The text of a manual · part 22 of 29
AnS(H) CPU User's Manual: APPENDICES, pages 167 to 176
Pages 167 to 176 of 242, from AnS(H) CPU User's Manual
The original document is the PDF (3.1 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Mitsubishi A1S38
Page 167
APPENDICES
X
Y
M
L
S
B
F
T
C
D W R A0 A1 Z
V
Constant
Pointer
Levle
K
P
N
H
I n
Index
Word device
Subset
Available device Bit device
Number of steps
Automatic refresh parameter setting ............. RRPA Digit designation
1.1.3
MELSEC-A
Carry flag
Error flag
M9012
M9011
20
D
Command LEDA/LEDB
RRPA
SUB n
LEDC
D
LEDA·······Executed while ON LEDB·······Executed at leading edge LEDC······ Device number designated SUB·········Constant designated
LEDR
Automatic Refresh Parameter Data
(1)
Data to be set n
Head I/O number of object master module
D
Head number of devices which stores link parameters
Automatic refresh parameter setting items D +0
RX's head number
D + 1
AnSHCPU side refreshed device code
D + 2
AnSHCPU side refreshed device's head number
D + 3
Number of refresh points
D + 4
RY's head number
D + 5
AnSHCPU side refreshed device code
D + 6
AnSHCPU side refreshed device's head number
D + 7
Number of refresh points
D + 8
RW's head number
D + 9
AnSHCPU side refreshed device code
D +10
AnSHCPU side refreshed device's head number
D +11
Number of refresh points
D +12
SB's head number
D +13
AnSHCPU side refreshed device code
D +14
AnSHCPU side refreshed device's head number
D +15
Number of refresh points
D +16
SW's head number
D +17
AnSHCPU side refreshed device code
D +18
AnSHCPU side refreshed device's head number
D +19
Number of refresh points
APP - 11
RX refresh range setting
RY refresh range setting
RW refresh range setting
SB refresh range setting
SW refresh range setting
Page 168
APPENDICES
MELSEC-A (2)
Points for automatic refresh parameter area Automatic refresh parameter data occupies 20 points from D1 +0 to D1 +19. When there is a device on which automatic refresh will not be performed (RX, RY, RW, SB, SW), set "0" to its refreshed device code or number of refresh points.
(3)
Automatic refresh parameter settings
Item
Set data
Setting end
RX's head number
Set the head number of RX on the master/local module side.
RY's head number
Set the head number of RY on the master/local module side.
System User RWr : System
RW's head number
Set the head number of RW on the master/local module side.
SB's head number
Set the head number of SB on the master/local module side.
System
SW's head number
Set the head number of SW on the master/local module side.
System
RWw : User
Set the AnSHCPU side device with the following device code : AnSHCPU side refreshed device code
Device name
X
Y
M
B
T
C
D
W
R
Device code
1
2
3
4
5
6
7
8
9
User
0 : No automatic refresh setting AnSHCPU side refreshed Set the head device number on the AnSHCPU side. device's head number Number of refresh points
Set the number of points on which automatic refresh will be performed. 0 : No automatic refresh setting
APP - 12
User User
Page 169
APPENDICES
MELSEC-A
Functions
(1)
Set the devices and numbers of points on which automatic refresh will be performed between the AnSHCPU and master/local module. When the FROM/TO instruction is used to read/write data from/to the master/local module, the RRPA instruction need not be executed.
AnSHCPU Designation of device code
Master module
Designation of device's head number RX area
D +1,
RX
D +2
D +0
Refresh
[ D +3] points
RY
RY area D +5,
D +6
D +4
Refresh
[ D +7] points
RW
RW area D +9,
Refresh
D +10
D +8
RWr
RWr [ D +11] points
RWw
RWw SB
SB area D +13,
D +14
D +12
Refresh
[ D +15] points
SW
SW area D +17,
D +18
D +16
Refresh
[ D +19] points
(2)
When the RRPA instruction is executed, the automatic refresh settings are registered to the AnSHCPU and automatic refresh is performed between the AnSHCPU and master/local module.
(3)
The following table indicates whether refreshed devices may be set or not.
Refreshed device
Device code
Setting RX
RY
RW
SB
SW
X *1
1
ϒ
ϒ
ϒ
ϒ
ϒ
Y *1
2
ϒ
ϒ
ϒ
ϒ
ϒ
M (L, S)
3
ϒ
ϒ
ϒ
ϒ
ϒ
B *2
4
ϒ
ϒ
ϒ
ϒ
ϒ
T
5
ϒ
ϒ
ϒ
ϒ
ϒ
C
6
ϒ
ϒ
ϒ
ϒ
ϒ
D
7
ϒ
ϒ
ϒ
ϒ
ϒ
W *2
8
ϒ
ϒ
ϒ
ϒ
ϒ
R
9
ϒ
ϒ
ϒ
×
×
ϒ : May be set, × : Cannot be set
APP - 13
Page 170
APPENDICES
MELSEC-A REMARKS *1 : Set the range which is not being used by the main base, extension base and data link. *2 : Set B and W in the range not used by data link.
(4)
If the automatic refresh parameters are changed (RRPA instruction is executed) during RUN, new data is not used for control. When the AnSHCPU is switched to STOP/PAUSE, then to RUN, the new automatic refresh parameters are used for refreshing.
(5)
Set RWr and RWw areas in the RW area. Since the RWw area is set after the RWr area reserved for 64 stations, set RWw as shown below. RW area
RWr
Points for 64 stations [ D +11] points
RWw
(6)
Instructions for setting refreshed device in SB and SW (a)
In SB and SW, set refreshed devices within the specified number of points starting from the head number. SB0000 to SB003F are refreshed from the AnSHCPU to the master module, and SB0040 to SB00FF are refreshed from the master module to the AnSHCPU.
(b)
File registers (R) cannot be specified as refreshed devices in SB and SW. If file registers are set in SB or SW and written to the AnSHCPU, an instruction code error occurs and the AnSHCPU is inoperative.
(c)
The device range set for refreshed devices in SB or SW should not be specified as a latch range.
(d)
The SB and SW refresh ranges set with the RRPA instruction during power-on cannot be changed.
APP - 14
Page 171
APPENDICES Execution Conditions
MELSEC-A As shown below, when the LEDA instruction is used, the RRPA instruction is executed every scan while the write command is ON. When the LEDB instruction is used, the RRPA instruction is executed only one scan on the leading edge (OFF → ON) of the write command. Instruction Execution Step 0
Instruction Execution END
Step 0
Instruction Execution END
Step 0
Instruction Execution END
Step 0
Instruction Execution END
Step 0
Sequence program flow
Write command
ON OFF
RRPA (with LEDA)
RRPA (with LEDB)
Operation Errors
Any of the following conditions will result in an operation error and the error flag (M9011) switch on. Description
Error code D9008
D9092
50
503
The device code specified is 0 or other than 1 to 9 The head number of a bit device is not a multiple of 16 The number of refresh points is not a multiple of 16
Program Example
The following program sets the automatic refresh parameters to the master module of CC-Link allocated to I/O numbers 000 to 01F. (1)
Automatic refresh parameter settings and data storage devices Setting item
RX's head number
Set data
Data storage device
0
D1000
AnSHCPU side refreshed device code
X (1)
D1001
AnSHCPU side refreshed device's head number
A0H
D1002
Number of refresh points
32
D1003
RY's head number
0
D1004
AnSHCPU side refreshed device code
Y (2)
D1005
AnSHCPU side refreshed device's head number
A0H
D1006
Number of refresh points
48
D1007
RW's head number
0
D1008
D (7)
D1009
AnSHCPU side refreshed device code AnSHCPU side refreshed device's head number
160 (A0H)
D1010
Number of refresh points
272
D1011
SB's head number
0
D1012
M (3)
D1013
AnSHCPU side refreshed device code AnSHCPU side refreshed device's head number Number of refresh points SW's head number
160 (A0H)
D1014
256
D1015
0
D1016
AnSHCPU side refreshed device code
W (8)
D1017
AnSHCPU side refreshed device's head number
A0H
D1018
Number of refresh points
256
D1019
APP - 15
Page 172
APPENDICES
MELSEC-A (2)
Program example 0
X0020
P H 0000
D1000
RX's head number (0) setting
P H MOV 0001
D1001
"X" setting
MOV
P H MOV 00A0 D1002
A0H (XA0) setting
P K MOV 32
D1003
32 points setting
P H MOV 0000
D1004
RY's head number (0) setting
P H MOV 0002
D1005
"Y" setting
P H MOV 00A0 D1006
A0H (YA0) setting
P K MOV 48
D1007
48 points setting
P H MOV 0000
D1008
RW's head number (0) setting
P H MOV 0007
D1009
"D" setting
P H MOV 00A0 D1010
160 (D160) setting (160=A0H)
P K MOV 272
D1011
272 points setting
P H MOV 0000
D1012
SB's head number (0) setting
P H MOV 0003
D1013
"M" setting
P H MOV 00A0 D1014
160 (M160) setting (160=A0H)
P K MOV 256
D1015
256 points setting
P H MOV 0000
D1016
SW's head number (0) setting
MOV
P H 0007
D1017
"W" setting
MOV
P H 00A0 D1018
A0H (WA0) setting
MOV
P K 256
256 points setting
LEDB
D1019
RRPA SUB
K 0 RRPA instruction designation
LEDC D1000 LEDR CIRCUIT END
APP - 16
Page 173
APPENDICES
X
Y
M
L
S
B
F
T
C
D W R A0 A1 Z
V
Constant
Pointer
Levle
K
P
N
H
I
Index
Word device
Subset
Available device Bit device
Number of steps
Read from automatic updating buffer memory ······ RIFR Digit designation
1.1.4
MELSEC-A
Carry flag
Error flag
M9012
M9011 n1 n2 n3
29
D n4
Data to be set n1
Command LEDA/LEDB
RIFR
SUB n1
LEDC/SUB n2
LEDC/SUB n3
LEDC
D
LEDC/SUB n4
LEDA·······Executed while ON LEDB·······Executed at leading edge LEDC······ Device number designated SUB·········Constant designated n3
LEDR
Functions
(1)
n2
Head I/O number of object master module Read destination designation • Intelligent device station : Station numbers 1 to64 (only when the host station is the master station) • Random access buffer : FFH Intelligent device station's sending/receiving buffer address specified in master station (Specify the offset address)
D
Device which will store the read data n4
Number of points read : 1 to 8192
Reads the points of data specified at n4 from the automatic updating buffer memory address specified at n3 for the station having the station number specified at n2 in the master module specified at n1 and stores that data into the devices starting from the one specified at D . RIFR instruction execution range
AnSHCPU
Mater station
Intelligent device /local station n2 n1
RIFR instruction n3
D
Specified device n4
APP - 17
Automatic updating buffer memory
Transferred when data is updated
Page 174
APPENDICES
Execution Conditions
MELSEC-A (2)
When executed, the RIFR instruction reads data from the automatic updating buffer of the master module.
(3)
Up to 8192 points may be read by the RIFR instruction.
(4)
To set the number of automatic updating buffer memory points, make the automatic updating buffer size setting using the network parameter instruction (RLPA instruction).
As shown below, when the LEDA instruction is used, the RIFR instruction is executed every scan while the read command is ON. When the LEDB instruction is used, the RIFR instruction is executed only one scan on the leading edge (OFF → ON) of the read command. Instruction execution Step 0
Instruction execution END
Step 0
Instruction execution END
Step 0
Instruction execution END
Step 0
Instruction execution END
Step 0
Sequence program flow
Read command
ON OFF
RIFR (with LEDA)
RIFR (with LEDB)
Operation Errors
Either of the following conditions will result in an operation error and the error flag (M9011) switch on. Description
Error code
The buffer address specified is outside the range of automatic updating buffer memory designation range.
D9008
D9092
50
503
The number of refresh points is greater than 8192.
Program Examples
The following program reads 11 points of data to D100 and thereafter from 400H of the automatic updating buffer memory set to station number 1 in the master module of CC-Link allocated to I/O numbers 000 to 01F. 0
X0020
LEDB RIFR SUB
H 0000
SUB
K 1
SUB
H 0400
LEDC
D100
SUB
K 11 LEDR
CIRCUIT END
APP - 18
RIFR instruction designation
Page 175
APPENDICES
X
Y
M
L
S
B
F
T
C
D W R A0 A1 Z
V
Constant
Pointer
Levle
K
P
N
H
I
Index
Word device
Subset
Available device Bit device
Number of steps
Write to automatic updating buffer memory ............RITO Digit designation
1.1.5
MELSEC-A
Carry flag
Error flag
M9012
M9011 n1 n2 n3
29
D n4
Data to be set n1
Command LEDA/LEDB
RITO
SUB n1
LEDC/SUB n2
LEDC/SUB n3
LEDC
D
LEDC/SUB n4
LEDA·······Executed while ON LEDB·······Executed at leading edge LEDC······ Device number designated SUB·········Constant designated n3
LEDR
Functions
(1)
n2
Head I/O number of object master module Write destination designation • Intelligent device station : Station numbers 1 to 64 (only when the host station is the master station) • Random access buffer : FFH Intelligent device station's sending/receiving buffer address specified in master station (Specify the offset address)
D
Device which will store the written data n4
Number of points written : 1 to 8192
Writes the points of data specified at n4 from the devices beginning with the one specified at D to the automatic updating buffer memory addresses beginning with the specified one at n3 for the station having the station number specified at n2 in the master module specified at n1 . RITO instruction execution range
AnSHCPU
Mater station
Intelligent device /local station n2 n1
RITO instruction n3 D
Specified device n4
APP - 19
Automatic updating buffer memory
Transferred when data is updated
Page 176
APPENDICES
Execution Conditions
MELSEC-A (2)
When executed, the RITO instruction writes data.
(3)
Up to 8192 points may be written by the RITO instruction.
(4)
To set the number of automatic updating buffer memory points, make the automatic updating buffer size setting using the network parameter instruction (RLPA instruction).
As shown below, when the LEDA instruction is used, the RITO instruction is executed every scan while the write command is ON. When the LEDB instruction is used, the RITO instruction is executed only one scan on the leading edge (OFF → ON) of the write command. Instruction Execution Step 0
Instruction Execution END
Step 0
Instruction Execution END
Step 0
Instruction Execution END
Step 0
Instruction Execution END
Step 0
Sequence program flow
Write command
ON OFF
RITO (with LEDA)
RITO (wth LEDB)
Operation Errors
Either of the following conditions will result in an operation error and the error flag (M9011) switch on. Description
The buffer address specified is outside the range of automatic updating buffer memory designation range. The number of refresh points is greater than 8192.
APP - 20
Error code D9008
D9092
50
503