5. LOADING AND INSTALLATION /MELSEC-A

5, LOADING AND INSTALLATION

5.1 Unit Mounting

This section explains unit mounting instructions, 5.1.1 Mounting instructions

_Explanation is given to the instructions for mounting the PC to a panel, etc.

(1) To improve ventilation or facilitate the replacement of unit, rovide 50mm (1,97 inch) or more the clearance around the PC.

(2) Do not mount the base unit vertically or horizontally to allow ventilation.

(3) Ensure that the base unit mounting surface is uniform to prevent strain. It excessive force is applied to the printed circuit boards, this will result in incorrect operation. Therefore, mount the base unit on a flat surface.

(4) Avoid mounting the base unit close to vibration sources, such as large-sized magnetic contactors and no-fuse breakers, install the base unit in another panel or separate the base unit from the vibration source.

(5) Provide a wiring duct as necessary. However, if the dimensions from the top and bottom of the PC are less than those shown in Fig. 5.1, note the following points:

(a) When the duct is located above the PC, the height of the duct should be 50mm (1.97 inch) or less to allow for suf-ficient ventilation.

Between the duct and the top of the PC, provide a distance so that the cable may be removed by opening the cable connector fixing lever. ;

If the lever at the unit top cannot be opened, unit replacement cannot be made.

5-1

IB (NA) 66058-A

Page 29 read from a scan by OCR; it may hold reading errors

5. LOADING AND INSTALLATION /MELSEC/A

5.1.2 Installation This section describes the installation of the unit.

(1) For the mounting hole positions of each unit, refer to Appendix 1, Dimensional Outline Drawing.

(2) Fig 5.1 shows dimensions when the A7PU is mounted on the CPU unit. For the dimensions of side-to-side and top-to-bottom arrangements, refer to the Fig. 5.2 and 5.3, respectively.

(3) Fig.5.4 shows dimensions when the extension base unit is installed. If Type AOJ2C10B extension cable is used, the unit can also be mounted on the door of the panel. AQJ2-EQ30103 AOJ2CPU

AQJ2-E320- > -E2403 i -E2800C0 S - A7PU AQJ2CPU

161 (6.34)

Unit: mm (inch) (1) Mounting (2) Mounting A7PU to !/O unit (3) Mounting A7PU to 2 1/O units A7PU to CPU and CPU combination and CPU combination

Fig. 5.1 Dimensions in Unit-to-Unit Mounting

120 (4.72)

The pane! ceiling, wiring duct, and component position indicated. g Oo A0J2co3 | 80 (3.15) or more =| 032006 E56 r= 50 to 70 (1.97 to 2.76) 1 *1 | go to 90 (3.15 to 3.54) OT] E56 *1:; When the duct is placed in 80 (3.15) clearance, select a proper duct. Unit: mm (inch)

Fig. 5.2 Side-to-Sede Installation Fig.5.3 Top-to-Bottom Installation g A0J2C10B 1/O units . 1/O units a e 100 to 120 Oo (3.94 to 4.72) E56 sa ( & 8 =a] 1 8 8

70 to 80 A0J2C04B

Extension cable (2.76 to 3.15) _

\_ Extension base unit (A55B, A65B)

Unit: mm (inch) Xv Extension base unit

(1) Side-to-side installation (2) Top-to-bottom installation Fig.5.4 Installation of Extension Base Unit

Fig.5.5 Horizontal Installation (not allowed)

POINT |

The distance from the CPU unit front to the external equipment should be 100mm or more.

5-2

IB (NA) 66058-A

Page 30 read from a scan by OCR; it may hold reading errors

5. LOADING AND INSTALLATION /MELSEC-A

5.1.3 Unit-to-unit mounting method Install the units as described below.

(1) Mounting the CPU unit (or extension power supply unit) to Type E28 £031/0 unit (or E3217}, £24173)

Cover mounting screw

Unit mounting screw (4-M4x0.7x18)

Mt LPLSSL LS

SILIITTLISTSSSTLLY,

(2) Mounting the CPU unit (or extension power supply unit) to Type E5633 1/0 unit bed tet

~\ ww

Unit mounting screw (4-M4x0.7x 18)

5-3

IB (NA) 66058-A

Page 31 read from a scan by OCR; it may hold reading errors

5. LOADING AND INSTALLATION | /MELSEC-A

(3) Mounting Type E28{7031/O unit (or, E32!7}, E24f"} ) to the E56i-3073 1/0 unit

Cover mounting screw

Unit mounting screw (4-M4x0.7x18)

POINT |

(1) The terminal block of the I/O unit is fixed by 2 mounting screws. To remove the terminal block, loosen the mounting screws.

Terminal block mounting screw Terminal block mounting screw

\

5-4

IB (NA) 66058-A

Page 32 read from a scan by OCR; it may hold reading errors

‘5, LOADING AND INSTALLATION / MELSEC-Al

(4) Connecting units using the AOQJ2-2F bracket

(a) Installation method

~“

\ 4 b - f

~\

Unit installation screw (4-M4x0.7x18)

%w

Unit installation screw (4-M4x0.7x18)

(b) Installed unit dimensions

Vj ~ A0J2C03 , / AQJ2CPU : Installation surf: ie Ys, Lill Yelle ante . 12.6 (0.50) _ 200 (7.87) .| MIN 37 (1.46) Unit: mm (inch) 5-5

IB (NA) 66058-D

Page 33 read from a scan by OCR; it may hold reading errors

- 5. LOADING AND INSTALLATION MELSEC-A

5.1.4 Unit-to-unit mounting

This section describes unit-to-unit mounting.

Up to three units can be mounted on the panel. When two or three units are mounted, unit combinations are as follows:

Number , . oe of Units Unit combination Upper (1) unit CPU | PW | E32) | E28 | E2BIo Upper E320; | o | oO (1) unit ry Zunits | Lower Four | oO | © ower unit ial en (2) unit E2800 ie) ie) E563} | O (o) oO (e) (e) © indicates that the upper (1) and lower (2) units may be combined. Upper (1) unit CPU | PW | Upper (1) unit | E320: (e) (e) 3 units | Intermediate (2) unit | elie red iate E24r; Oo fe) [ESGiIC fixed: Lower (3) unit| E2scx2} o | oO © indicates that the upper (1), intermediate (2), and tower units may be combined. 5-6

IB (NA) 66058-A

Page 34 read from a scan by OCR; it may hold reading errors

5. LOADING AND INSTALLATION /MELSEC-AA

5.2 Wiring

Wiring instructions for the AOJ2CPU system.

5.2.1 Wiring instructions instructions for wiring the power cable or I/O cables.

(1) Wiring of power source

(a) If voltage variations are greater than the specified, connect a constant-voltage transformer. In this case, use a transformer of within 5% output distortion factor,, - J Constant-voltage PC, - -+ transformer

(b}) Use a power supply which generates minimal noise across wire and across PC and ground. When excessive noise is generated, connect an insulating transformer.

I H rt ' H H 1 1/0 ! ‘ 3| \ PC E||3 ! equipment Lod bee Insulating transformer Insulating transformer

(c) When a power transformer or insulating transformer is employed to reduce the voltage from 200V AC to 100V AC, use one with a capacity greater than that indicated in the following table.

Power Supply Unit Transformer Capacity AONJ2CPU 56VA AOJ2PW 120VA

(d) When wirng, separate the PC power source from those for 1/O equipment and power equipment as shown below.

Main power . PC power source source 100V AC - 0 o - » - <s & PC 1/0 power source

“oN . - - o o - -» 1/0 equipment

Main power PC power source source 200V AC, © % ~o - 3| vO 1 power source

2 Z ile 1/O equipment

Main circuit power source oo Main circuit equipment

5-7 iB (NA) 66058-A

Page 35 read from a scan by OCR; it may hold reading errors

5. LOADING AND INSTALLATION _ - - - W SMELSEC-q

(e) Twist the 100V AC, 200V AC, and 24V DC cables as closely as possible. Connect units with the shortest possible wire lengths.

(f) To minimize voltage drop, use the thickest (max. 2mm? (0.0031"'sq.)) wires possible for the 100V AC, 200V AC, and 24V DC cables.

(g) Do not bundle the 100V AC and 24V DC cables with main-circuit wires or the I/O signal wires (high-voltage, large-current). Also, do not wire the above indicated cables close to the aforementioned wires. If possible, provide more than 100mm distance between the cables and wires.

(h) As a measure against verylarge surges (e.g. due to lightening), connect a varistor as shown below.

: [| ae Ty] re . | | equipment

L

= £2

[m [ ee

« Surge absorber for lightening

POINT |

1. Ground the surge absorber (E,) an the PC (E,) separately from each other,

2. Select a surge absorber making allowances for power voltage rises.

IB (NA) 66058-A

Page 36 read from a scan by OCR; it may hold reading errors

5. LOADING AND INSTALLATION | /MELSEC-A

(2) Wiring of 1/0 equipment

(a) Applicable size of wire to the terminal block connector is 0.75 to 2mm? (0.0012 to 0.0032’sq.). However, it is recommended to use wires of 0.75mm? (0.0012’’sq.) for con-venience.

(b) Separate the input and output lines.

(c) I/O signal wires must be at least 100mm (3.93 inch) away from high-voltage and large-current main circuit wires.

(d) When the I/O signal wires cannot be separated from the main circuit wires and power wires, ground on the PC side with batch-shielded cabies. Under some conditions it may be preferable to ground on the other side.

PC Shield cable, Ara nN 00 Input ul 4 LA == f o> Output Shield sheath (ra) 1 (DC =

(e) If wiring has been done with of piping, ground the piping.

(f) Separate the 24V DC 1/O cables from the 100V AC and 200V AC cables.

(g) If.wiring over 200mm (7,87 inch) or longer distance, trouble can be caused by leakage currents due to line capacity,

(3) Grounding

(a) The A series PC has good noise resistance (see Section 3.1). Therefore, the PC may be used without grounding except when there is excessive noise.

However, follow (b) to (e) described below.

(b) Ground the PC as independently as possible. Class 3 grounding should be used (grounding resistance 1002 or less).

(c) When independent grounding is impossible, use the joint grounding method as shown in the figure below (2).

Other Other , i PC equipment PC equipment is, I Class 3 | ae = grounding, = = (1) Independent grounding = (2) Joint grounding (3) Joint grounding . Best ... Good . . Not allowed 5-9

IB (NA) 66058-A

Page 37 read from a scan by OCR; it may hold reading errors

5. LOADING AND INSTALLATION

MELSEC-Al

(d) Use 2mm? (0.0031’sq.) (AWG #14) or thicker grounding wire. Grounding point should be as near as possible to the PC to minimize the distance of grounding cable.

(e) Should incorrect operation occur due to grounding, dis-connect one or both of the LG and FG terminals of base units from the grounding.

5.2.2 Wiring to unit terminals

This section explains the wiring of power lines and grounding lines to the main and extension bases.

(1) AOJ2 o - 100V/110V AC, _ - _ - _o AC |

POINT |

1.

Use the thickest possible (max.. 2mm? (0.0031'sq.)) wires for the 100V/200V AC and 24V DC power cables. Be sure to twist these wires starting at the connection ter- minals. To prevent short-circuit should any screws loosen, use solderless terminals with insulation sleeves.

When the LG terminals and FG terminals are connected, be sure to ground the wires. Do not connect the LG terminals and FG ter- minals to anything other than ground. If LG terminals and FG terminals are connected without grounding the wires, the PC may be susceptible to noise, also since the LG ter- minals have potential, the operator may get an electric shock when touching metal parts.

AOJ2CPU Unit

100V/200V AC

SHORT 100V AC, HO, Sto

(9)

ie]

We) +40 ]124G

INPUT LG ed, - - - - -£0 |FG Seen]

© }+24V DC

Connect to 24V DC terminal of unit which ra requires 24V DC inside the 1/O unit.

1/0 Unit (AQJ2-E 2867} }, ! i ! 1 [ 1 I 1 i] I I 1 I

1-0 |] FG

Extension base (A65B) AG1P 1/0

INPUT PPPS OI 100V/200V AC

Lo C44] SHORT 100V AC OL SHORT 200V AC Grounding LG line FG => Grounding 5-10

IB (NA) 66058-A

Page 38 read from a scan by OCR; it may hold reading errors

5, LOADING AND INSTALLATION /MELSEC_AA

(2) AOQJ2-DC24

POINT |

1.

Use the thickest possible (max. 2mm? (0.0031''sq.)) wires for the 100V/200V AC and 24V DC power cables. Be sure to twist these wires starting at the connection ter- minals. To prevent short-circuit should any screws loosen, use solderless terminals with insulation sleeves.

When the LG terminals and FG terminals are connected, be sure to ground the wires. Do not connect the LG terminals and FG ter- minals to anything other than ground. If LG terminals and FG terminals are connected without grounding the wires, the PC may be susceptible to noise, also since the LG ter- minals have potential, the operator may get an electric shock when touching metal parts.

* ., .The power supply used to supply 24V DC to both the AQJ2-DC24 and I/O unit must satisfy the operating voltage ranges of the AOJ2-DC24 and I/O unit.

Fuse p-----

5-11

LowrTad

Grounding line

A0J2-DC24

‘a

2 a z

Le | o°O aa

29g oo

&S iu Tf

S - - 0, e)

o

°o

°

°o

1/O Unit (AQJ2-E2872) ! 1 ! 1 ' I t t I I I mr Lat) © _J}FG 1 = + Grounding

IB (NA) 66058-D