The text of a manual · part 15 of 29

AnS(H) CPU User's Manual: 8. LOADING AND INSTALLATION, pages 109 to 116

Pages 109 to 116 of 242, from AnS(H) CPU User's Manual

The original document is the PDF (3.1 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Mitsubishi A1S38

Page 109

8. LOADING AND INSTALLATION 8.

MELSEC-A

LOADING AND INSTALLATION This chapter describes the procedure for loading and installation and gives relevant precautions to ensure that the system performs with high reliability and that its functions are used to best effect.

8.1

Safety Consideration When the power to the system is turned ON or OFF, the process output may not perform normally at times due to the difference between the delay time and the rise time of the power supply of the PC CPU main module and the external power supply (especially DC). Also, if there is an error in the external power supply, the output process may malfunction. For example, if the power supply to the PC is switched on after switching on the external power supply for the sequence program operation at a DC output module, the DC output module may temporarily output erroneous signals when the power to the PC is switched on. A circuit that allows the power to the PC to be switched on first must therefore be provided. In addition, if there is an abnormality in the external power supply or trouble in the PC, this could cause malfunction. To (a) prevent erroneous operation of the entire system, and (b) ensure safety, prepare circuits (such as an emergency stop circuit, protection circuit, and interlock circuit) that prevent machine damage and/or accidents due to erroneous operation of peripheral devices. An example system design circuit based on this concept is shown on the following page.

POINT Some types of AnS series output module detect a blown fuse error as soon as the external power supply is turned OFF. In the example circuit illustrated on the next page, since the start-up of the AnSHCPU takes place earlier than the rise of the external power supply to the output module, a blown fuse error is detected. To solve this problem, the system is designed to keep the M9084 ON until the external power supply rises so as not to check for blown fuses. (When M9084 is ON, the I/O module comparison and battery checks are not performed.)

8-1

Page 110

8. LOADING AND INSTALLATION (1)

MELSEC-A

System design circuit example

ALL AC

Mixed AC and DC

POWER

POWER

TRANSFORMER TRANSFORMER

TRANSFORMER

FUSE

FUSE

FUSE

CPU M9006

FUSE

FUSE CPU M9006

Ym M9039

Ym

DC POWER SUPPLY

Yn M9039

*5

Yn

Y1

XM

(-)

*6

(+)

XM

M9084 PROGRAM

TM *1

TM M9084

START SW

FUSE

TM

RA1 MC

FUSE

MC1 N0 M10

MC N0 START

STOP SW INPUT MPDULE RA2 XM

M10

FUSE *1

PROGRAM

RA1 MC MC

STOP SW INPUT MODULE

*2

OUTPUT MODULE

RA2

XM

Ym *3

L Yn

OUTPUT MODULE

RA1

MC

L Yn

OUTPUT MODULE

RA1

OUTPUT MODULE

*4 *4

MC

MC2 MC1 MC1

RA2

MC2 Y1

MC2

*8

MC1

RA2 MC1

MC2

*8

The power-ON procedure is as follows : For AC 1) Set the CPU to RUN. 2) Switch ON the power. 3) Turn ON the start switch. 4) When the magnetic contactor (MC) comes in, the output equipment is powered and may be driven by the program.

*1 : RUN/STOP circuit interlocked with RA1 (run *7 monitor relay) *2 : Low battery alarm *3 : RA1 switched ON by M9039 (run monitor relay) MC *4 : Power to output equipment switched OFF when the STOP signal is *4 given. *5 : Input switched when power supply established. *6 : Set time for DC power Voltage relay is supply to be established. recommended *7 : ON when run by M9039 *8 : Interlock circuits as necessary. *2

Ym

MC

For AC/DC Set the CPU to RUN. Switch ON the power. Turn ON the start switch. When DC power is established, RA2 comes ON. Timer (TM) times out after the DC power reaches 100 %. (The TM set value should be the period of time from when RA2 comes ON to the establishment of 100 % DC voltage. Set this value to approximately 0.5 seconds.) 6) When the magnetic contactor (MC) comes in, the output equipment is powered and may be driven by the program. (If a voltage relay is used at RA2, no timer (TM) is required in the program.) 1) 2) 3) 4) 5)

8-2

Page 111

8. LOADING AND INSTALLATION (2)

MELSEC-A

Fail-safe measures against PC failures Problems with the CPU or memory can be detected by the self-diagnosis function. However, problems with the I/O control area may not be detected by the CPU. If such a problem arises, all I/O points turn ON or OFF depending on the nature of the problem, and it may not be possible to maintain normal operating conditions and operating safety. Although Mitsubishi PCs are manufactured under strict quality control, they may fail or operate abnormally due to unspecifiable reasons. To prevent the abnormal operation of the whole system, machine breakdown, and accidents, build a fail-safe circuit outside the PC. The following is an example of a fail-safe circuit.

ON delay timer Internal program Y00

T1

1 sec

OFF delay timer

*2

M9032 Y00

T2

1 sec MC

External load

Y00

Y01

L to to

Y0F

L

24 V 0.5 sec

0.5 sec

-

+

0V 24 V DC CPU module

Output module *1 T1

T2 MC

*1 : Y00 repeats turning ON and then OFF at 0.5 second intervals. Use a nocontact output module (transistor in the example shown above). *2 : If an OFF delay timer (especially a miniature timer) is not available, use ON delay timers to make a fail-safe circuit as shown on the next page.

8-3

Page 112

8. LOADING AND INSTALLATION

MELSEC-A

A fail-safe circuit built with ON delay timers

ON delay timer Internal program T1

Y00

1 sec

*1 M1

M9032 Y00

ON delay timer M1 T2

ON delay timer

1 sec

M1 M2 M2

T2

Y00 External load 0.5 sec

0.5 sec

Y01

L to to

Y0F

L

MC

24 V -

+

0V 24 V DC CPU module

Output module T1

M2 MC

*1 : Use a solid-state relay for the M1 relay.

8-4

Page 113

8. LOADING AND INSTALLATION 8.2

MELSEC-A

Installation Environment Never install the AnSHCPU system in the following environments :

8.3

(1)

Locations where the ambient temperature is outside the range of 0 to 55 °C.

(2)

Locations where the ambient humidity is outside the range of 10 to 90 % RH.

(3)

Locations where dew condensation takes place due to sudden temperature changes.

(4)

Locations where there are corrosive and/or combustible gasses.

(5)

Locations where there is a high level of conductive powder (such as dust and iron filings, oil mist, salt, and organic solvents).

(6)

Locations exposed to the direct rays of the sun.

(7)

Locations where strong power and magnetic fields are generated.

(8)

Locations where vibration and shock are directly transmitted to the main module.

Calculation of Heat Generated by the Programmable Controller System The operating ambient temperature of the PC must be kept below 55 °C. In order to plan a heat dissipating design for the panel that houses the equipment, the average power consumption (heat generation) of the devices and equipment housed in the panel must be known. Therefore, the method for determining the average power consumption of an AnSHCPU system is described here. Calculate the temperature rise inside the panel from the power consumption. Average power consumption Power is consumed by the following PC areas :

I5 V AC power supply

Power supply module

5 V DC line

PC CPU module

I24 V External 24 V DC power supply

24 V DC line

Output module

Input module

Special fucntion module

Relay transistor

Input current (IIN) × E

Power supply

Input power (IIN)

Output current (lOUT) × Vdrop Output power (IOUT) AC

DC

8-5

AC

AC E

LOAD DC

DC

Page 114

8. LOADING AND INSTALLATION (1)

MELSEC-A

Power consumption of a power supply module Approximately 70 % of the power supply module current is converted into power and 30 % of that 70 % is dissipated as heat, i.e., 3/7 of the output power is actually used. Wpw = 3 {(I5V × 5) + (I24V × 24)} (W) 7 Where, I5V = V DC logic circuit current consumption of each module. I24V = current consumption of the output modules (with an average number of points switched ON) ...(Not for 24 V DC input power supply modules)

(2)

Total 5 V DC power consumption 5 V DC is supplied to each module via the base plate, which powers the logic circuitry. W5V = I5V × 5 (W)

(3)

Total 24 V DC output module power consumption (with an average number of points switched ON) 24 V DC is supplied to drive output devices. W24V = I24V × 24 (W)

(4)

Power consumption of output circuits (with an average number of points switched ON) WOUT = IOUT × Vdrop × average number of outputs on at one time (W) Where, IOUT = output current (actual operating current) (A) Vdrop = voltage dropped across each output load (V)

(5)

Power consumption of input circuits (with an average number of points switched ON) WIN = IIN × E × average number of inputs on at one time (W) Where, IIN E

= input current (effective value for AC) (A) = input voltage (actual operating voltage) (V)

8-6

Page 115

8. LOADING AND INSTALLATION (6)

MELSEC-A

Power consumption of the special function module power supply is expressed as : Ws = I5V × 5 + I24V × 24 + I100V × 100 (W) The sum of the above values is the power consumption of the entire PC system. W = WPW + W5V + W24V + WOUT +WIN + WS (W) Further calculations are necessary to work out the power dissipated by the other equipment in the panel. Generally, the temperature rise in the panel is expressed as : T=

W UA

(°C)

Where, W = power consumption of the entire PC system (obtained as shown above) 2

A = panel inside surface area (m ) U = 6 (if the panel temperature is controlled by a fan, etc.) 4 (if the panel air is not circulated) POINT If the temperature rise inside the panel exceeds the stipulated range, you are recommended to install a heat exchanger in the panel to lower the temperature. If an ordinary ventilation fan is used, dust will be sucked in along with the air from outside the panel and this may affect the performance of the PC.

8-7

Page 116

8. LOADING AND INSTALLATION 8.4

MELSEC-A

Module Mounting This section gives the mounting instructions for the main base unit and extension base units.

8.4.1

Mounting instructions The instructions for mounting the PC to a panel, etc. are presented below : (1)

To improve ventilation and facilitate the replacement of the module, provide 30 mm (1.18 in.) or more of clearance around the PC. However, when an extension base unit of one of models A52B, A55B, A58B, A62B, A65B, and A68B is used, allow a clearance of 80 mm (3.15 in.) or more between the top face of the module and the surface of a structure or component.

(2)

Do not mount the base unit vertically or horizontally since this will obstruct ventilation.

(3)

Ensure that the base unit mounting surface is uniform to prevent strain. If excessive force is applied to the printed circuit boards, this will result in incorrect operation. Therefore, mount the base unit on a flat surface.

(4)

Avoid mounting the base unit close to vibration sources, such as large magnetic contactors and no-fuse breakers, install the base unit in another panel or distance the base unit from the vibration source.

(5)

Provide a wiring duct as necessary. However, if the dimensions from the top and bottom of the PC are less than those shown in Fig. 8.1, note the following points : (a)

When the duct is located above the PC, the height of the duct should be 50 mm (1.97 in.) or less to allow for sufficient ventilation. Between the duct and the top of the PC, provide a sufficient distance to allow the cable to be removed by opening the cable connector fixing the lever. If the lever at the top of the module cannot be opened, it will not be possible to replace the module.

(b)

(6)

If a duct is built under the PC, provide a clearance between the bottom surface of the PC and the surface of the duct so that the input power cable (100/200 V AC) of the power supply module and the I/O cables and the cable for 12/24 V DC of I/O modules are not affected or bent.

If an equipment which generates noise or heat is positioned in front of the PC (i.e, mounted on the back side of a panel door), allow a clearance of 100 mm (3.94 in.) or more between the PC and the equipment. Also allow a clearance of 50 mm (1.97 in.) or more between the right/left side of a base unit and this equipment.

8-8