Manual · Mitsubishi
MELSEC F-12R, F-20M Programmable Controller Instruction Manual
Manual20 pagesPDF 659 KB
Instruction manual for the Mitsubishi MELSEC F-12R and F-20M programmable controllers and extension units: installation, wiring and specifications.
Covers · 1 model
The models it covers
Summary
What is in it
The instruction manual for the Mitsubishi MELSEC F-12R and F-20M compact programmable controllers and their extension units. It explains the F series model naming and output types, mounting on a panel or DIN rail, power supply and grounding, wiring inputs and outputs, connecting an extension unit, sink and source input handling, relay, SSR and transistor output handling, maintenance and diagnostics, and outlines and specifications. Programming with the F-20P-E is covered in a separate manual.
Its parts
- Input Handling
- Output Handling
- Maintenance and Diagnostics
- Outlines and Specifications
From the manual · read page by page
Key facts from this manual
Some pages are scans or cannot be read; this says only what the readable text supports. Each line names its page in the PDF.
Instruction manual for the Mitsubishi MELSEC F-12R and F-20M programmable controllers of the F series and their extension units. It covers installation, power and I/O wiring, extension units, battery and relay board replacement, LED diagnostics and specifications. Programming with the F-20P-E programmer unit is covered in a separate manual.
- Device
- F-12R: relay output base unit of the F series, compatible with the F-20 and its peripherals except that the ROM function is not available p. 3
- I/O points
- F-12R base unit: 6 inputs and 6 outputs; F-10ER extension unit: 4 inputs and 6 outputs p. 17
- Supply voltage
- U type: 90 to 132VAC, 50/60Hz; ES type: 220 to 240VAC +10% -15%, 50/60Hz; D and DS types: 24VDC p. 17
- Power consumption
- Base unit less than 11VA, extension unit less than 6VA, not counting external loads p. 5, 17
- Inputs
- Photocoupler isolated, 24VDC: 8mA per input on sink input (U) units, 6mA on source input (ES) units p. 8, 9, 17
- Relay outputs
- Normally open contacts, 2A at 24VDC, 110/120VAC or 220/240VAC (resistive load) p. 10
- Program
- 320 steps, relay symbols with 14 instructions, average 0.1ms per step p. 17
- Timers and counters
- 8 on-delay timers (0.1 to 9.9s or 1 to 99s); 8 power-failure compensated down-counters p. 17
- Auxiliary relays
- 64, of which 16 are battery backed p. 17
- Battery
- F-20BC non-chargeable lithium battery, replace every five years p. 13
- Extension
- F-12R: F-10ER relay extension unit, joined by the 300mm cable supplied with the extension unit p. 3, 4
- Peripherals
- Programming panel F-20P-E, program loader F-20H, remote cable F-20P-CAB p. 3
- Mounting
- Screws through four corner holes, or DIN rail with the F-20D attachment (for F-10, 12, 20) p. 3, 4
- Weight
- F-12R and F-10ER: approx. 1.3 kg; F-20 units: approx. 1.5 kg p. 17
What this manual walks you through
- Mounting on a flat surface or DIN rail p. 4
- Wiring power, earth and the RUN/STOP switch p. 5
- Routing input and output wiring p. 6
- Connecting an extension unit p. 7
- Wiring sink and source inputs p. 8, 9
- Wiring relay, SSR and transistor outputs p. 10, 11, 12
- Replacing the backup battery p. 13
- Preliminary checks and LED diagnostics p. 14
- Replacing the relay output board p. 15
- Measuring insulation resistance p. 15
Good to know
- When replacing the battery, power must be off and the swap must be done within 30 seconds while a capacitor holds the program memory. p. 13
- A DC powered model and an AC powered model cannot be paired as base unit and extension unit. p. 7
- Do not power proximity switches from the 24V input terminals; use an external 16 to 36VDC source. p. 9
- An input pulse shorter than 50 milliseconds may not be accepted. p. 8
- Leave about 30mm of space around the unit for heat dissipation. p. 4
Questions this manual answers
How many inputs and outputs does the F-12R have?
The F-12R base unit has 6 inputs and 6 outputs; an F-10ER extension unit adds 4 inputs and 6 outputs. p. 17
What battery does the F-12R use?
A non-chargeable lithium battery, list number F-20BC, which backs the program memory, counters and 16 auxiliary relays; replace it every five years or when the battery LED lights. p. 13, 14
Can the F-12R use a ROM cassette?
No. The F-12R is compatible with the F-20 and its peripherals, but the ROM function is not available. p. 3
The whole text · 2 parts
Read the manual here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.
The file