The text of a manual · part 2 of 2
MELSEC F-12R, F-20M Programmable Controller Instruction Manual, pages 11 to 20
Pages 11 to 20 of 20
The original document is the PDF (659 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Mitsubishi F-12R
Page 11
| Output Handling
| SSR Output Type {F-200S-00)
Basic Unit F-20MS Output 30 ~ 37 eccal can 8 2y
[elelelelelerelslélelele)
Oo |o Go 2 olelererelelele) my C3 r34]
Ei aslsslceleeieeleoleleles
@@[@l P]
Extension Unit F-20ES Gutput 40 ~ 47 o}o}o; o
20000000 34.88.36, bn g Gelepleleleelebleblelslee[ela1 &1
é
Fuse
é
Fuse
@) @ ees <
Parailel Small load Resistance boon a“
| DESCRIPTION // | [cCauTION //
1. Connect external load devices e.g. contactors, pilot 1. Each triac (SSR) inside the unit will withstand lamps, solenoid (electromagnetic) valves etc., to moderate surge currents, and is protected by a residu-output terminations 30 to 37 of the base unit and 40 al current circuit. With the triac ‘off’ current leakage to 47 of the extension unit (where used). is less than 1.2mA at AC120V or 2,2mA at AC220V,
2. The load limitation of the triac (SSR) outputs is 1A However it is possible that this might have some for each individual output, but the total collective effect on external loads. output load should no exceed 4A across all eight out- 2, It is not possible to operate triac output card on puts at AC110/120V or AC220/240V. DC loads.
3. For inductance loads, the rated coil fo magnetic 3. 2A rated back-up fuses or cireuit protectors are re-contactors should be within 50VA at AC110/120V commended per each 4 outputs to prevent damage to or 100VA at AC220/240V. If the coil load is over the circuit boards of the PC in the event of a short these limits then an external relay will be required. circuit fault in one of the external circults.
4. For lamp loads above 100W then an external relay 4. Overload Protection will also be required,
Back-up fuses or circuit protectors are recommended on output circuits to prevent damage to the circuit boards of the PC in the event of a short circuit fault in an external output circuit.
Page 12
[Output Handling|
|
[elelelelelarerererol ele]
Transistor Output Type {F-200T-00)
Sink Output Models (F-20MT-U F-20MT-ES) ojialolo ie F-20ET-Li F-20ET-ES
0000 pezav 30.3 46 36°97 BenVD)
oi | sebRslslels(swlelelels BeIs|e)
Ue? Ol @
= DC 24V 4 External ‘ Power Supply : é Fuse ; Fuse * Blank Terminal t Source Output Models [ololelelelelerelelolelo mm te -20MT- ESS, F-20ET-ESS aloie 08 oevv® 39 3 5 36.37 Oo Outpat] | [gle silsisleissisieslelslaalele fo] el? Ul @
DC zay =
{f=
External Power Supply é Fuse p Fuse
* Blank Terminal
| DISCRIPTION //
[CAUTION = //
1. The external DC power supply should be DC24V
1. Connect external load devices e.g., contactors, pilot
AY fr.
lamps, solenoid (electromagnetic) valves etc., to output terminations 30 to 37 of the base unit and 40, 47 of the extension unit (where used}.
. The load limitation of the NPN transistor outputs is 1A for each individual output, but the total collective output load should net exceed 4A across all eight outputs at DC24V.
. Bue to surge current limitations lamp loads should be within 3W,
. When other load are connected to a output termination in addition to lamp load, the total collective output load should be as specified with reference to foi-lowing table. .
Lamp Load Additional Load 2W 6W iW T6W 0 7 24w
+15%, 30%.
. 2A rated back-up fuses or protectors are recommended per each 4 outputs to prevent damage to the circuit boards of the PC in the event of a short circuit fault in one of the external circuits.
. Overload Protection
Back-up fuses or circuit protectors are recommended on output circuits to prevent damage to the circuit boards of the PC in the event of a short circuit fault in an external output circuit.
Page 13
Maintenance and Diagnostics
Battery Maintenance
1. The program memory, counters and 16 of the 64 auxilliary relays are backed by a non-chargeable lithium battery (list no: F-20BC},
2. When the battery runs low, LED indicator on the base unit is ifluminated. (See next page}.
3. However, regardless of its condition, it is recommended that the battery be replaced every five years.
BATTERY RENEWAL: Battery is renewed by the following procedure.
. 1 Remove covers for extension cable, ROM cassette and Programming Panel connecter.
4 Remove a retaining screw for battery holder and pull out the battery together with holder, connector and installation screw.
2 Remove 2 screws at both ends of upper cover,
3 Take off upper cover.
5 Renew the battery set together with holder and connecting lead. Service battery is supplied with battery holder and connecting lead in a set.
6 Re-assemb!e the installation screw and upper cover of the unit in reverse of the procedure,
CAUTION:
1. Disconnection of existing battery and connection of new battery must be completed within 30 seconds, whilst an inside capacitor supports the program memory.
2. Ensure that power is off during battery replacement.
Page 14
PRELIMINARY CHECKS
Before operating the unit, it is advisable to carry out the following checks:
a, That the power and earth leads are properly connected.
b. That input and output leads are properly connected and not entangled. {It is worthwhile numbering each lead according to its input and output assignment}.
c. That output loads and input contacts are within the specification limits detailed earlier.
DIAGNOSTICS
The base unit’s LEDs enable the following conditions to be checked:
1. Power Supply LED illumination indicates that the power is ‘on’, lf the LED fails to illuminate when the unit is under apparent power, then the unit may be faulty.
2. Run If the run LED is not ifluminated when the programming panel! is turned to ‘monitor’ and the unit is in ‘run’ mode then (assuming all wiring connections to be correct}, it is likely the unit is faulty.
3. Battery lf the battery LED illuminates then renew the battery.
4. Interference from external apparatus lf the ‘cpu error’ LED Hluminates this may be as a result of electrical noise interference from some external apparatus. Otherwise it indicates a fault in the unit.
Battery Voltage Charge Indicator
/[8|e[2]9\e12] - /8| © eoongon0opn0gg Input Indicator ~~
Power Supply Indicator, T ° P 9 | 6 @]
Output Indicator -. Jog ob000
\ (slelelelelsiciels) O
RUN Indicator CPU Error Indicator
5. Input circuit operation
Failure of the input LEDs to iNuminate when properly connected and powered may be fault of the unit,
. Outputs lf outputs fail to function, whether the LEDs are illuminated, it may be a unit fault. However, in the case of those units fitted with relay outputs the life of the relay is stated in the section of Relay Output. If the unit has exceeded this number of operations or the output relays are obviously worn out then 4 replacement relay board should be fitted as detailed in the next section.
Page 15
Checking the Programme
Programmes can be checked and monitored by using the facility available on the programming panel for this purpose. Maintenance Periodically the unit's installation should be checked to ensure that it has not been contaminated by dust or other contaminants, also that all-termination connections are still tight. The unit should not be installed in a situation where the temperature is likely to rise to above 50°C. Relay Board Replacement The relay output board can be changed as follows:
Remove the front cover with same procedure in the section of battery renewai, and renew the relay board as illustrated: .
: A See es
Remove front cover Remove mounting screws for Remove mounting screws for board terminal box
Insulation in order to measure the insulation resistance of the programmable controller, first remove all terminal leads and take measurements between the earth and other required terminats.
Page 16
Outlines (mm) : SPE *F-12R Base Unit and F-1OER Extension Unit
4, 4.5 (hole} M3 Terminal Screw, _ Val |-@ ++ | Oo; 2 ml 3 » ie 4 155 mens 165 100 ¢ * F-20 Base Unit and Extension Unit 4-45 (hole) M3 Terminal Screw t ® =a, _ C o| Oo Mm] oO [ | @- | o = 240 mach 255 100 P t *F-20P-E programming unit P T g | | E
B ie s | = W
Page 17
SPECIFICATIONS
Voltage Main voltage
D,DS: 24VDC + - 8V U: 90 ~ 132VAC, 50/60Hz with LED indication ES: 220 ~ 240VAC +10% - 15%, 50/60Hz
Consumption
BU: Lessthan 11VA EU: Less than 6VA
Number of points
F-t2R BU: 6 Points F-10ER EU: 4 Points F-20 BU and EU: 12 Points
Input Type and method
No-voliage contact, Photocoupler isolated
Current and voltage
ES: 6mA/24VDC U: BmA/24VDC
Indication
LED, all inputs
Number of points
F-12R BU: 6 Points F-10ER EU: 6 Points F-20 BU and EU: & Points
Indication LED, all outputs Output type R* s* T Output Method No-waltage Triac (SSR) Transistor * ro eaea 1A/110/ (Except PaOER yen sae Current and vaitage 220/240VAC 120VAC 1A/DC24 (Resistance 220/240V AC Load} Number of points BU: 8 Points Timer Type and method Digital, set by PP, on-delay timer Range 0.1 ~9.9s or 1 ~ 99s Number of points BU: 8 Points Counter Type and method Digital, set by PP, down-counter, Power-failure compensated Setting range i~99 tla Number of points BU: 64 Points (Included 16 Points of battery back-up) Method Stored program Language Relay symbals, 14 instructions Memory C-MOS RAM + EP-ROM (Option) Program Capacity 320 steps Speed Average: 0.1ms/step {Version 1:0.05ms} Write in by key of PP compensation Operation continues if failure duration is less than 20ms Battery Lithium, capable of 5-year RAM backup Self-diagnosic functions Battery voltage-drop indication, CPU error indication Protection Insulation resistance More than 5M&2, SOOV DC between terminals and earth (Except D, DS type)
Insulation withstand voltage
1,500VAC, Imin
Noise immunity
1,000V, 1yusec Verified using a noise simulator
Noise Spike Withstand NEMA noise spike test (VEMA-ICS2-230) Ambient-temperature O~ 55°C Storage temperature, 15 ~ 68°C
Environment ,, Ambient humidity
Less than 95% RH, no condensation
Vibration resistance
10 ~ 55Hz, 0.5mm (max.: 2G}
Dimensions Wx Hx D (mm)
See the outlines
Weight kg
F-12R/F-10ER: approx. 1.3 kg F-20 BU/EU: approx. 1.5 kg
PP: Programming panel BU; Basic Unit EU: Extension Unit
U: AC 110/120V Type R: Relay Output Type ES: AC 220/240V Type S: SSR Output Type D, DS: DC 24V Type T: Transistor Output Type
Page 18
MEMO
Page 19
Page 20
a'a MITSUBISHI ELECTRIC CORPORATION
HEAD OFFICE MITSUBISHI DENK] BLDG, MARUNOUCHI, TOKYO 100. TELEX J24532 CABLE MELCO TOKYO
The specifications and designs are
329900207 -01B Printed in Japan (ROD} subject to change without notice.