table 4.2 Current Consumption *The A6WU is 0.3A in standby state (online) and 0.8A during write

4.3

IB (NA) 66058-D

Page 24 read from a scan by OCR; it may hold reading errors

4, CONCEPT AND CAUTIONS FOR AOJ2CPU SYSTEM CONFIGURATION /MELSEC-AA

The internal current consumption values in Table 4.2 when all points are on.

When the power is supplied from the AQJ2CPU’s built-in’ power supply, the total internal current consumption of the entire system should be within the AQJ2CPU’s built-in power supply capacity range. p wat 5V current 5V current CPU's built-in power 5V current consumption of consumption of supply capacity: > consumption +~. \ i + ipheral 5V DC, 2A of CPU, _éSImulltaneously _Periphera . ON" 1/O units equipment (A7PU) Current consumption of 24V DC internal current 24V DC input sonsumption of 24V DC, 0.58 > simultaneously + simultaneously “ON” “ON” points relay/transistor outputs lf the total consumption exceeds the CPU’s built-in power supply capacity range, use the extension power supply unit (AQJ2PW). For the 1/O units which is supplied with 5V DC power by the extension unit, set the 1/O unit's internal power supply select. switch to “EX5V". (For details, refer to the 1/O Unit Edition.)

POINT |

The allowable current capacity of the 5V DC power supply which can be supplied from the extension power supply unit to the 1/O units and extension base unit is 2.3A. If it exceeds 2.3A, use the extension base unit AG5B.

(2) Since the 5V DC power is supplied to the I/O units and extension base unit through the |/O cables and extension cables, respectively, the voltage may drop at the cables. Therefore, specified voltage (4.75V DC or more) may not be supplied at the receiving end, causing input/output errors. Calculate the voltage requirement as described below and determine whether or not the AQJ2PW is to be used.

1) 5V DC power requirement

(a) 5V DC output voltage range of the power supply unit is 4.9 to 5.2V DC.

(b) The specified voltage at the |/O unit or the extension base unit is 4.75V DC or more.

4-4

IB (NA) 66058-A

Page 25 read from a scan by OCR; it may hold reading errors

4. CONCEPT AND CAUTIONS FOR AOJ2CPU SYSTEM CONFIGURATION. / MELSEC-AA

2) Cable resistances

AOQJ2CO1 ...... 0.0472 AQJ2C03 ...... 0.061782 AOJ2C06 ...... 0.088222 AQJ2CO4B ..... 0.06262 AOJ2C10B ..... 0.1262

Due to the above requirements 1) and 2), it is necessary to satisfy the specified voltage (4.75V DC or more) of the system at the receiving end when the 5V DC output of the power supply unit is a minimum of 4.9V DC. Voltage calculation at the receiving end is as described below:

v1 ; v2 +12 l2 | LL a | CPU it y \ uni i i hy he T “1 12 1/O unit number (0) 1/O unit number (1)

V1: Voltage drop at the cable between CPU unit and 1/O unit (0) V2: Voltage drop at the cable between |/O unit (0) and 1/0 unit (1) R1: Resistance of the cable between CPU unit and I/O unit (0) R2: Resistance of the cable between I/O unit (0) and 1/O unit (1) {1: Current consumption of the 5V DC power in {/O unit (0) 12: Current consumption of the 5V DC power in I/O unit (1)

The voltage drops V1 and V2 are,

V1=R1 (11412)

V2=R211 The voltage at the receiving end of 1/O unit (1) is,

Receiving end voltage = 4.9 - (V1+V2)>4.75 To satisfy the requirement that the receiving end voltage shall be 4.75V DC or more,

4.9 - 4.752V1+V2

0.152R1(11+12)+R212

If this condition is met, extension is allowed up to the 1/O unit (1).

Therefore, the number of |/O units to be extended or use of the extension base unit (A55B) can be determined when the following condition is met:

0.15(=4.9 - 4.75)2 sum of the voltage drops up to the receiving end

1B (NA) 66058-A

Page 26 read from a scan by OCR; it may hold reading errors

4. CONCEPT AND CAUTIONS FOR AOJ2CPU SYSTEM CONFIGURATION MELSECAA

(3) 5V DC power voltage drop calculation example using AQJ2 cables Power _ System Configuration Voltage Drop Judge Select Switch Using CPU’s Built-in Power Supply Only | 112 1/0 E I AQJ2C06 (2 pieces) . 0.15V xample Pieces) V 1 =AQJ2CO6Resistance x (11 +12) or less | CPUS5V 1 (1 048A ZO ie =0.0882 X (0.24 +0.48) O position =0.064(V) , BO%ON GOKON Using Extension Power Supply | 240 1/0 A0J2C01 A0J2C06 A0J2C01 cPUSV {2 pieces) (1 piece) (1 piece) V 1 =A0J2CO1 Resistance X (11-12) position: =0.47X (0.24+0.45) 1/0 unit rescceewrrnnne 1s 020A 12 QA 1A Wa O.4A Sea pee =0.033(V Example wales IIE men 0.033 (V) O 0,1 2 eyrtee dors aU T t V 2 =A0J2COGResistance x | s EX5V 2 Unitto-unt 1° Unit-to-unit Unit-to-unit +AQJ2C0 1 Resistance X |« position: "mounting * ! | mounting | mounting | =0.0882X0.45+0.047X0.21 HO units ee es | = ? Ow . r 0.05(V) 2,3,4,5 EUS EUS EMS i ESEASII ESAS! ESAS Mounting Extension Power Supply Unit V 1 =A0J2C01 Resistance X I on 1/O Unit at Final End +A0J2CO6Resistance X (li t12+13) =0.047 x0.96 +0.0882 x(0.24+0.48+0.72) 336 1/0 A0J2C06 AgJ2c01 =0.172(V) 0.15V (3 pieces) (1 piece) When the extension power) | or more oeeee peceea a, \ supply unit is used at the final r aly : 1s 0.204 OA teeta Yi =0.8A end, voltage drop at the final! x rien pote wake Ul ff ve end unit supplied with power tote ot ZZ is large and the requirement of CPU5V een ‘ Unit-to-unit 0.15V or fess is not satisfied. position: cee Load [ mounting} Therefore, take the following 1/0 units Example CPU Pt remedy 01 3 ESAS, ESAS ES6AS ESSAS ES6AS ES6AS , r) 4, 2 a 4 ct EX5V aqucos. = AGU2CO1 ; position: (3 pieces) (1 piece) V1 =AQJ2CO1 Resistance X Is 1/0 units ON tke +A0J2COGResistance X (11 +12) 2,3,4,5 oo a CL) Ie 0.488 er boa =0.047 X0.72 + 0.0882 x (0.24 +0.48) ek u ‘fn U Vive |: = riirtn erty + tt t 7 =0.0974(V) fo) Unit-to-unit ! : Unit-to-unit V 2 =A0J2CO6Resistance X/ + mounting 5 ' mounting =0.0882 x 0.24 See ae ee wns = CPU PW 0.021(V) ESAS ESAS ES6AS ESAS ESAS ESGAS 0 4 2 3 4 5 Using Extension Base Unit | 448 1/0 ; CPU5V AQJ2C06 AQJ2CO1 A0J2C10B 41/0 units ae we V 1 =AQJ2CO6Resistance x1: position: nee . . +AQJ2CO1 Resistance X |» 1/0 unit PTSTTeeuess sy gaa 0k boat AXxA2(2 units) =0.0882%0.2440.047x0.4 units Example rt HH Th - AY42(2 units} =0.08 . .047X0.48 O 0,1 4 rites potty + tt a, - - =0.0437(V) EX5V tue : Vz =A0J2C10BResistance x Is position: er eT ’ Ve = , tie ot =0.0126 0.492 . Rekate booed A vp oany ° 1/0 units cPy pw Type ASSB base unit, : : 2,3 ESASO ESAS? «= ESAS 2 EMASS

1) I/O unit numbers are indicated in parentheses. I/O unit current consumption has been calculated, assuming that the simultaneous ON ratio is a maximum of 60%.

2) In Examples 2, 3, and 4, the units supplied with 5V DC power from the extension power supply unit are indicated by the full line. The units supplied with the power by the CPU’s built-in power supply are shown by the dotted line.

3) Indicated above are voltage drops occurring between the power supply unit and the I/O unit at the final end.

4-6

IB (NA) 66058-A

Page 27 read from a scan by OCR; it may hold reading errors

"4. CONCEPT AND CAUTIONS FOR AOJ2CPU SYSTEM CONFIGURATION /MELSEC-A

POINT |

(1) As shown in Example 3 and 4, the voltage drop of the _ 1/O unit at the final end varies depending on the location of the extension power supply unit and the connection of the cable. Therefore, select the I/O or extension cable or select 1/O unit so that the voltage drop may be 0.15V in the system.

(2) Avoid using the extension power supply unit at the final end because the voltage drop value is larger.