AnS(H) CPU User's Manual: 9. EMC DIRECTIVE AND LOW-VOLTAGE INSTRUCTION

Pages 125 to 135 of 242, from AnS(H) CPU User's Manual

The original document is the PDF (3.1 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Mitsubishi A1S38

Page 125

9. EMC DIRECTIVE AND LOW-VOLTAGE INSTRUCTION 9.

EMC DIRECTIVE AND LOW-VOLTAGE INSTRUCTION

9.1

Requirements for Compliance to EMC Directive (89/336/EEC)

MELSEC-A

The EMC Directive (89/336/EEC) will become mandatory within Europe from January 1st 1996. The EMC directive in essence defines the amount of electromagnetic output a product is allowed to produce and how susceptible that product is to electromagnetic interference. Any manufacturer or importer of electrical/electronic apparatus must before releasing or selling products within Europe after that date have either a CE mark attached to their goods. Testing to comply with the directive is done by use of agreed European standards which define limits for radiated and mains conducted electromagnetic emissions from equipment, levels of immunity to radiated emissions, ability for equipment to cope with transient voltage surges and electro-static discharges. When installed in the specified manner this unit will be compliant with the relevant standards EN50081-2 and prEN50082-2 as applicable in the EMC directive. Failure to comply with these instructions could lead to impaired EMC performance of the equipment and as such Mitsubishi Electric Corporation can accept no liability for such actions.

9.1.1

EMC standards When the PC is installed following the directions given in this manual its EMC performance is compliant to the following standards and levels as required by the EMC directive.

Specifications

EN50081-2 : 1995 prEN50082-2 : 1991

EN50082-2 : 1995

Test Item

Test Description

Standard Values

EN55011 Radiated noise

Measure the electric wave released by the product.

30 M-230 M Hz QP : 30 dBµ V/m (30 m measurement) *1

EN55011 Conduction noise

Measure the noise released by the product to the power line.

150 K-500k Hz QP: 79 dB, Mean : 66 dB *1 500 K-30M Hz QP : 73 dB, Mean: 60 dB

IEC801-2 Static electricity immunity *2

Immunity test by applying static electricity to the module enclosure.

4 k V contact discharge 8 k V air discharge

IEC801-3 Radiated electromagnetic field *2

Immunity test by radiating an 10 V/m, 27-500 M Hz electric field to the product.

IEC801-4 First transient burst noise

Immunity test by applying burst noise to the power line 2 k V and signal cable.

EN61000-4-2 Static electricity immunity *2

Immunity test by applying static electricity to the module enclosure.

EN61000-4-4 First transient burst noise

Immunity test by applying burst noise to the power line 2 k V and signal cable., 2 k V

230 M-1000 M Hz QP : 37 dBµ V/m (30 m measurement)

4 k V contact discharge 8 k V air discharge

ENV50140 Radiated electromagnetic field AM modulation *2

Immunity test by radiating an 10 V/m, 80-1000 M Hz, 80 % AM modulation@1 k electric field to the product. Hz

ENV50204 Radiated electromagnetic field Pulse modulation *2

Immunity test by radiating an 10 V/m, 900 M Hz, 200 Hz pulse modulation, 50 % electric field to the product. duty

ENV50141 Conduction noise

Immunity test by inducting electromagnetic field to the power line signal cable.

9-1

10 Vrms, 0.15-80 M Hz, 80 % modulation@1 k Hz

Page 126

9. EMC DIRECTIVE AND LOW-VOLTAGE INSTRUCTION

MELSEC-A

(*1) QP: Quasi-peak value, Mean : Average value (*2) The PC is an open type device (device installed to another device) and must be installed in a conductive control box. The tests for the corresponding items were performed while the PC was installed to inside the control box. 9.1.2 9.1.2.1

Installation instructions for EMC Control cabinet When constructing a control cabinet where the PC system will be installed, the following instructions must be followed.

9.1.2.2

(1)

Use a conductive control cabinet.

(2)

When attaching the control cabinet's top plate or base plate, mask painting and weld so that good surface contact can be made between the cabinet and plate.

(3)

To ensure good electrical contact with the control cabinet, mask the paint on the installation bolts of the inner plate in the control cabinet so that contact between surfaces can be ensured over the widest possible area.

(4)

Earth the control cabinet with a thick wire so that a low impedance connection 2 to ground can be ensured even at high frequencies. (22 mm wire or thicker is recommended.)

(5)

Holes made in the control cabinet must be 10 cm (3.94 in.) diameter or less. If the holes are 10 cm (3.94 in.) or larger, radio frequency noise may be emitted.

(6)

Connect the door of cabinet to the main body with flat braided wires at as many points as possible so that a low impedance can be ensured even at high frequencies.

Connection of power and earth wires Earthing and power supply wires for the PC system must be connected as described below. (1)

Provide an earthing point near the power supply module. Earth the power supply's LG and FG terminals (LG : Line Ground, FG : Frame Ground) with the thickest and shortest wire possible. (The wire length must be 30 cm (11.18 in.) or shorter.) The LG and FG terminals function is to pass the noise generated in the PC system to the ground, so an impedance that is as low as possible must be ensured. As the wires are used to relieve the noise, the wire itself carries a large noise content and thus short wiring means that the wire is prevented from acting as an antenna.

Note) A long conductor will become a highly efficient antenna at high frequency.

9-2

Page 127

9. EMC DIRECTIVE AND LOW-VOLTAGE INSTRUCTION

9.1.2.3

MELSEC-A

(2)

The earth wire led from the earthing point must be twisted with the power supply wires. By twisting with the earthing wire, noise flowing from the power supply wires can be relieved to the earthing. However, if a filter is installed on the power supply wires, the wires and the earthing wire may not need to be twisted.

(3)

Except for A1S61PEU and A1S62PEU, short between FG and LG terminals by a short jumper wire.

Cables The cables led from the control cabinet contain a high frequency noise element and outside the control panel these cables act as antennae and radiate noise. The cables connected to input/output modules or special modules which leave the control panel must always be shielded cables. Mounting of a ferrite core on the cables is not required (excluding some models) but if a ferrite core is mounted, the noise radiated through the cable can be suppressed further. Use of a shielded cable is also effective for increasing the noise immunity level. The PC system's input/output and special function module provide a noise immunity level of equivalent to that stated in IEC801-4 : 2 k V when a shielded cable is used. If a shielded cable is not used or if the shield earthing treatment is not suitable even when used (See Section 9.1.2.4), the noise immunity level is less than 2 k V. Note) prEN50082-2 specifies the noise resistance level based on the signal wire application. Signals involved in process control : 2kV Signals not involved in process control : 1 k V The meaning of "involved in process control" is not defined in prEN50082-2. However, when the purposes of the EMC Directive are considered, the signals that could cause personal injury or risks in the facility if a malfunction occurs should be defined as "signals involved in process control". Thus, it is assumed that a high noise immunity level is required.

9-3

Page 128

9. EMC DIRECTIVE AND LOW-VOLTAGE INSTRUCTION 9.1.2.4

MELSEC-A

Shield earthing When a shield of the shielded cable is earthed to the cabinet body, please ensure that the shield contact with the body is over a large surface area. If the cabinet body is painted it will be necessary to remove paint from the contact area. All fastenings must be metallic and the shield and earthing contact must be made over the largest available surface area. If the contact surfaces are too uneven for optimal contact to be made either use washers to correct for surface inconsistencies or use an abrasive to level the surfaces. The following diagrams show examples of how to provide good surface contact of shield earthing by use of a cable clamp. Screw Clamp fitting

Shield section

Paint mask

(a) Peal the cable insulation off and expose the shield section.

Shielded cabl

(b) Sandwich the exposed shield section with the and earth to the control cabinet over a wide area.

Note) The method of earthing by soldering a wire onto the shield section of the shielded cable as shown below is not recommended. The high frequency impedance will increase and the shield will be ineffective.

Shielded cable Wire Crimp terminal

9.1.2.5

MELSECNET/II module The following requirements apply to A1SJ71AR21, A1SJ71BR11, AnNCPUR21, AnACPUR21. (1)

Always use a triaxial cable for the module. The radiated noise in the band of 30 M Hz or higher can be suppressed by using a triax cable. Earth the outer shield by the method described in Section 9.1.2.4.

Earth this section

(2)

Always mount a ferrite core onto the triaxial cable. Mount the ferrite core near the control cabinet outlet of each cable. Use of the TDK ZCAT3035 ferrite core is recommended.

9-4

Page 129

9. EMC DIRECTIVE AND LOW-VOLTAGE INSTRUCTION 9.1.2.6

MELSEC-A

Ethernet module (1)

Always earth the AUI cable connected to the A1SJ71E71-B5. The AUI is a shielded cable so remove the outer insulation and connect to earth the exposed shield section using as wide a surface area as possible in the manner shown below.

AUI cable Shield

Always use a triaxial cable for the coaxial cable connected to the A1SJ71E71B2. The earthing precautions are the same as Section 9.1.2.5.

(3)

For A1SJ71E71-B2/B5, always mount a ferrite core in addition to items (1) and (2) above. Use of the TDK ZCAT3035 ferrite core is recommended.

Positioning Modules (1)

When wiring with a 2 m (6.6 ft.) or less cable Ground the shield section of the external wiring cable with the cable clamp. (Ground the shield at the closest location to the A1SD75 external wiring connector.) Wire the external wiring cable to the drive unit and external device with the shortest distance. Install the drive unit in the same panel.

A1SD75 module

CPU module

External wiring connector

Power supply module

9.1.2.7

(2)

Cable clamp External wiring cable (within 2 m (6.56 ft.))

Drive uni

(2)

When wiring with cable that exceeds 2 m (6.6 ft.), but is 10 m (32.8 ft.) or less Ground the shield section of the external wiring cable with the cable clamp. (Ground the shield at the closest location to the AISD75 external wiring connector.) Install a ferrite core. Wire the external wiring cable to the drive unit and external device with the shortest distance.

9-5

Page 130

9. EMC DIRECTIVE AND LOW-VOLTAGE INSTRUCTION

MELSEC-A

AISD75 module

CPU module

Power supply module

External wiring connector Ferrite core Cable clamp

External wiring cable (2 m to 10 m (6.56 ft. to 32.81 ft.))

Drive unit

(3)

Ferrite core and cable clamp types and required quantities (a)

Cable clamp Type : AD75Ck (Mitsubishi Electric)

(b)

Ferrite core Type : ZCAT3035-1330 (TDK ferrite core)

(c)

Required quantity Cable length

9.1.2.8

Required Qty

Prepared part 1 axis

2 axes

3 axes

Within 2 m (6.6 ft.)

AD75CK

1

1

1

2m (6.6 ft.) to 10m (32.8 ft.)

AD75CK

1

1

1

ZCAT3035-1330

1

2

3

I/O and other communication cables Always earth the shield section of the I/O signal cables and other communication cables (RS-232-C, RS-422, etc.) in the same manner as described in Section 9.1.2.4 if the cables go outside of the control cabinet.

9.1.2.9

Power supply module The precautions required for each power supply module are described below. Always observe the items noted as precautions. Model

Precautions

A1S61P A1S62P A1S63P (*1)

Always mount one of the filters listed in Section 9.1.2.10 to the incoming power supply lines.

A1S61PEU A1S62PEU A1S61PN A1S62PN A1SJCPU-S3 A1SJHCPU

None

(*1)

Always ground the LG and FG terminals after short-circuiting them. If a sufficient filter circuitry is built into a 24 V DC external power supply module, the noise generated by A1S63P will be absorbed by that filter circuit, so a line filter may not be required.

9-6

Page 131

9. EMC DIRECTIVE AND LOW-VOLTAGE INSTRUCTION 9.1.2.10

MELSEC-A

Ferrite core A ferrite core is effective for reducing noise in the band of 30 M Hz to 100 M Hz. Mounting of a ferrite core is not necessary except for some particular models described in Section 9.1.2.5 and 9.1.2.6. However if further attenution of noise is necessary, mounting of a ferrite core on cables which radiate noise is recommended. When a ferrite core is mounted, mount the ferrite core just before the point where the cable goes outside of the cabinet. The ferrite will not be effective if the mounting position is not adequate.

Ferrite core

Ferrite core

Noise

Noise

(a) When there is a distance from the cable exit hole, the noise will jump over the ferrite, thus the effect will be halved.

9.1.2.11

(b) When mounted by the cable exit hole, the noise will not jump over the ferrite.

Noise filter (power supply line filter) The noise filter (power supply line filter) is a device effective to reduce conducted noise. Except some particular models described in Section 9.1.2.8, installation of a noise filter onto the power supply lines is not necessary. However conducted noise can be reduced if it is installed. (The noise filter is generally effective for reducing conducted noise in the band of 10 M Hz or less.) Usage of the following filters is recommended. Model name

FN343-3/01

FN660-6/06

ZHC2203-11

Manufacturer

SCHAFFNER

SCHAFFNER

TDK

Rated current

3A

6A

3A

Rated voltage

250 V

9-7

Page 132

9. EMC DIRECTIVE AND LOW-VOLTAGE INSTRUCTION

MELSEC-A

The precautions required when installing a noise filter are described below. (1)

Do not bundle the wires on the input side and output side of the noise filter. When bundled, the output side noise will be induced into the input side wires from which the noise was filtered. Input side (power supply side)

Input side (power supply side)

Introductio Filter

Filter Output side (device side)

(a) The noise will be included when the input and output wires are bundled.

(2)

9.2

Output side (device side)

(b) Separate and lay the input and output wires.

Earth the noise filter earthing terminal to the control cabinet with the shortest wire possible (approx. 10 cm (3.94 in.)).

Requirement to Conform to the Low-Voltage Instruction The low-voltage instruction, one of the European Instructions, is now regulated. The low-voltage instruction require each device which operates with power supply ranging from 50 V AC to 1000 V and 75 V DC to 1500 V to satisfy necessary safety items. In the Sections from 9.2.1 to 9.2.8, cautions on installation and wiring of the MELSEC-AnS series PC to conform to the low-voltage instruction regulation are described. We have put the maximum effort to develop this material based on the requirements and standards of the regulation that we have collected. However, compatibility of the devices which are fabricated according to the contents of this manual to the above regulation is not guaranteed. Each manufacturer who fabricates such device should make the final judgement about the application method of the low-voltage instruction and the product compatibility.

9.2.1

Standard applied for MELSEC-AnS The standard applied for MELSEC-AnS is EN61010-1 safety of devices used in measurement rooms, control rooms, or laboratories. For the modules which operate with the rated voltage of 50 V AC/75 V DC or above, we have developed new models that conform to the above standard. (See Appendix 4.) For the modules which operate with the rated voltage under 50 V AC/75 V DC, the conventional models can be used, because they are out of the low-voltage instruction application range.

9-8

Page 133

9. EMC DIRECTIVE AND LOW-VOLTAGE INSTRUCTION 9.2.2

MELSEC-A

Precautions when using the MELSEC-AnS series PC Module selection (1)

Power module For a power module with rated input voltage of 100/200 V AC, select a model in which the internal part between the first order and second order is intensively insulated, because it generates hazardous voltage (voltage of 42.4 V or more at the peak) area. (See Appendix 4.) For a power module with 24 V DC rated input, a conventional model can be used.

(2)

I/O module For I/O module with rated input voltage of 100/200 V AC, select a model in which the internal area between the first order and second order is intensively insulated, because it has hazardous voltage area. (See Appendix 4.) For I/O module with 24 V DC rated input, a conventional model can be used.

(3)

CPU module, memory cassette, base unit Conventional models can be used for these modules, because they only have a 5 V DC circuit inside.

(4)

Special module Conventional models can be used for the special modules including analog module, network module, and positioning module, because the rated voltage is 24 V DC or smaller.

(5)

Display device Use an A870GOT CE compatible model.

9.2.3

Power supply The insulation specification of the power module was designed assuming installation category II. Be sure to use the installation category II power supply to the PC. The installation category indicates the durability level against surge voltage generated by a thunderbolt. Category I has the lowest durability; category IV has the highest durability.

Category I

Category III

Category I

Category I

Figure 1. : Installation Category Category II indicates a power supply whose voltage has been reduced by two or more levels of isolating transformers from the public power distribution.

9-9

Page 134

9. EMC DIRECTIVE AND LOW-VOLTAGE INSTRUCTION 9.2.4

MELSEC-A

Control box Because the PC is an open device (a device designed to be stored within another module), be sure to use it after storing in the control box. (1)

Electrical shock prevention In order to prevent persons who are not familiar with the electric facility such as the operators from electric shocks, the control box must have the following functions :

(2)

(a)

The control box must be equipped with a lock so that only the personnel who has studied about the electric facility and have enough knowledge can open it.

(b)

The control box must have a structure which automatically stops the power supply when the box is opened.

Dustproof and waterproof features The control box also has the dustproof and waterproof functions. Insufficient dustproof and waterproof features lower the insulation withstand voltage, resulting in insulation destruction. The insulation in our PC is designed to cope with the pollution level 2, so use in an environment with pollustion level 2 or below. Pollution level 1 : Pollution level 2 :

Pollution level 3 :

Pollution level 4 :

An environment where the air is dry and conductive dust does not exist. An environment where conductive dust does not usually exist, but occasional temporary conductivity occurs due to the accumulated dust. Generally, this is the level for inside the control box equivalent to IP54 in a control room or on the floor of a typical factory. An environment where conductive dust exits and conductivity may be generated due to the accumulated dust. An environment for a typical factory floor. Continuous conductivity may occur due to rain, snow, etc. An outdoor environment.

As shown above, the PC can realize the pollution level 2 when stored in a control box equivalent to IP54. 9.2.5

Module installation (1)

Installing modules contiguously In AnS series PCs, the left side of each I/O module is left open. When installing an I/O module to the base, do not make any open slots between any two modules. If there is an open slot on the left side of a module with 100/200 V AC rating, the printed board which contains the hazardous voltage circuit becomes bare. When it is unavoidable to make an open slot, be sure to install the blank module (A1SG60). When using the A1S5οB expansion base with no power supply, attach the cover packaged with the expansion base to the side of the leftmost module.

9 - 10

Page 135

9. EMC DIRECTIVE AND LOW-VOLTAGE INSTRUCTION 9.2.6

MELSEC-A

Grounding There are two kinds of grounding terminals as shown below. Either grounding terminal must be used grounded. Be sure to ground the protective grounding for the safety reasons.

9.2.7

Protective grounding

:

Maintains the safety of the PC and improves the noise resistance.

Functional grounding

:

Improves the noise resistance.

External wiring (1)

24 V DC external power supply For special modules that require a 24 V DC I/O module or external power supply, use a model whose 24 V DC circuit is intensively insulated from the hazardous voltage circuit.

(2)

External devices When a device with a hazardous voltage circuit is externally connected to the PC, use a model whose circuit section of the interface to the PC is intensively insulated from the hazardous voltage circuit.

(3)

Intensive insulation Intensive insulation refers to the insulation with the dielectric withstand voltage shown in Table 2. Table 2 : Intensive Insulation Withstand Voltage (Installation Category II, source : IEC664) Rated voltage of hazardous voltage area

Surge withstand voltage (1.2/50 µs)

150 V AC or below

2500 V

300 V AC or below

4000 V

9 - 11