Summary

What is in it

The instruction manual for the Mitsubishi MELSEC F-12R and F-20M compact programmable controllers and their extension units. It explains the F series model naming and output types, mounting on a panel or DIN rail, power supply and grounding, wiring inputs and outputs, connecting an extension unit, sink and source input handling, relay, SSR and transistor output handling, maintenance and diagnostics, and outlines and specifications. Programming with the F-20P-E is covered in a separate manual.

Its parts

  1. Input Handling
  2. Output Handling
  3. Maintenance and Diagnostics
  4. Outlines and Specifications

From the manual · read page by page

Key facts from this manual

Some pages are scans or cannot be read; this says only what the readable text supports. Each line names its page in the PDF.

Instruction manual for the Mitsubishi MELSEC F-12R and F-20M programmable controllers of the F series and their extension units. It covers installation, power and I/O wiring, extension units, battery and relay board replacement, LED diagnostics and specifications. Programming with the F-20P-E programmer unit is covered in a separate manual.

Device
F-12R: relay output base unit of the F series, compatible with the F-20 and its peripherals except that the ROM function is not available p. 3
I/O points
F-12R base unit: 6 inputs and 6 outputs; F-10ER extension unit: 4 inputs and 6 outputs p. 17
Supply voltage
U type: 90 to 132VAC, 50/60Hz; ES type: 220 to 240VAC +10% -15%, 50/60Hz; D and DS types: 24VDC p. 17
Power consumption
Base unit less than 11VA, extension unit less than 6VA, not counting external loads p. 5, 17
Inputs
Photocoupler isolated, 24VDC: 8mA per input on sink input (U) units, 6mA on source input (ES) units p. 8, 9, 17
Relay outputs
Normally open contacts, 2A at 24VDC, 110/120VAC or 220/240VAC (resistive load) p. 10
Program
320 steps, relay symbols with 14 instructions, average 0.1ms per step p. 17
Timers and counters
8 on-delay timers (0.1 to 9.9s or 1 to 99s); 8 power-failure compensated down-counters p. 17
Auxiliary relays
64, of which 16 are battery backed p. 17
Battery
F-20BC non-chargeable lithium battery, replace every five years p. 13
Extension
F-12R: F-10ER relay extension unit, joined by the 300mm cable supplied with the extension unit p. 3, 4
Peripherals
Programming panel F-20P-E, program loader F-20H, remote cable F-20P-CAB p. 3
Mounting
Screws through four corner holes, or DIN rail with the F-20D attachment (for F-10, 12, 20) p. 3, 4
Weight
F-12R and F-10ER: approx. 1.3 kg; F-20 units: approx. 1.5 kg p. 17

What this manual walks you through

  • Mounting on a flat surface or DIN rail p. 4
  • Wiring power, earth and the RUN/STOP switch p. 5
  • Routing input and output wiring p. 6
  • Connecting an extension unit p. 7
  • Wiring sink and source inputs p. 8, 9
  • Wiring relay, SSR and transistor outputs p. 10, 11, 12
  • Replacing the backup battery p. 13
  • Preliminary checks and LED diagnostics p. 14
  • Replacing the relay output board p. 15
  • Measuring insulation resistance p. 15

Good to know

  • When replacing the battery, power must be off and the swap must be done within 30 seconds while a capacitor holds the program memory. p. 13
  • A DC powered model and an AC powered model cannot be paired as base unit and extension unit. p. 7
  • Do not power proximity switches from the 24V input terminals; use an external 16 to 36VDC source. p. 9
  • An input pulse shorter than 50 milliseconds may not be accepted. p. 8
  • Leave about 30mm of space around the unit for heat dissipation. p. 4

Questions this manual answers

How many inputs and outputs does the F-12R have?

The F-12R base unit has 6 inputs and 6 outputs; an F-10ER extension unit adds 4 inputs and 6 outputs. p. 17

What battery does the F-12R use?

A non-chargeable lithium battery, list number F-20BC, which backs the program memory, counters and 16 auxiliary relays; replace it every five years or when the battery LED lights. p. 13, 14

Can the F-12R use a ROM cassette?

No. The F-12R is compatible with the F-20 and its peripherals, but the ROM function is not available. p. 3

What happens to the F-12R during a short power failure?

Operation continues if the failure lasts less than 20ms. A longer failure turns all outputs off and resets the timers, while counters and 16 auxiliary relays are kept by the battery. p. 5, 17

What does the battery LED on the F-12R mean?

It lights when the battery runs low; renew the battery. p. 13, 14

The whole text · 2 parts

Read the manual here as text

Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.

  1. Pages 1 to 101-10
  2. Pages 11 to 2011-20

The file

Size and text

PublisherMitsubishi Electric Corporation
Pages20
PDF659 KB
TextThe pages are scans; their text was read by OCR, which may hold reading errors.

The first pages · 3 of 20

Look before you download

Each page opens the PDF at that page.

Page 1
Page 1of 20
Page 2
Page 2of 20
Page 3
Page 3of 20