AnS(H) CPU User's Manual: 8. LOADING AND INSTALLATION, pages 117 to 124
Pages 117 to 124 of 242, from AnS(H) CPU User's Manual
The original document is the PDF (3.1 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Mitsubishi A1S38
Page 117
8. LOADING AND INSTALLATION 8.4.2
MELSEC-A
Installation This section explains how to mount main and extension base units. Indicates the panel top, wiring duct, or any assembly. Main base
Extension base
30 mm (1.17 in.) or more
30 mm (1.17 in.) or more
Fig. 8.1 Parallel mounting Indicates the panel top, wiring duct, or any assembly.
30 mm (1.17 in.) or more
Main base
Main base
30 mm (1.17 in.) or more 30 mm (1.17 in.) or more
Extension base (A5[ ]B, A6[ ]B)
30 mm (1.17 in.) or more
Extension base (A5[ ]B, A6[ ]B)
Duct (max. length 50 mm (1.97 in.))
80 mm (3.15 in.) or more 30 mm (1.17 in.) or more
Fig. 8.2 Serial mounting
Panel, etc.
Door PC Contactor, relay, etc. 100 mm (3.94 in.) or more
Fig. 8.3 Minimum front clearance with panel door
Fig. 8.4 Vertical mounting (not allowed)
8-9
Fig. 8.5 horizontal mounting (not allowed)
Page 118
8. LOADING AND INSTALLATION 8.5
MELSEC-A
Installation and Removal of Module This section explains the mounting and removal of the I/O module and special function module, etc., to and from the base module. (1)
Module mounting The module mounting procedure is as follows.
Insert the module mounting hook into the module mounting hole in the base unit.
Base unit Module Module connector
Install the module on the base unit by pushing the top forward.
Make sure the hook is securely inserted in the module mounting hole in the base unit. Then, secure the module with the module mounting screw.
Module mounting hook Module mounting hole
End
POINT (1)
(2)
When securing the module, be sure to insert the module mounting hook into the module mounting hole. If the module is forcibly secured without insertion, the module's connector or the module itself may be damaged. Always turn the power supply OFF before mounting or removing any module.
8 - 10
Base unit
Module mounting screw
Module
Page 119
8. LOADING AND INSTALLATION (2)
MELSEC-A
Module removal The module removal procedure is as follows.
Base unit
Remove the module mounting screw. Then, while pushing the hook latch, pull the module toward you.
Module connector
Lift upwards and remove the module hook from the module mounting hole.
Module
End Module mounting hole
POINT (1)
(2)
When removing the module, be sure to remove the module mounting screw first and then remove the module mounting hook from the module mounting hole. If the module is forcibly removed, the screw or module mounting hook will be damaged. Always turn the power supply OFF before mounting or removal.
8 - 11
Page 120
8. LOADING AND INSTALLATION 8.6
MELSEC-A
Installing and Removing the Dustproof Cover When an A1S52B(S1), A1S55B(S1), or A1S58B(S1) is used, it is necessary to mount the dustproof cover, which is supplied with the base, to the I/O module loaded at the left end to prevent foreign matter from entering the I/O module. If the dustproof cover is not mounted, foreign matter will enter the I/O module, resulting in malfunction. The following explains the installation and removal of the dustproof cover. (1)
Installation
I/O modul
Dustproof cover
To fit the dustproof cover to the I/O module, first insert it at the terminal side and then press it against the I/O module as shown in the figure. (2)
Removal
I/O modul
Notch
Dustproof cover
Fit the tip of a flat blade screwdriver into the notch on the left side of the dustproof cover. While keeping the screwdriver tip in the notch, gently move the screwdriver to the left (as shown above) until the cover snaps open.
8 - 12
Page 121
8. LOADING AND INSTALLATION 8.7
MELSEC-A
Wiring This section gives the wiring instructions for the system.
8.7.1
Wiring instructions
ø DANGER • Before biginning any installation or wiring work, make sure all phases of the power supply have been obstructed from the outside. Failure to completely shut off the power supply phases may cause electric shock and/or damage to the module. • When turning on the power or operating the module after installation or wiring work, be sure the module's terminal covers are correctly attached. Failure to attach the terminal covers may result in electric shock.
ù CAUTION • Be sure to ground the FG terminals and LG terminals to the protective ground conductor. Not doing so could result in electric shock or erroneous operation. • When wiring the PC, check the rated voltage and terminal layout of the wiring, and make sure the wiring is done correctly. Connecting a power supply that differs from the rated voltage or wiring it incorrectly may coups fire or breakdowns. • Tighten the terminal screws with the specified torque. If the terminal screws are loose, it may result in short circuits, fire or malfunction. If the terminal screws are tightened too much, it may damage the screws and the module result in short circuits, malfunction or cause the module to fall out. • Be careful not to let foreign matter such as filings or wire chips gear inside the module. These can cause fire, breakdowns and malfunction. • Perform correct pressure-welding, crimp-contact or soldering for connectors for the outside using the specified tools. See the User's Manual of the corresponding I/O module for tools required to perform pressure-welding and crimp-contact. Incorrect connection may cause short circuits, fire, or malfunction. • Do not bunch the control wires or communication cables with the main circuit or power wires, or install them close to each other. They should be installed 100 mm (3.94 in.) or more from each other. Failure to do so may result in nose that would cause malfunction.
8 - 13
Page 122
8. LOADING AND INSTALLATION
MELSEC-A
Precautions when wiring power supply cable are described. (1)
Wiring power supply (a)
Separate the PC's power supply line from the lines for I/O devices and power devices as shown below. When there is much noise, connect an insulation transformer. Main power suppl
PC power suppl
Insulation transformer
200 V AC
PC T1 I/O power supply I/O devices Main circuit device Main circuit device
(b)
100 V AC, 200 V AC and 24 V DC wires should be twisted as dense as possible. Connect the modules with the shortest distance. Also, to reduce the voltage drop to the minimum, use the thickest wires 2 possible (maximum 2 mm ).
(c)
As a countermeasure to power surge due to lightening, connect a surge absorber for lightening as shown below. PC/IO devices
AC
E2 Surge absorber for lightening
E1
POINT (1) Separate the ground of the surge absorber for lightening (E1) from that of the PC (E2). (2)
Select a surge absorber for lightening whose power supply voltage does no exceed the maximum allowable circuit voltage even at the time of maximum power supply voltage elevation.
8 - 14
Page 123
8. LOADING AND INSTALLATION (2)
MELSEC-A
Wiring of I/O equipment (a)
The applicable size of wire for connection to the terminal block 2 connector is 0.75 (18) to 1.25 mm (14 AWG). However, it is 2 recommended to use wires of 0.75 mm (18 AWG) for convenience.
(b)
Separate the input and output lines.
(c)
I/O signal wires must be at least 100 mm (3.94 in.) away from highvoltage and large-current main circuit wires.
(d)
If the I/O signal wires cannot be separated from the main circuit wires and power wires, ground at the PC side with batch-shielded cables. Under some conditions, it may be preferable to ground at the other side. PC
Shielded cable
Input RA Output
Shielded sheath
DC
(2)
(e)
If wiring has been done with piping, ground the piping.
(f)
Separate the 24 V DC I/O cables from the 100 V AC and 200 V AC cables.
(g)
If wiring over 200 m (0.12 mile) or longer distances, problems can be caused by leakage currents due to line capacity. Take corrective action as described in Section 10.4.
Grounding Grounding must be done in conformance with (a) to (d) below (a)
Ground the PC as independently as possible. Be sure to ground to the protective ground conductor (grounding resistance 100 Ω or less).
(b)
If independent grounding is impossible, use the joint grounding method as shown in the figure below (2).
Another equipment
PC
PC grounding
Another equipment
PC
Another equipment grounding
The protective ground conductor
(1) Independent grounding…Best
(c)
(2) Joint grounding…..Good
(3) Joint grounding…..Not allowed 2
Use a wire with a cross-sectional area of at least 2 mm for grounding. Make the grounding point as close to the PC as possible so that the grounding wire is not too long.
8 - 15
Page 124
8. LOADING AND INSTALLATION (d) 8.7.2
MELSEC-A
If any malfunction occur due to grounding, disconnect either or both of the LG and FG terminals of the base unit from the ground.
Wiring to module terminals This section explains the wiring of power lines and grounding lines to the main and extension bases . Main base unit (A1S38B) 100/110 V AC 200/220 V AC
A1S62PN
CPU
AC +24 V
Select the transformer by seeing Section 8.7.1 (C).
24G (FG)
Fuse
(LG) INPUT
AC DC
100-240 V AC
24 V DC Extension base unit (A1S58B-S1)
I/O
Connect to the 24 V DC terminals of an I/O module that requires 24 V DC internally.
I/O
5 V DC line
POINT (1)
(2)
(3)
8.8
2
Use the thickest possible (max. 2 mm (14 AWG)) wires for the 100 V/200 V and 24 V DC power cables. Be sure to twist these wires starting at the connection terminals. To prevent a short-circuit should any screws loosen, use solderless terminals with insulation sleeves. When the LG terminals and FG terminals are connected, be sure to ground the wires. Do not connect the LG terminals and FG terminals to anything other than ground. If LG terminals and FG terminals are connected without grounding the wires, the PC may be susceptible to noise. In addition, since the LG terminals have potential, the operator may receive an electric shock when touching metal parts.
FG Extension base unit (A1S68B-S1)
A1S61PN
I/O
100/110 V AC 200/220 V AC NC NC
5 V DC line
(FG) (LG) INPUT 100-240 V AC
Grounding wire Ground
A1S61PN and A1S62PN do not need to be switched as the are 100-240 V AC wide-range.
Precaution when Connecting the Uninterruptive Power Supply (UPS) Be sure of the following items when connecting the AnSHCPU system to the uninterruptive power supply (abbreviated as UPS hereafter) : Use a UPS which employs the constant inverter power supply method with 5 % or less voltage fluctuation. Do not use a UPS with the constant commercial power supply method.
8 - 16