Page 85
5. POWER SUPPLY MODULE 5. 5.1
MELSEC-A
POWER SUPPLY MODULE Specifications (1)
Table 5.1 shows the specifications of the power supply modules.
Table 5.1 Power supply modules specifications Item
Specifications A1S61P
A1S62P
Base loading slot
Power supply module loading slot
Rated input voltage
100 to 120 V AC + 10 %/-15 % (85 to 132 V AC)
24 V DC (+ 30 %/- 35 %)
200 to 240 V AC + 10 %/-15 % (170 to 264 V AC)
(15.6 to 31.2 V DC)
50/60 Hz ± 3 %
Rated input frequency Input voltage distortion factor
Within 5 % (See Section 8.8)
Max. input apparent power
Overcurrent protection Overvoltage protection
41 Ω
105 V A
Inrush current Rated output current
A1S63P
20 A 8 ms or lower
81 A 1 ms or lower
5 V DC
5A
3A
24 V DC ± 10 %
0.6 A
5A
5 V DC
5.5 A or higher
3.3 A or higher
5.5 A or higher
24 V DC
0.66 A or higher
5 V DC
5.5 to 6.5 V
24 V DC
Efficiency
65 % or higher
Allowable momentary power failure time *3 Dielectric withstand voltage
20 ms or lower
1 ms or lower
Between primary and 5 V DC
1500 V AC *1
1500 V AC *1
500 V AC
Between primary and 24 V DC
1500 V AC *1
5 M Ω or higher at insulation resistance tester
Insulation resistor
Noise durability
Noise voltage 500 Vp-p, Noise width 1 µs, Noise frequency 25 to 60 Hz (noise simulator condition)
Noise voltage 1500 Vp-p, Noise width 1 µs, Noise frequency 25 to 60 Hz (noise simulator condition)
Power indication
Power LED indication (light at the time of output of 5 V DC)
Terminal screw size
M3.5 × 7
Applicable wire size
0.75 to 2 mm (AWG 18 to 14)
2
Applicable solderless terminal
RAV 1.25 to 3.5, RAV 2 to 3.5
Applicable tightening torque
59 to 88 N·cm (6 to 9 kg·cm)
External dimension [mm (in.)]
130 × 55 × 93.6 (5.12 × 2.17 × 3.69)
Weight [kg (lb.)]
0.53 (1.17)
0.55 (1.21)
0.5 (1.1)
*1: Overcurrent protection The overcurrent protection device shuts off the 5 V, 24 V DC circuit and stops the system if the current flowing in the circuit exceeds the specified value. When this device is activated, the power supply module LED is switched OFF or dimly lit. If this happens, eliminate the cause of the overcurrent and start up the system again. *2: Overvoltage protection The overvoltage protection device shuts off the 5 V DC circuit and stops the system if a voltage of 5.5 to 6.5 V is applied to the circuit. When this device is activated, the power supply module LED is switched OFF. If this happens, switch the input power OFF, then ON to restart the system. The power supply module must be changed if the system is not booted and the LED remains OFF.
5-1
Page 86
5. POWER SUPPLY MODULE
A1S61PEU
MELSEC-A
A1S62PEU
A1S61PN
200 to 240 V AC (10 %/- 15 %) (170 to 264 V AC)
A1S62PN
100 to 240 V AC (+ 10 %/-15 %) (85 to 264 V AC) 50/60 Hz ± 5 % 105 V A
40 A 8 ms or lower
20 A 8 ms or lower
5A
3A
5A
3A
0.6 A
0.6 A
5.5 A or higher
3.3 A or higher
5.5 A or higher
3.3 A or higher
0.66 A or higher
0.66 A or higher
20 ms or higher 1780 V AC
1780 V AC
1780 V AC
5 M Ω or higher at insulation resistance tester
AC across input/LG and output/FG 2830 V AC rms/3 cycle (2000 m (6562 ft.)) AC across input/LG and output/FG5 M Ω or higher, measures with a 500 V DC insulation resistance tester
(1) Noise voltage 1500 Vp-p, Noise width 1 µs, Noise frequency 25 to 60 Hz (noise simulator condition) (2) Noise voltage IEC801-4, 2 kV
RAV 1.25 to 3.5, RAV 2 to 3.5
RAV 1.25 to 4, RAV 2 to 4
59 to 88 N·cm (6 to 9 kg·cm)
83 to 113 N·cm (8.5 to 11.5 kg·cm)
130 × 55 × 93.6 (5.12 × 2.17 × 3.69)
130 × 54.5 × 93.6 (5.12 × 2.15 × 3.69)
0.53 (1.17)
0.55 (1.21)
0.60 (1.32)
*3: Allowable momentary power interruption time This value indicates the momentary power interruption time allowed for the PC CPU and varies according to the power supply module used with the PC CPU module. The allowable momentary power interruption time for a system in which an A1S63P is used is defined as starting when the primary power supply of the 24 V DC stabilized power supply of the A1S63P is turned OFF and lasting until the 24 V DC becomes less than the specified voltage (15.6 V DC). *4: A1S61PEU and A1S62PEU comply with EN61010-1 and safety aspects of IEC-1131-2 to meet the Low Voltage Directive which will be mandatory from the 1st of January 1997. *5: Do not apply over 400 Voltage between AC and LG as the Varistor is installed between the AC and LG.
5-2
Page 87
5. POWER SUPPLY MODULE (2)
MELSEC-A
Performance specifications for the A1SJHCPU built-in power supply.
Table 5.2 Performance specifications for the A1SJHCPU built -in power supply Type
A1SJHCPU
Item
Input power supply
% 100-120 V AC ±10 15 % (85 to 132 V AC) % 500-240 V AC ±10 15 % (170 to 264 V AC)
Input frequency
50/60 Hz ± 3 Hz
Input voltage distortion factor
Within 5 % (See Section 8.8)
Input maximum apparent power
100 V A
Rush current
20 A 8 msec or less
Rated output
5 V DC 3 A
Overcurrent protection *1
3.3 A or over
Overvoltage protection
Not provided
Efficiency
65 % or over
Power supply indication
POWER LED indicator
Terminal screw size
M3.5 × 8
Applicable solderless terminal
0.3 to 2 mm
2
Applicable solderless terminal
RAV 1.25-3.5, RAV 2-3.5
Allowable momentary power failure
20 msec or less (100 V AC or over)
POINT *1 : Overcurrent protection When a current larger than the specification value flows through the 5 V DC circuit, the overcurrent protection device cuts off the circuit and stops the system. The POWER LED turns off or lights dimly due to the voltage drop. If this device operated, remove causes of failures such current capacity shortage and short-circuit and restart the system.
5-3
Page 88
5. POWER SUPPLY MODULE 5.1.1
MELSEC-A
Selection of the power supply module Select the power supply module according to the total current consumption of I/O modules, special function modules and peripheral devices supplied by the power supply module. When an A1S52B(S1), A1S55B(S1), A1S58B(S1), A52B, A55B or A58B is used, the power is supplied from the power supply module of the main base unit. This point should also be taken into consideration. See Section 2.3 for details of the 5 V DC current consumptions of I/O modules, special function modules, and peripheral devices.
Power supply module
CPU I/O modules A1SX10, A1SY10, etc. Special funcntion modules A1SD61, A1SD71-S2, etc. Peripheral devices A8PUE, A6WU, etc.
(1)
* Peripheral device AD71TU * Take the current consumption of the peripheral device to be connected to the special function module into consideration. When an AD71TU is connected to an A1SD71-S2, the current consumption of the AD71TU must be counted in.
Power supply module when an extension base A1S52B(S1), A1S55B(S1), A1S58B(S1), A52B, A55B or A58B is used. When an extension base A1S52B(S1), A1S55B(S1), A1S58B(S1), A52B, A55B or A58B is used, the 5 V DC is supplied from the power supply module of the main base unit through the extension cable. Note the following points regarding the use of an extension base from among A1S52B(S1), A1S55B(S1), A1S58B(S1), A52B, A55B and A58B : (a)
Select a power supply module for the main base unit whose 5 V DC capacity can cover the 5 V DC current consumption of the A1S52B(S1), A1S55B(S1), A1S58B(S1), A52B, A55B or A58B. [Example] When the 5 V DC current consumption by the main base unit is 3 A and that by the A1S55B(S1) is 1 A, the power supply module installed at the main base unit must be A61P (5 V DC, 5 A).
(b)
Since the power is supplied to the A1S52B(S1), A1S55B(S1), A1S58B(S1), A52B, A55B or A58B through the extension cable, some voltage drop occurs in the cable. It is necessary to select a power supply module and length of cable which can provide 4.75 V DC or more at the receiving end. For details of voltage drop and other information, see Section 6.1.3 "Application standards for extension base units".
5-4
Page 89
5. POWER SUPPLY MODULE 5.2
MELSEC-A
Names of Parts and Settings The following gives the names and description of the parts of the power supply modules : [12]
[12] MELSECA1S61P
MELSECA1S62P
[1]
POWER
[1]
POWER
MITSUBISHI
MITSUBISHI
[11]
[11] INPUT AC85 –132V AC170–264V 50/60Hz
OUTPUT DC 5V 5A
INPUT AC85 –132V AC170–264V 50/60Hz
OUTPUT DC 5V 5A DC24V0.6A
+24V
[2]
24G
[3]
[3]
FG SHORT AC100V
[4]
FG SHORT AC100V
[4]
OPEN AC200V
[5]
OPEN AC200V
[5]
LG INPUT
[6]
LG INPUT
[6]
AC100/200V
AC100/200V
[10]
[10] (1) A1S61P
(2) A1S62P
[12] MELSECA1S63P
[1]
POWER
MITSUBISHI
[11] INPUT DC15.6 –31.2V
OUTPUT DC 5V 5A
NC NC
[3]
FG
[5]
LG
[7]
+24V INPUT 24G
[10] (3) A1S63P
5-5
Page 90
5. POWER SUPPLY MODULE
MELSEC-A
[12]
[12] MELSECA1S61PEU
MELSECA1S62PEU
[1]
POWER
[1]
POWER
MITSUBISHI
MITSUBISHI
[11]
[11] INPUT 200–240VAC 105VA 50/60Hz
OUTPUT 5VDC 5A
INPUT 200–240VAC 105VA 50/60Hz
OUTPUT 5VDC 3A 24VDC 0.6A
+24V
[2]
24G
[3] [4]
[3] [4]
(FG) (LG)
INPUT
[8]
(FG) (LG)
INPUT
[8]
240VAC
240VAC
A1S61PEU
A1S62PEU
[10]
[10] (4) A1S61PEU
(5) A1S62PEU
[12]
[12] MELSECA1S61PN
MELSECA1S62PN
[1]
POWER
[1]
POWER
MITSUBISHI
MITSUBISHI
[11]
[11] INPUT 100–240VAC 105VA 50/60Hz
OUTPUT 5VDC 5A
INPUT 100–240VAC 105VA 50/60Hz NC
OUTPUT 5VDC 3A 24VDC 0.6A
+24V
[2]
NC
24G
[3]
(FG)
[3]
(FG)
[4]
(LG)
[4]
(LG)
INPUT
[9]
INPUT
[9]
100–240VAC
100–240VAC A1S61PN
A1S62PN
[10]
[10] (6) A1S61PN
(7) A1S62PN
No.
Name
[1]
POWER LED
The indicator LED for the 5 V DC power.
Description
[2]
24 V and 24 G terminals
Used to supply 24 V DC to inside the output module (using external wiring).
[3]
FG terminal
The grounding terminal connected to the shield pattern of the printed circuit board.
5-6
Page 91
5. POWER SUPPLY MODULE
No.
MELSEC-A
Name
Description Either a 100 V AC or 200 V AC power supply can be connected: when using 100 V AC, short the two input voltage terminals with the jumper supplied as an accessory; to use 200 V AC, leave these terminals open. The jumper is not attached to the module when shipment. It is packed in a bag together with the module. < Setting when the power supply voltage is 100 V AC >
[4]
Input voltage select terminals
FG
Short using the jumper provided as an accessory
SHORT 100VAC OPEN 200VAC
LG
INPUT 100/200VAC
[5]
LG terminal
Grounding for the power supply filter. The potential of A1S61P or A1S62P terminal is 1/2 of the input voltage.
[6]
Power supply input terminals
Used to connect a 100 V AC or 200 V AC power supply.
[7]
Power supply input terminals
Used to connect a 24 V DC power supply.
[8]
Power supply input terminals
Used to connect a 200 V AC power supply.
[9]
Power supply input terminals
Used to connect 100 V AC to 200 V AC power supply.
[10] Terminal screw
M3.5 × 7
[11] Terminal cover
The protective cover of the terminal block.
[12] Module fixing screw
Used to fix the module to the base unit. (M4 screw, tightening torque : 59 to 88 N·cm {6 to 9 kg·cm})
POINT (1)
If the setting differs from the supply line voltage, the following results will occur. Do not make the wrong setting. Supply line voltage 100 V AC
200 V AC
Setting to 100 V AC (Short the input voltage select terminals.)
The power supply module is damaged. (The CPU is not damaged.)
Setting to 100 V AC (Open the input voltage select terminals.)
No error occurs in the module. However, the CPU does not operate.
(2)
Do not cable to the unused terminals such as FG and LG on the terminal block (terminals whose name is not printed on the terminal cover).
(3)
Be sure to ground the terminal
5-7
LG to the protective ground conductor.