AnS(H) CPU User's Manual: 10. MAINTENANCE AND INSPECTION
Pages 136 to 139 of 242, from AnS(H) CPU User's Manual
The original document is the PDF (3.1 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Mitsubishi A1S38
Page 136
10. MAINTENANCE AND INSPECTION
MELSEC-A
10. MAINTENANCE AND INSPECTION This chapter describes items to be checked in daily and periodic maintenance and inspection in order to maintain the programmable controller in the normal and optimum condition. Daily Inspection Table 10.1 shows the inspection and items which are to be checked daily. Table 10.1 Daily inspection No.
Check item
Check point
Judgement
Corrective action
1
Base unit mounting conditions
Check for loose mounting screws and cover
The base unit should be securely mounted.
Retighten screws.
2
Mounting conditions of I/O module, etc.
Check if the module is disengaged and if the hook is securely engaged.
The hook should be securely engaged and the module should be positively mounted.
Securely engage the hook.
Check for loose terminal screws.
Screws should not be loose.
Retighten terminal screws
Check distance between Solderless terminals.
The proper clearance should be provided between Solderless terminals
Correct.
Check connectors of extension cable.
Connections should no be loose.
Retighten connector mounting screws.
"POWER" LED
Check that the LED is ON.
ON (OFF indicates an error.)
See Section 11.2.2
"RUN" LED
Check that the LED is ON during RUN.
ON (OFF or flashing indicates an error.)
See Sections 11.2.3 and 11.2.4
"ERROR" LED
Check that the LED is ON when an error occurred.
OFF (ON when an error occurred.)
See Sections 11.2.5 and 11.2.6
Input LED
Check that the LED turns ON and OFF.
ON when input is ON. OFF when input is OFF. (Display, other than above, indicates an error.)
See Sections 11.2.7
Output LED
Check that the LED turns ON and OFF.
On when output is ON. OFF when output is OFF. (Display, other than above, indicates an error.)
See Sections 11.2.7
3
4
Connecting conditions
CPU module indicator lamps
10.1
10 - 1
Page 137
10. MAINTENANCE AND INSPECTION Periodic Inspection
This section explains the inspection items which are to be checked every six months to one year. This inspection should also be performed when the equipment is moved or modified or the wiring is changed. Table 10.2 Periodic inspection
2
3
4
5
Check point
Ambient temperature Measure whit thermometer and hygrometer. Ambient Measure corrosive humidity gas.
Judgement 0 to 55 °C
10 to 90 % RH
Corrective action When PC is used inside a panel, the temperature in the panel is the ambient temperature.
There should be no corrosive gases.
Ambience
Line voltage check. Mounting conditions
1
Check item Ambient environment
No.
Connecting conditions
10.2
MELSEC-A
Measure voltage across 100/200 V AC terminal.
85 to 132 V AC
Change supply power.
170 to 264 V AC
Move the module.
The module should be mounted securely and positively.
Retighten screws.
Ingress of dust or foreign material
Visual check.
There should be no dust or foreign material in the vicinity of the PC.
Remove and clean.
Loose terminal screws
Retighten.
Connectors should not be loose.
Retighten.
Distances between Solderless terminals.
Visual check.
The proper clearance should be provided between Solderless terminals.
Correct.
Loose connector
Visual check.
Connectors should not be loose.
Retighten connector mounting screws.
Preventive maintenance
If battery capacity reduction is not indicated, change the battery when specified service life is exceeded.
Looseness, play
Battery
Check battery status by mounting special auxiliary relays M9006 and M9007.
10 - 2
Page 138
10. MAINTENANCE AND INSPECTION 10.3
MELSEC-A
Replacement of Battery M9006 or M9007 turns ON when the voltage of the battery for program backup and power interruption compensation falls. Even if this special relay turns ON, the contents of the program and the power interruption compensation function are not lost immediately. However, if the ON state is overlooked, the PC data contents may be lost. Special auxiliary relays M9006 and M9007 are switched ON to indicate that the battery has reached the life time (minimum) indicated in Table 10.3 and it must be replaced if continued use of the power interruption RAM and /or data backup is required. The following sections give the battery service life and the battery changing procedure.
10.3.1
Service life of battery Table 10.3 shows the service life of the battery. Table 10.3 Battery life Battery life
Battery life (Total power interruption time) [Hr] Guaranteed value (MIN)
Actual service value (TYP)
After M9006 or M9007 is turned ON
A1SJHCPU A1SHCPU A2SHCPU
4000
20000
100
A2SHCPU-S1
2200
12000
56
CPU model
*
The actual service value indicates a typical life time and the guaranteed value indicates the minimum life time.
Preventive maintenance is as follows : (1)
Even if the total power interruption time is less than the guaranteed value in the above table, change the battery after four to five years.
(2)
When the total power interruption time has exceeded the guaranteed value in the table above and M9006 has turned ON, change the battery.
10 - 3
Page 139
10. MAINTENANCE AND INSPECTION 10.3.2
MELSEC-A
Battery replacement procedure When the service life of the battery has expired, replace the battery using the following procedure : Even if the battery is removed, the memory is backed up by a capacitor for some time. However, if the replacement time exceeds the guaranteed value shown in the following table, the contents of the memory may be lost. Therefore, replace the battery as quickly as possible. Replacement of battery
Table 10.4 Backup time by capacitor Capacitor backup time (Minutes) Turn OFF the PC power supply.
Guaranteed value (MIN)
Actually applied value (TYP)
5
15
Open the cover on the front of the AnSCPU.
Remove the old battery from the holder and remove the lead from the lead clamp. Then, remove the lead connector from the connector.
Insert a new battery into the holder in the correct orientation and connect the lead wires to the connector. (Clamp the lead with the lead clamp.) (The red lead is positive, and the blue one negative.)
A1SHCPU
Close the cover on the front of the AnSCPU.
Battery connector
Turn ON the PC power supply.
Monitor M9006 and check ON/OFF.
OFF
ON Battery failure
End
10 - 4
A6BAT