11. TROUBLESHOOTING
MELSEC-A
11. TROUBLESHOOTING This chapter describes various procedures for troubleshooting, and corrective action. 11.1
Basic Troubleshooting System reliability depends not only on reliable equipment but also on short downtimes in the event of faults. The three basic points to be kept in mind in troubleshooting are : (1)
Visual checks Check the following points (a)
Machine motion (in the stopped and operating status)
(b)
Power ON or OFF
(c)
Status of I/O equipment
(d)
Condition of wiring (I/O wires, cables)
(e)
Display status of various indicators (such as the POWER LED, RUN LED, ERROR LED, and I/O LED)
(f)
Status of various setting switches (such as extension base and power interruption compensation)
After checking (a) to (f), connect the peripheral equipment and check the running status of the PC CPU and the program contents. (2)
Trouble check Observe any changes in the error condition when performing the following operations :
(3)
(a)
Set the RUN/STOP keyswitch to the STOP position.
(b)
Reset using the RUN/STOP keyswitch.
(c)
Turn the power ON and OFF.
Narrow down the possible causes of the trouble : Deduce where the fault lies, i.e : (a)
Inside or outside the PC CPU.
(b)
In the I/O module or another module.
(c)
In the sequence program.
11 - 1
Page 141
11. TROUBLESHOOTING 11.2
MELSEC-A
Troubleshooting This section explains the procedure for determining the cause of problems, errors, and corrective action to be taken in response to error codes.
11.2.1
Troubleshooting flowcharts The procedures for troubleshooting are given in the following flowcharts : Occurrence of error
See Section 11.2.2 See the flowchart used when the POWER LED goes OFF.
Is the POWER LED OFF?
Is the RUN LED OFF?
See Section 11.2.3 See the flowchart used when the RUN LED goes OFF.
Is the RUN LED flashing?
See Section 11.2.4 See the flowchart used when the RUN LED flashes.
Is the ERROR LED ON?
See Section 11.2.5 See the flowchart used when the ERROR LED Is lit.
Is the ERROR LED flashing?
See Section 11.2.6 See the flowchart used when the ERROR LED flashes.
I/O module does not operate properly.
See Section 11.2.7 See the flowchart used when the output load of the output module does not come ON.
Program cannot be written.
See Section 11.2.8 See the flowchart used when a program cannot be written to the PC CPU.
11 - 2
Page 142
11. TROUBLESHOOTING 11.2.2
MELSEC-A
Flowchart used when the POWER LED goes OFF POWER LED is OFF.
Is the power supply operating?
NO Correct the power supply.
YES
Is the line voltage 85 to 132 V AC or 170 to 264 V AC?
NO
NO
YES
Is the power supply module fixed to the base?
Overcurrent or overvoltage protection device activated?
YES
Set the Supply voltage to within the rated voltage.
NO
NO
YES
Does the POWER LED come ON?
Does the POWER LED come ON?
YES
Fix the power supply module correctly.
NO
Does the POWER LED come ON?
YES
YES (1) Eliminate the excess current. (2) Switch the input power OFF, then ON.
NO
NO
Does the POWER LED come ON?
YES
Consult your nearest Mitsubishi representative. End
11 - 3
Page 143
11. TROUBLESHOOTING 11.2.3
MELSEC-A
Flowchart used when the RUN LED goes OFF RUN LED goes OFF.
Is an error indicated on the peripheral?
YES
Take corrective action by referring to the error code list.
NO
Reset the AnSHCPU using the RUN/STOP keyswitch.
RUN LED goes ON.
RUN LED remains OFF.
(1) Due to defective PC parts or a connection failure. (2) Due to excessive noise.
In case of (1) In case of (2)
Move the RUN/STOP keyswitch on the AnSHCPU to STOP and write END to address 0 using a peripheral device.
Move the RUN/STOP key switch to RUN.
Consult your nearest Mitsubishi representative.
RUN LED dose not go ON.
RUN LED goes ON .
Software error.
Check program with the programmer and correct the program.
Connect a noise suppression circuit, such as CR, to the noise source.
11 - 4
Page 144
11. TROUBLESHOOTING 11.2.4
MELSEC-A
Flowchart used when the RUN LED flashes The following shows the corrective measures to take if the RUN LED flashes when the power is switched ON, when operation is started, or during operation. RUN LED flashes.
Hardware fault
Check the error using peripheral equipment. (See Section 11.3)
Consult your nearest Mitsubishi representative.
Reset the AnSCPU using the RUN/STOP keyswitch.
Correct the error. (See Section 11.3)
Set the RUN/STOP keyswitch to the RUN position.
Does the RUN LED come ON?
YES
End
11 - 5
NO
Page 145
11. TROUBLESHOOTING 11.2.5
MELSEC-A
Flowchart used when the ERROR LED is lit The following shows the corrective measures when the ERROR LED is lit in the RUN status. ERROR LED is lit.
NO Is M9008 ON?
YES
Hardware fault
Cause of the ERROR LED being lit.
Check corrective action in the fault code list.
Software error
Reset the AnSHCPU using the RUN/STOP
YES Can it be corrected?
NO Set the RUN/STOP keyswitch to the STOP position
Take corrective action.
Correct the cause of the error.
Set the RUN/STOP keyswitch to the RUN position.
YES
Does the ERROR LED come ON?
Consult your nearest Mitsubishi representative.
NO
End
11 - 6
Page 146
11. TROUBLESHOOTING 11.2.6
MELSEC-A
Flowchart used when the ERROR LED flashes The following shows the corrective measures when the ERROR LED flashes. The ERROR LED flashes.
Is "0" stored in special register D9124?
YES
NO Consult your nearest Mitsubishi representative. Reset the ON annunciator coil using a RST F[ ] instruction.
END
11 - 7
Page 147
11. TROUBLESHOOTING 11.2.7
MELSEC-A
Flowchart used when the output load of the output module does not come ON Output load does not come ON.
Is the indicator LED of the output module ON?
NO
Check the output state in monitor mode with the programmer.
YES
Is the indicator LED of the input module ON?
NO
Measure the voltage between the module input and COM terminal. 0V
YES
Is the voltage of the power supply for the load applied?
NO
Check the Input signal in monitor mode with the programmer.
(monitor signal OFF)
YES
Is voltage across the output module's output COM terminals as specified?
0V
Check the wiring load of the power supply for the load and restore the power.
Check external wiring and external input equipment.
Specified voltage Check the load wiring and load and restore the power.
Failure of output module. Replace output module.
Check rush current when the output load reaches the maximum number of simultaneous ON signals.
NG
Change the output relay number to adjust the rush current to comply with specifications.
Consult your nearest Mitsubishi representative.
OK
POINT If the input or load signals are not switched OFF, see Section 11.4 I/O Connection Troubleshooting and take corrective measures.
11 - 8
Specified voltage
Page 148
11. TROUBLESHOOTING 11.2.8
MELSEC-A
Flowchart used when a program cannot be written to the PC CPU The following shows the corrective measures when a program cannot be written to the PC CPU. Program cannot be written to the PC CPU
Is the RUN/STOP keyswitch set to STOP?
RUN
Set the RUN/STOP keyswitch to STOP
STOP
YES Can the program be written?
NO Replace the PC CPU.
NO
Is the memory protect switch OFF?
NO
YES Can the program be written?
Switch OFF the memory protect.(M.PRO OFF)
OFF NO
Is a ROM memory cassette used?
NO
Can the program be written?
YES
YES Replace the E2PROM memory cassette or use a built-in RAM
NO
Can the program be written?
YES
Counstult your nearest Mitsubishi representative. End